A/D refresh rate
PLUS+1
®
module
A/D refresh rate
MC012-110/112
All: 1.00 ms
MC024-110/112
All: 1.00 ms
MC024-120/122
All: 1.00 ms
MC050-110/112
All: 1.00 ms
MC050-120/122
All: 1.00 ms
MC050-155/15B
All: 1.00 ms
IOX012-110
Refresh rate is a function of CAN message frequency
IOX024-120
Refresh rate is a function of CAN message frequency
AIN/Temp/Rheo; Din/AIN/FreqIN/Rheo
Analog/Temperature/Rheostat (AIN/Temp/Rheo);
Digital/Analog/Frequency/Rheostat (Din/AIN/FreqIN/Rheo)
When configured as a resistance/rheostat/temp sensor input, the device will provide up to 3.76 mA
current to an external load which can then be measured. The equation for calculating AD counts for a
given load is: AD counts = (30996 x RL / (RL + 1322)). The following chart shows the relationship between
AD counts and load.
Rheostat inputs
The following chart shows the relationship between load resistance versus worst case error over the full
operating temperature -40° C to 70° C (-40° F to 158° F).
Technical Information
PLUS+1® MC0XX-1XX Controller Family
Inputs/outputs types and specifications
10 |
©
Danfoss | April 2018
L1321895 | BC00000227en-US0401