Discharge line
Insulation
Bracket
Thermostat
35
accessoRies
compressor model
attenuation*
(at 50Hz) dB(a)
Hood code number
SM / SZ 084 - 090 - 100
7
7755011
SM / SZ 110 - 120
8.5
7755010
SM / SZ 115 - 125
8
7755009
SM / SZ 160
8
7755008
SM / SZ 148 - 161**
8
7755017
SM / SZ 175 - 185
8
7755007
SY / SZ 240 - 300
7
7755016
SY / SZ 380
7
7755022
* Attenuation of compressor sound power level measured in free space
** Not available for code 3 version compressors
Discharge gas temperature must not
exceed 275°F.
The discharge gas thermostat acces-
sory kit includes all components
required for installation as shown
below. The thermostat must be
attached to the discharge line within
6” of the compressor discharge port.
Discharge thermostat kit code
number: 7750009.
Acoustic compressor hoods have been
developed to meet specific extra-low
noise requirements. These hoods
incorporate soundproofing materials
and offer excellent high and low
frequency attenuation.
discharge temperature
protection
compressor acoustic
hoods