Installation and servicing of the conden-

sing units by qualified personnel only. 

Follow these instructions and sound refri-

geration engineering practice relating to 

installation, commissioning, maintenance 

and service.

 The condensing unit must only be used for 

its designed purpose(s) and within its scope of 

application. 

 Under all circumstances, the EN378 (or  

other applicable local safety regulation) 

requirements must be fulfilled.

The condensing unit is delivered under nitro-

gen gas pressure (1 bar) and hence it cannot 

be connected as it is; refer to the «installation»

 

section for further details. 

The condensing unit must be handled with cau-

tion in the vertical position (maximum offset 

from the vertical : 15°)

MADE IN INDIA

OP-MPVE034MLW04E

Application

Refrigerant

M.W.P. HP

114X7039

MBP

(1) R404A, R507, R22, 

     R448A, R449A, R452A

(1) 28 bar

             LP (1)  7  bar

IP54

(2) R134a, R513A

(2) 23 bar

(2)  5  bar

Voltage

380-400V3N~/50Hz

LRA

OIL INSIDE   POE 46

30.5 A

7.5 A

MCC

Serial No.

EAN No.

Danfoss A/S, 6430 Nordborg, Denmark

Barcode Serial No: 

123456CG0514

XXXXXXXXXXX

118UXXXX

A
B
C

D
E
F

G

A

:   Model

B

:   Code  number 

C

:   Application,  Protection

D

:   Refrigerant 

E

:   Housing Service Pressure

F

:   Supply voltage, Locked Rotor Ampere,  

Maximum Current Consumption

G

:   Serial Number and bar code

* For exact values please refer name plate in unit

Name plate

L

M

N

O

[mm]

[mm]

[mm]

[mm]

250

650

550

550

Picture 1 : Minimum mounting distances

Designation system for the 

Optyma

™ Slim Pack range

    OP-MPVE   034   ML  W10    E

1 2 3 4

5

6

7

8

1

Application

 

M = MBP 
L = LBP

2

Package

 

P = Packaged unit

3

Refrigerant

 

V= R22/R134a/R513A/R404A/R448A/R449A/R452A
M= R22
Q = R404A/R507/R452A

4

Condenser

 

E: Extreme and tropical ambient conditions up to 48°C

5

Swept volume

 

Swept volume in CC

6

Compressor platform

 

ML = MLZ (Scroll)
MT = MT (Reciprocating)
NT = NTZ (Reciprocating)
LL = LLZ (Scroll)

7

Version 

See version control table - W02, W04, W08 and W10

8

Voltage code 

G = Compressor 230V/1N~/50Hz, fan 230V/1~/50Hz
E = Compressor 400V/3N~/50Hz, fan 230V/1~/50Hz

W02

W04

W08

W10

Service valves

Low Pressure cartridge

Receiver

Filter drier

Sight Glass

Solenoid Valve

Cranckase Heater (Only for LBP models)

Full Ebox

Fan speed controller

Dual Pressure switch KP

HP alarm provision

LP alarm Provision

Discharge gas thermostat provision

7. Version control

Instructions

Optyma™

 

Slim Pack 

OP-LPQE/MPVE/MPME

© Danfoss | DCS (CC) | 2020.06

118A0665C - AN238286441930en-001401 | 1 



Содержание Optyma OP-MPME048MTW02E

Страница 1: ...number C Application Protection D Refrigerant E Housing Service Pressure F Supply voltage Locked Rotor Ampere Maximum Current Consumption G Serial Number and bar code For exact values please refer name plate in unit Name plate L M N O L mm M mm N mm O mm 250 650 550 550 Picture 1 Minimum mounting distances Designation system for the Optyma Slim Pack range OP MPVE 034 ML W10 E 1 2 3 4 5 6 7 8 1 App...

Страница 2: ...ystem as soon as possible toavoidoilcontaminationfromambientmoisture Avoid material entering into the system while cutting tubes Never drill holes where burrs cannot be removed Braze with great care using state of the art technique and vent piping with nitrogen gas flow Connect the required safety and control devices When the schrader port is used for this remove the internal valve It is recommend...

Страница 3: ...nt of refrigerant charge as well as operating conditions as a reference for future inspections 13 Maintenance Always switch off the unit at main switch before remove fan panel Internal pressure and surface temperature are dangerous and may cause permanent injury Maintenance operators and installers require appropriate skills and tools Tubing temperature may exceed 100 C and can cause severe burns ...

Страница 4: ...d Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP man reset LP aut reset Manual test Convertible reset Manual reset LP auto HP man LP auto HP auto LP diff Manual reset Test Test Resist Load Pilot duty AC DC Max 50 VA 17 Dual Pressure Switch factory settings Refrigerants High pressure settings bar g Low pressure settings bar g ON OFF ON OFF ...

Страница 5: ...84 098 OP MPVE068 080 093 099 108 OP LPQE048 068 OP MPVE034 046 057 OP MPME048 060 Chassis B2 Chassis B3 OptymaTM Slim Pack OptymaTM Slim Pack Instructions 118A0665C AN238286441930en 001401 5 Danfoss DCS CC 2020 06 ...

Страница 6: ...Code G version W02 OP MPVE034 046 OP MPME048 060 OP MPZE060 Code G version W02 OP MPVE068 080 093 WD1 WD2 Instructions 6 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Страница 7: ... E version W02 OP MPVE034 046 068 080 099 108 OP MPME048 060 Code G version W04 OP MPVE034 046 057 OP MPME048 060 LPQE048 068 WD3 WD4 Instructions 118A0665C AN238286441930en 001401 7 Danfoss DCS CC 2020 06 ...

Страница 8: ... version W04 OP MPVE034 046 057 068 080 099 108 OP MPME048 060 OP LPQE048 067 068 084 098 Code G version W04 OP MPVE068 080 093 WD5 WD6 Instructions 8 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Страница 9: ...Code E version W08 OP MPVE046 068 080 099 108 Code G version W10 OP MPVE034 046 057 OP LPQE048 068 WD7 WD8 Instructions 118A0665C AN238286441930en 001401 9 Danfoss DCS CC 2020 06 ...

Страница 10: ...Code E version W10 OP MPVE046 057 OP LPQE048 068 Code G Version W10 OP MPVE068 080 WD9 WD10 Instructions 10 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Страница 11: ... Fuse control circuit H1 Low pressure alarms H2 High pressure alarms M1 Compressor M2 Fan motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Legend BK black BU blue BN brown GY grey RD red WH white Code E Version W10 OP LPQE067 084 098 OP MPVE068 080 099 10...

Страница 12: ...serves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved ...