These Performer® compressors
are protected against overheating
and overloading by an internal
safety motor protector. However,
an external manual reset overload
protector is recommended for
protecting the circuit against over-
current.
These Performer® compressors
are provided with a bimetallic sin-
gle pole single throw thermostat
which is located in the motor win-
dings. Because the thermostat is
an automatic reset device, it must
be wired in a lockout safety circuit
with a manual reset to restart the
unit. For over-current protection,
an external manual reset overload
protector must be used.
The “must trip” value of these
overload relays must be set in ac-
cordance with power line sizing
and design and shall never exceed
the “A max.” value stamped on the
nameplate.
These Performer® compressors
motors are protected by an ex-
ternal module protecting against
phase loss/reversal, over heating
and high current draw.
Instructions