move any panel from the condensing unit.
• Remove surface dirt, leaves, fibres, etc. with
a vacuum cleaner, equipped with a brush or
other soft attachment. Alternatively, blow com-
pressed air through the coil from the inside out,
and brush with a soft bristle. Do not use a wire
brush. Do not impact or scrape the coil with the
vacuum tube or air nozzle.
If the refrigerant system has been opened, the
system has to be flushed with dry air or nitrogen
to remove moisture and a new filter drier has to
be installed. If evacuation of refrigerant has to be
done, it shall be done in such a way that no refri-
gerant can escape to the environment.
Service panel removal procedure for
W09 Version.
OP-LSQM014, 018, OP-MSGM018, 021, OP-
MSYM009, 012, 014, OP-MSGM012, 015
OP-MSYM018, OP-LSQM026 - 034 - 048 - 068
- 074, OP-MSYM018 - 024 - 026 - 034, OP-
MSXM034 - 044 - 046 - 057, OP-MSGM026 -
033, OP-LSQM067 - 084 - 098, OP-MSXM068
- 080 - 093 - 099 - 108
Step 1: Pull the cap from the isolator switch
using screw driver.
Step 2: Unscrew the isolator switch from the ser-
vice panel.
Step 3: Take out the isolator switch.
Step 4: Follow the same procedure you would
follow for slim pack for removing the service
panel.
14 - Warranty
Always transmit the model number and serial num-
ber with any claim filed regarding this product.
The product warranty may be void in following
cases:
• Absence of nameplate.
• External modifications; in particular, drilling,
welding, broken feet and shock marks.
• Compressor opened or returned unsealed.
• Rust, water or leak detection dye inside the
compressor.
• Use of a refrigerant or lubricant not approved
by Danfoss.
• Any deviation from recommended instructions
pertaining to installation, application or main-
tenance.
• Use in mobile applications.
• Use in explosive atmospheric environment.
• No model number or serial number transmit-
ted with the warranty claim.
15 – Disposal
Danfoss recommends that condensing
units and oil should be recycled by a
suitable company at its site.
13 - Fan speed controller setting for R134a
refrigerant
Sr. No.
FSC type
Fan speed Controller
Spare part number
Refrigerant
letter
For Refrigerant
Factory
setting
Action required
1
XGE-2C
061H3144
Q
R404A/R452A/R507
15 bar
360°=1 turn = Approx 0.8 bar
(Clockwise rotation =
Increase pressure setting,
Counter clockwise rotation =
Decrease pressure setting)
2
H
R404A/R507
15 bar
3
X
R404A/R507/R134a/R407A/
R407F/R448A/R449A
15 bar
4
Y
R404A/R507/R449A
15 bar
5
G
R134a
8 bar
6
X
If refrigerant used is R134a
15 bar
Rotate the screw by 9 turns in counter
clockwise direction to reach 8 bar