Solenoid disabling function (-NP)
PVEH-NP and PVEA-NP have a build in feature that disables the solenoids by US at 50% and gives a
feedback on the solenoid status. This is done to facilitate application monitoring. The fault monitoring is
still activated but the closed loop will remain passive until the control signal shifts.
US disable range
48 % U
DC
to 52 % U
DC
Solenoid disable reaction time
From active to passive
750 ms <-> 1000 ms
From passive to active
0 ms <-> 50 ms
Solenoid feedback signal
Maximum load
50 mA
Voltage if solenoid active by load 20
mA
> U
DC
– 1.5 V
Voltage if solenoid active by load 50
mA
> U
DC
– 2.0 V
Voltage if solenoid passive
< 1 V
PVEH-F (six pin) has also the disable function but not the feedback. Our general recommendation is
disabling of PVE that are not in active use.
Solenoid disabling function (-NP) curves
U
DC
U
S
Ground
S
fb
Technical Information
PVE, Series 4 for PVG 32/100/120 and PVHC
Safety and monitoring
18
520L0553 • Rev GD • Jan 2014