Instructions
© Danfoss | DCS (CC) | 2021.03
30 | AN37261865152501-010101 - 118A2176A
OP-MSXM034MLW05E
Application
Refrigerant
M.W.P. HP
114X7062
MBP
PS = 32 bar
(1) R404A, R452A, R507,
R448/9A, R454C, R455A
(1) 28 bar
LP (1) 7 bar
IP54
(2) R134a,R1234yf,
R513A
(2) 23 bar
(2) 5 bar
Voltage
380-400V~3N~50Hz
LRA
30,5 A
7,5 A
MCC
Serial No.
Barcode Serial No:
123456CG4818
118UXXXX
A
B
C
D
E
F
G
MADE IN INDIA
EAN No.
Danfoss A/S, 6430 Nordborg, Denmark
XXXXXXXXXXXXX
A
: Model
B
: Code number
C
: Application, Protection
D
: Refrigerant
E
: Housing Service Pressure (Maximum working pressure)
F
: Supply voltage, Locked Rotor Ampere, Maximum Continuous Current
G
: Serial Number and bar code
Name plate
* For exact values please refer name plate in unit
OP - MSXM 034 ML W05 G
1 2 3 4
5
6
7
8
1 Application
M = MBP
L = LBP
2 Package
Condensing unit family: S = Slim Pack
3 Refrigerant
T = R404A/R507, R455A, R454C, R448A/R449A, R452A
S = R134a, R513A, R1234yf
V =R454C, R455A, R452A, R404A/R507
4 Condenser
M = Microchannel heat condenser
5 Swept volume
Displacement in cm
3:
Example 034 = 34 cm
3
6 Compressor platform
(Such as DP/DX/DS = Fixed speed Reciprocating compressor)
7 Version
W05: Optyma™ Slim Pack standard version (see Version table)
8 Voltage code
G = 230V/1-phase compressor & fan
E = 400V/3-phase compressor & 230V/1-phase fan
Optyma™
Slim Pack
W05*
Condensing unit :IP level
IP54
Refrigerant
Group I / Group II
Compressor technology
Reciprocating
Control box (pre-wired E-panel)
yes
Microchannel condenser
yes
Fan speed controller
-
Main switch (circuit breaker)
-
Filter drier (flare connections)
yes
Sight glass
yes
Crankcase heater
yes
HP/LP adjustable pressostat
Auto/Manual reset mode
Access door(s)
yes for E-Box
Acoustic insulation
-
Discharge gas thermostat
yes * (Provision)
HP/LP Alarm
yes* (Provision)
Electrical Box design
IP54
Adjustable time delay (Compressor)
yes
Version control
Designation system for the
Optyma
™ Slim Pack range
* Compatible with A2L refrigerant
N
O
L
M
L
L
[mm]
M
[mm]
N
[mm]
O
[mm]
250
50
550
550
Picture 1 : Minimum mounting distances
Annex - A
Technical data (English)