OPTYMA
TM
Control three-phase
Operation and Maintenance Guide
Pump-down function
Select the PUMP-DOWN function mode for the
compressor working on X1 terminal block, change
the selection connection as indicated in the wiring
diagram.
The AU parameter must never be set at 4, as the
PUMP-DOWN function is made electromechanically
inside the panel.
Password function
The protection function is activated when parameter
PA is set with a value other than 0,.
See parameter P1 for the different protection types.
When PA is set, protection starts after two
minutes of inactivity. 000 appears on the display. Use
the up/ down keys to change the number, and the
set key to confirm it. Use the universal number 100 if
you have forgotten the password.