manualshive.com logo in svg
background image

Instructions

  •   Avoid material entering into the system while 

cutting  tubes.  Never  drill  holes  where  burrs 

cannot be removed.

  •   Braze with great care using state-of-the-art tech-

nique and vent piping with nitrogen gas flow.

  •   Connect the required safety and control de-

vices. When the schrader port is used for this, 

remove the internal valve.

  •   The  liquid  injection  valve  must  be  fed  by  li-

quid, picked-up on the liquid line of the sys-

tem, downstream the filter drier. 

  •   Protect the compressor and the liquid injec-

tion  valve  against  heat  while  brazing  the  li-

quid line. 

5 – Leak detection

  Never  pressurize  the  circuit  with  oxygen  or 

dry air. This could cause fire or explosion.

  •   Pressurize the system on HP side first and then 

on LP side. Never let the pressure on LP side ex-

ceed the pressure on HP side with more than 5 

bar. Such pressure difference could cause inter-

nal compressor damage.

  •   Do not use dye for leak detection.

  •   Perform a leak detection test on the complete 

system.

  •   The test pressure must not exceed : 

Models

LP side HP side

PSH 019.023.026.030.034.039

33 bar  45 bar 

 

  •   When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

  •   Never  use  the  compressor  to  evacuate  the 

system.

  •   Connect a vacuum pump to both the LP & HP 

sides.

  •   Pull down the system under a vacuum of 500 

µm Hg (0.67 mbar) absolute.

  •   Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

 

  •   Switch off and isolate the main power supply. 

  •   All  electrical  components  must  be  selected  as 

per  local  standards  and  compressor  require-

ments.

  •   The Performer® scroll compressor only works 

correctly  in  one  rotation  direction.  Line 

phases L1, L2, L3 must absolutely be connec-

ted  to  compressor  terminals  T1,  T2,  T3  to 

avoid reverse rotation.

  •   Use ø 4.8 mm (3/16”) screws and ¼” ring ter-

minals for the power connection. Fasten with 

3 Nm torque.

  •   The compressor must be connected to earth 

with the 5 mm earth terminal screw.

  •   Connect  the  discharge  temperature  sensor 

cable plug to OCS.

  •   Connect the OCS to power supply and earth

 To avoid personal injury, with 230V OCS, do 

not forget to connect the earth, and to check for 

earth continuity.

8 – Filling the system

  •   Keep the compressor switched off.

  •   Fill  the  refrigerant  in  liquid  phase  into  the 

condenser or liquid receiver. The charge must 

be as close as possible to the nominal system 

charge to avoid low pressure operation and ex-

cessive superheat. Never let the pressure on LP 

side exceed the pressure on HP side with more 

than  5  bar.  Such  pressure  difference  could 

cause internal compressor damage.

  •   Keep the refrigerant charge below the indica-

ted charge limits if possible. Above this limit; 

protect the compressor against liquid flood-

back with a pump-down cycle or suction line 

accumulator.

  •   Never leave the filling cylinder connected to 

the circuit.

Compressor models

Refrigerant 

charge limit (kg)

PSH019

5.9

PSH023.026.030.034.039

7.9

 

9 – Verification before commissioning

  Use  safety  devices  such  as  safety  pressure 

switch  and  mechanical  relief  valve  in  com-

pliance  with  both  generally  and  locally  appli-

cable  regulations  and  safety  standards.  Ensure 

that they are operational and properly set. 

  Check  that  the  settings  of  high-pressure 

switches  and  relief  valves  don’t  exceed  the 

maximum service pressure of any system com-

ponent.

  •   A  low-pressure  switch  is  recommended  to 

avoid  vacuum  operation.  Minimum  setting 

for PSH: 1.6 bar (absolute).

  •   Verify that all electrical connections are pro-

perly  fastened  and  in  compliance  with  local 

regulations.

  •   Ensure that the liquid injection valve (LIV) coil 

is correctly positioned on the LIV body: one of 

the lock pins on the coil must fit into one of 

the dents on the valve body.

  •   When  a  crankcase  heater  is  required,  it 

must  be  energized  at  least  12  hours  before 

initial  start-up  and  start-up  after  prolonged 

shutdown for belt type crankcase heaters (6 

hours for surface sump heaters).

10 – Start-up

  •   Never start the compressor when no refrige-

rant is charged.

  •   All service valves must be in the open position.

  •   Balance the HP/LP pressure.

  •   Energize  the  compressor.  It  must  start 

promptly.  If  the  compressor  does  not  start, 

check wiring conformity and voltage on ter-

minals.

  •   If the internal overload protector trips out, it 

must cool down to 60°C to reset. Depending 

on ambient temperature, this may take up to 

several hours.

11 – Check with running compressor

  •   Check current draw and voltage.

  •   Check  suction  superheat  to  reduce  risk  of 

slugging.

  •   Observe  the  oil  level  in  the  sight  glass  for 

about 60 minutes to ensure proper oil return 

to the compressor.

  •    Check all tubes for abnormal vibration. Move-

ments in excess of 1.5 mm require corrective 

measures such as tube brackets.

  •   When  needed,  additional  refrigerant  in  liquid 

phase may be added in the low-pressure side as 

far as possible from the compressor. The com-

pressor must be operating during this process.

  •   Do not overcharge the system.

  •   Never release refrigerant to atmosphere.

  •   Before leaving the installation site, carry out 

a  general  installation  inspection  regarding 

cleanliness, noise and leak detection.

  •   Record type and amount of refrigerant charge 

as well as operating conditions as a reference 

for future inspections.

12 – Maintenance

  Internal  pressure  and  surface  temperature 

are dangerous and may cause permanent injury.

Maintenance  operators  and  installers  require 

appropriate skills and tools. Tubing temperature 

may exceed 100°C and can cause severe burns.

  Ensure  that  periodic  service  inspections  to 

ensure system reliability and as required by local 

regulations are performed.

To prevent system related compressor problems, 

following periodic maintenance is recommended:

  •    Verify that safety devices are operational and 

properly set.

  •    Ensure that the system is leak tight.

  •    Check the compressor current draw.

  •    Confirm that the system is operating in a way 

consistent  with  previous  maintenance  re-

cords and ambient conditions.

  •    Check  that  all  electrical  connections  are  still 

adequately fastened.

  •    Keep the compressor clean and verify the ab-

sence of rust and oxidation on the compres-

sor shell, tubes and electrical connections.

13 - Warranty

Always transmit the model number and serial number 

with any claim filed regarding this product.

The product warranty may be void in following cases:

  •    Absence of nameplate.

  •    External  modifications;  in  particular,  drilling, 

welding, broken feet and shock marks.

  •    Compressor opened or returned unsealed.

  •    Rust,  water  or  leak  detection  dye  inside  the 

compressor.

  •    Use of a refrigerant or lubricant not approved 

by Danfoss.

  •    Any  deviation  from  recommended  instruc-

tions pertaining to installation, application or 

maintenance.

  •    Use in mobile applications.

  •    Use in explosive atmospheric environment.

  •    No model number or serial number transmit-

ted with the warranty claim.

14 – Disposal

Danfoss recommends that compressors 

and compressor oil should be recycled 

by a suitable company at its site.

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on 

order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.

All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

FRCC.EI.020.A1.02 - February 2012 

Copyright Danfoss Commercial Compressors - DSS - 02/12

Отзывы: