Successful AMT
1.
The display shows “Press [OK] to finish AMT”.
2.
Press the [OK] key to exit the AMT state.
Unsuccessful AMT
1.
The frequency converter enters into alarm mode.
A description of the alarm can be found in the
Troubleshooting
section.
2.
"Report Value” in the [Alarm Log] shows the last
measuring sequence carried out by the AMT,
before the frequency converter entered alarm
mode. This number along with the description of
the alarm will assist you in troubleshooting. If you
contact Danfoss Service, make sure to mention
number and alarm description.
Unsuccessful AMT is often caused by incorrectly registered
motor name plate data or too big difference between the
motor power size and the frequency converter power size.
Step 4. Set speed limit and ramp time
Set-up the desired limits for speed and ramp time.
Minimum Reference
3-02 Minimum Reference
Maximum Reference
3-03 Maximum Reference
Motor Speed Low Limit
4-11 Motor Speed Low Limit
[RPM]
or
4-12 Motor Speed Low
Limit [Hz]
Motor Speed High Limit
4-13 Motor Speed High Limit
[RPM]
or
4-14 Motor Speed High
Limit [Hz]
Ramp-up Time 1 [s]
3-41 Ramp 1 Ramp Up Time
Ramp-down Time 1 [s]
3-42 Ramp 1 Ramp Down Time