background image

1 – Introduction

These instructions pertain to Optyma

TM

 Slim 

Pack condensing units OP-LPQE/MPVE/MPME 

(R22, R404A, R507, R134a, R513A, R448A, R449A, 

R452A) used for refrigeration systems. They 

provide necessary information regarding safety 

and proper usage of this product.

The condensing unit includes following:

  •  Scroll/reciprocating  compressor

 •  Microchannel heat exchanger

 •  Dual pressure switches

 •  Service valves suction/ liquid

 •  Weather proof housing (IP 54)

  •  Filter  drier

 •  Receiver with stop valve

  •  Sight  glass

  •  Solenoid  valve

 •  Phase sequence relay *

)

 •  Fully pre-wired electrical panel (including main 

switch, compressors contactor, overload relay)

 •  Crankcase heater (OP-LPQE units in W04 and 

W10 only)*

)

Fan speed controller (W10 only)

*

)

 Refer version control for components details in 

all versions

2 – Handling and storage

 •  It is recommended not to open the packaging 

before the unit is at the final place for installation.

 •  

Handle the unit with care. The packaging 

allows for the use of a forklift or pallet jack. Use 

appropriate and safe lifting equipment. 

 •  Store and transport the unit in an upright position.

 •  Store the unit between -35°C and 50°C.

 •  Don’t expose the packaging to rain or corrosive 

atmosphere.

 

• 

 

After unpacking, check that the unit is 

complete and undamaged.

3 – Installation precautions

 Do not braze as long the condensing unit is 

under pressure.

 Never place the unit in a flammable atmosphere 

 Place the unit in such a way that it is not blocking 

or hindering walking areas, doors, windows or similar.

 •  Ensure adequate space around the unit for air 

circulation and to open doors. Refer to picture1 

for minimal values of distance to walls.

 •  Avoid installing the unit in locations which are daily 

exposed to direct sunshine for longer periods.

 •  Avoid installing the unit in aggressive and 

dusty environments.

 •  Ensure a foundation with horizontal surface 

(less than 3° slope), strong and stable enough 

to carry the entire unit weight and to eliminate 

vibrations and interference.

 •  The unit ambient temperature may not exceed 

50°C during off-cycle.

 •  Ensure that the power supply corresponds to 

the unit characteristics (see nameplate).

 • 

 

When installing units for HFC refrigerants, 

use equipment specifically reserved for HFC 

refrigerants which was never used for CFC or 

HCFC refrigerants.

 •  Use clean and dehydrated refrigeration-grade 

copper tubes and silver alloy brazing material.

 •  Use clean and dehydrated system components.

 

• 

 

The suction piping connected to the 

compressor must be flexible in 3 dimensions 

to dampen vibrations. Furthermore piping has 

to be done in such a way that oil return for the 

compressor is ensured and the risk of liquid 

slug over in compressor is eliminated.

4 – Installation

 •  The installation in which the condensing unit is 

installed must comply to EEC Pressure directive 

(PED) no. 2014/68/EU. The condensing unit itself 

is not a ”unit” in the scope this directive. Under all 

circumstances local safety regulations must be 

fulfilled.

 • 

 

The unit must be securely installed on a 

stable and rigid support, and fixed from the 

beginning. See picture 2.

 • 

 It is recommended to install the unit on 

rubber grommets or vibration dampers . 

Rubber pads with mounting bolts are supplied.

 •  Slowly release the nitrogen holding charge 

through the schrader port.

 •  Connect the unit to the system as soon as possible 

to avoid oil contamination from ambient moisture.

 •  Avoid material entering into the system while 

cutting tubes. Never drill holes where burrs 

cannot be removed.

 

• 

 

Braze with great care using state-of-the-art 

technique and vent piping with nitrogen gas flow.

 

• 

 

Connect the required safety and control 

devices. When the schrader port is used for this, 

remove the internal valve.

 •  It is recommended to insulate the suction pipe 

up to the compressor inlet with 19 mm thick 

insulation.

5 – Leak detection

 Never pressurize the circuit with oxygen or 

dry air. This could cause fire or explosion.

 •  Do not use dye for leak detection.

 •  Perform a leak detection test on the complete 

system.

 •  The maximum test pressure is 31 bar.

 •  When a leak is discovered, repair the leak and 

repeat the leak detection.

6 – Vacuum dehydration

 •  Never use the compressor to evacuate the system.

 •  Connect a vacuum pump to both the LP & HP 

sides.

 •  Pull down the system under a vacuum of 500 

μm Hg (0.67 mbar) absolute.

 •  Do not use a megohmmeter nor apply power 

to the compressor while it is under vacuum as 

this may cause internal damage.

7 – Electrical connections

 •  Switch off and isolate the main power supply.

 •  Ensure that power supply can not be switched 

on during installation.

 •  All electrical components must be selected as 

per local standards and unit requirements.

 

• 

 

Refer to wiring diagram for electrical 

connections details.

 •  

Ensure that the power supply corresponds 

to the unit characteristics and that the power 

supply is stable (nominal voltage ±10% and 

nominal frequency ±2,5 Hz).

 •  Dimension the power supply cables according 

to unit data for voltage and current.

 •  Protect the power supply and ensure correct 

earthing.

 •  Make the power supply according to local 

standards and legal requirements.

 •  The unit is equipped with high and low pressure 

switches, which directly cut the power supply 

to the compressor and provides 230V a.c. alarm 

signals (max.50VA) in case of activation. Version 

W04 is also equipped with phase sequence relay 

to protect the unit against phase loss/sequence/ 

asymmetry and under-/over-voltage.

