Instructions
Pilot-controlled PCVQ DN 100 - DN 250 (PN 16, PN 25)
9.3 Dismounting, Mounting
Actuator AVP-F
9.4 Replacement of Trim
Valve AVP-F
Dismounting
1. Dismount impulse tubes.
2. Loosen union nut
1
.
3. Remove actuator.
Mounting
1. Place actuator at the valve and align,
observe position of the impulse tube
connections.
2. Screw on union nut
1
and tighten,
torque 100 Nm.
AVP-F DN 25
AVP-F DN 40
Dismounting
1. Unscrew actuator (see above).
2. Unscrew trim 2.
DN 25: with pipe tongs, wrap gum strips
around the trim
DN 40: with wrench SW 55
3. Pull out trim.
Mounting
Mounting is carried out in reverse order. Only
tighten with low torque, sealing is made with
O rings.
9
Replacement of Valve,
Actuator, Trims