![Danfoss OPTYMA Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/danfoss/optyma/optyma_operation-and-maintenance-manual_3573348005.webp)
©
Danfoss A/S (RA Marketing/MWA), Nov. 08
RS8FE102, 080R9278
5
OPTYMA
TM
Control three-phase
Operation and Maintenance Guide
Technical characteristics of OPTYMA
TM
Control three-phase
Technical characteristics
OPTYMA
TM
Control (4 HP)
OPTYMA
TM
Control (7.5 HP)
Housing dimensions
400 x 300 x 135 mm
400 x 300 x 135 mm
Weight
9 kg
10 kg
Protection rating
IP 65
IP 65
Power supply (3F+N+T)
400Vac ±10% 50/60Hz
400Vac ±10% 50/60Hz
Load type
3-phase
3-phase
Operating temperature
- 5 to + 40 °C
- 5 to + 40 °C
Storage temperature
-25 to +55 °C
-25 to +55 °C
Relative ambient humidity
from 30% to 95% RH
w/out condensate
from 30% to 95% RH
w/out condensate
Altitude
< 1000 m
< 1000 m
Main switch / general protection
Interruption power
4-pole magnetothermic 16A “D”
Icn=6kA / Ics=8kA / Icu=15kA
4-pole magnetothermic 25A “D”
Icn=6kA / Ics=8kA / Icu=15kA
Compressor protection
Adjustable motor circuit breaker
Adjustable motor circuit breaker
Defrosting
electrical
electrical
Status indicators
LED + display
LED + display
Alarm signals
LED + buzzer
LED + buzzer
Inputs
Ambient probe
EKS 221: code no. 084N3210
EKS 221: code no. 084N3210
Evaporator probe
EKS 221: code no. 084N3210
EKS 221: code no. 084N3210
Door switch
present
present
High/low pressure switch
present
present
Kriwan® connection
present
present
Compressor functioning mode selection
pump-down / thermostat
pump-down / thermostat
Digital inputs (requirements to contacts)
Gold plating
Gold plating
Outputs
Compressor
See motor circuit breaker
thermal range
See motor circuit breaker
thermal range
Condenser fans output 1
800W (1 phase)
800W
total
(1 phase)
Condenser fans output 2 (separated)
(1 phase)
Evaporator fans
500W (1 phase)
2000W (1phase / 3 phases)
Defrosting heaters
6000W (AC1) eq. resistive load
9000W (AC1) eq. resistive load
Room light
800W (AC1) resistive load
800W (AC1) resistive load
Solenoid valve
present
present
Compressor oil heater
present
present
Alarm relay
100W
100W