For units with a 3-phase scroll compressor, 

correct phase sequence for compressor rotation 

direction shall be observed.

 •  Determine the phase sequence by using a 

phase meter in order to establish the phase 

orders of line phases L1, L2 and L3.

 •  Connect line phases L1, L2 and L3 to main 

switch terminals T1, T2 and T3 respectively.

 DGT protection is required if the high and 

low pressure switch settings do not protect 

the compressor against operations beyond its 

specific application envelope. Please refer to 

the examples below, which illustrate where DGT 

protection is required (n°1) and where it is not 

(n°2). 

The compressor must not be allowed to cycle 

on the discharge gas thermostat. Continuous 

operations beyond the compressor’s operating 

range will cause serious damage to the 

compressor!

Discharge line

Thermostat

Bracket

Insulation

A DGT accessory is available from Danfoss: refer 

to section “Spare parts & accessories”.

8 – Safety

Fusible Plug is not available in unit, it is 

replaced with adapter plug. 

Unit has liquid receiver with an Adapter Plug 

with 3/8” NPT connection. installer/end user can 

select various options as mentioned in EN378-2 : 

2016 Article § 6.2.2.3

 

• 

 

The unit/installation into which the 

Picture 2 

Mounting bolts 

Picture 3 

Anticlockwise (open)

Clockwise (Close)

Schrader valve

Instructions

2 |  AN238286441930en-001401 - 118A0665C

© Danfoss | DCS (CC) | 2020.06

Содержание Optyma OP-MPME048MTW02E

Страница 1: ...number C Application Protection D Refrigerant E Housing Service Pressure F Supply voltage Locked Rotor Ampere Maximum Current Consumption G Serial Number and bar code For exact values please refer name plate in unit Name plate L M N O L mm M mm N mm O mm 250 650 550 550 Picture 1 Minimum mounting distances Designation system for the Optyma Slim Pack range OP MPVE 034 ML W10 E 1 2 3 4 5 6 7 8 1 App...

Страница 2: ...ystem as soon as possible toavoidoilcontaminationfromambientmoisture Avoid material entering into the system while cutting tubes Never drill holes where burrs cannot be removed Braze with great care using state of the art technique and vent piping with nitrogen gas flow Connect the required safety and control devices When the schrader port is used for this remove the internal valve It is recommend...

Страница 3: ...nt of refrigerant charge as well as operating conditions as a reference for future inspections 13 Maintenance Always switch off the unit at main switch before remove fan panel Internal pressure and surface temperature are dangerous and may cause permanent injury Maintenance operators and installers require appropriate skills and tools Tubing temperature may exceed 100 C and can cause severe burns ...

Страница 4: ...d Differential Voltage Use Copper wire only Tightening torque 20lb in When used acc to UL regulations HP LP man reset LP aut reset Manual test Convertible reset Manual reset LP auto HP man LP auto HP auto LP diff Manual reset Test Test Resist Load Pilot duty AC DC Max 50 VA 17 Dual Pressure Switch factory settings Refrigerants High pressure settings bar g Low pressure settings bar g ON OFF ON OFF ...

Страница 5: ...84 098 OP MPVE068 080 093 099 108 OP LPQE048 068 OP MPVE034 046 057 OP MPME048 060 Chassis B2 Chassis B3 OptymaTM Slim Pack OptymaTM Slim Pack Instructions 118A0665C AN238286441930en 001401 5 Danfoss DCS CC 2020 06 ...

Страница 6: ...Code G version W02 OP MPVE034 046 OP MPME048 060 OP MPZE060 Code G version W02 OP MPVE068 080 093 WD1 WD2 Instructions 6 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Страница 7: ... E version W02 OP MPVE034 046 068 080 099 108 OP MPME048 060 Code G version W04 OP MPVE034 046 057 OP MPME048 060 LPQE048 068 WD3 WD4 Instructions 118A0665C AN238286441930en 001401 7 Danfoss DCS CC 2020 06 ...

Страница 8: ... version W04 OP MPVE034 046 057 068 080 099 108 OP MPME048 060 OP LPQE048 067 068 084 098 Code G version W04 OP MPVE068 080 093 WD5 WD6 Instructions 8 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Страница 9: ...Code E version W08 OP MPVE046 068 080 099 108 Code G version W10 OP MPVE034 046 057 OP LPQE048 068 WD7 WD8 Instructions 118A0665C AN238286441930en 001401 9 Danfoss DCS CC 2020 06 ...

Страница 10: ...Code E version W10 OP MPVE046 057 OP LPQE048 068 Code G Version W10 OP MPVE068 080 WD9 WD10 Instructions 10 AN238286441930en 001401 118A0665C Danfoss DCS CC 2020 06 ...

Страница 11: ... Fuse control circuit H1 Low pressure alarms H2 High pressure alarms M1 Compressor M2 Fan motor K1 K1 Contactor K2 Start relay K2 Compressor contactor K3 Fan contactor Q1 Main switch R1 R2 Bleeder resistor S1 Room thermostat S2 Discharge gas thermostat X1 Terminals Y1 Solenoid valve Legend BK black BU blue BN brown GY grey RD red WH white Code E Version W10 OP LPQE067 084 098 OP MPVE068 080 099 10...

Страница 12: ...serves the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trade marks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved ...

Отзывы: