Coil
0
1
33
Control not ready
Control ready
34
Frequency converter not
ready
Frequency converter ready
35
Coasting stop
Safety closed
36
No alarm
Alarm
37
Not used
Not used
38
Not used
Not used
39
Not used
Not used
40
No warning
Warning
41
Not at reference
At reference
42
Hand mode
Auto mode
43
Out of freq. range
In frequency range
44
Stopped
Running
45
Not used
Not used
46
No voltage warning
Voltage warning
47
Not in current limit
Current limit
48
No thermal warning
Thermal warning
Table 8.3 Frequency Converter status word (FC profile)
Bus adress Bus register
1
PLC Register Content
Access
Description
0
1
40001
Reserved
Reserved for Legacy Drives VLT 5000 and VLT 2800
1
2
40002
Reserved
Reserved for Legacy Drives VLT 5000 and VLT 2800
2
3
40003
Reserved
Reserved for Legacy Drives VLT 5000 and VLT 2800
3
4
40004
Free
4
5
40005
Free
5
6
40006
Modbus conf
Read/Write
TCP only. Reserved for Modbus TCP (p12-28 and 12-29 -
store in Eeprom etc.)
6
7
40007
Last error code
Read only
Error code recieved from parameter database, refer to
WHAT 38295for details
7
8
40008
Last error register Read only
Address of register with which last error occurred, refer
to WHAT 38296 for details
8
9
40009
Index pointer
Read/Write
Sub index of parameter to be accessed. Refer to WHAT
38297 for details
9
10
40010
FC par. 0-01
Dependent on
parameter access
Parameter 0-01 (Modbus Register = 10 parameter
number
20 bytes space reserved pr parameter in Modbus Map
19
20
40020
FC par. 0-02
Dependent on
parameter access
Parameter 0-02
20 bytes space reserved pr parameter in Modbus Map
29
30
40030
FC par. xx-xx
Dependent on
parameter access
Parameter 0-03
20 bytes space reserved pr parameter in Modbus Map
1
Value written in Modbus RTU telegram must be one or less than register number. E.g. Read Modbus Register 1 by writing value 0 in telegram.
* Used to specify the index number to be used when accessing an indexed parameter.
RS485 Installation and Set-...
VLT Micro Drive Design Guide
78
MG02K102 - VLT
®
is a registered Danfoss trademark
8
8
Содержание P1K5
Страница 1: ...MAKING MODERN LIVING POSSIBLE Design Guide VLT Micro Drive...
Страница 96: ...www danfoss com drives MG02K102 132R0059 MG02K102 Rev 2011 08 16...