© Danfoss | Climate Solutions | 2022.08

AN41473467835501-000102 | 5

Defrost

Evaporator fans

Alarms

Level 1

Level 2

Description

Values

Min.

Def.

Max.

dEF

d0

Defrost frequency (Time between 2 starts)

H.

0

6

96

d1

Maximum defrost duration (

0

=defrost deactivated)

Min.

0

*

255

d2

Type of message during the defrost:

0

=Displays the real temperature; 

1

=Displays the temperature at the start of 

the defrost; 

2

=Displays the dEF message

0

2

2

d3

Maximum duration of the message

(Time added at the end of the defrost process)

Min.

0

5

255

d4

Final defrost temperature (by probe) (If I00 ≠ 1)

°C/°F

-50

8.0

50

d5

Defrost on connecting the unit:

0

=NO First defrost according to d0; 

1

=YES, First defrost according to d6

0

0

1

d6

Delay of the defrost start on connecting the unit

Min.

0

0

255

d7

1)

Type of defrost:

0

=Resistors; 

1

=Air/fans, 

2

=Hot gas; 

3

=Reversal of cycle

0

*

3

d8

Count of time between defrost periods:

0

=Total real time, 

1

 =Sum of compressor connected time

0

0

1

d9

Drip time when completing defrost (Shutdown of compressor and fans)

Min.

0

1

255

EP

Exit to level 1

Level 1

Level 2

Description

Values

Min.

Def.

Max.

FAn

F0

Shutdown temperature of fans

°C/°F

-50

45

50

F1

Probe 2 differential if fans are shut down

°C/°F

0.1

2.0

20.0

F2

Shut down fans when the compressor shuts down: 

0

=No, 

1

=Yes

0

0

1

F3

Status of the fans during the defrost: 

0

=Shut down; 

1

=Running

0

0

1

F4

Delay of start-up after defrost (If F3=0)

It will only actuate if it is higher than 

d9

Min.

0

2

99

EP

Exit to level 1

Level 1

Level 2

Description

Values

Min.

Def.

Max.

AL

A0

Configuration of the temperature alarms: 

0

=Relative to SP, 

1

=Absolute

0

1

1

A1

Alarm for maximum in probe 1 (It should be higher than the SP)

°C/°F

A2

99

99

A2

Alarm for minimum in probe 1 (It should be lower than the SP)

°C/°F

-50

-50

A1

A3

Delay of temperature alarms in the start-up

Min.

0

0

120

A4

Delay of temperature alarms from the end of a defrost

Min.

0

0

99

A5

Delay of temperature alarms from when the 

A1

 or 

A2

 value is reached

0

30

99

A6

Delay of the external alarm/Severe external alarm on receiving a signal in 

digital input (

I10

 or 

I20

 = 2 or 3)

Min.

0

0

120

A7

Delay of external alarm deactivation/Severe external alarm deactivation 

when the signal in digital input disappears (

I10

 or 

I20 

= 2 or 3)

Min.

0

0

120

A8

Show warning if the defrost ends for maximum time: 

0

=No, 

1

=Yes

0

0

1

A9

Relay alarm polarity

0

= Relay ON in alarm (OFF without alarm); 

1

= Relay OFF in alarm (ON 

without alarm)

0

0

1

A10

Differential of temperature alarms (

A1

 and 

A2

)

°C/°F

0.1

1.0

20.0

A12

Delay of open door alarm (If 

I10

 or 

I20

=1)

Min.

0

10

120

EP

Exit to level 1

* According to wizard.

1)

 It can only be modified using the configuration wizard (InI).

Содержание Optyma AK-RC 204B

Страница 1: ...rs are the maximum working currents and powers EN Temperature controller for walk in coolers and freezers type AK RC 204B and AK RC 205C 1 ES Controlador de temperatura para cuartos fr os y congelador...

Страница 2: ...g into consideration temporary modifications by other parameters C10 or C12 When an alarm is underway pressing once mutes the acoustic alarm Pressing for 3 seconds accesses the Set Point setting Indic...

Страница 3: ...g keys in sequence one after the other SET Warning If the pump down function is active a certain amount of time may elapse between starting the stand by function and the controller stopping Note If op...

Страница 4: ...ressor 0 Minimum time of compressor in OFF 1 Minimum time of compressor in OFF and in ON in each cycle 0 0 1 C5 Protection delay time Value of the option selected in parameter C4 Min 0 0 120 C6 COOL r...

Страница 5: ...s when the compressor shuts down 0 No 1 Yes 0 0 1 F3 Status of the fans during the defrost 0 Shut down 1 Running 0 0 1 F4 Delay of start up after defrost If F3 0 It will only actuate if it is higher t...

Страница 6: ...I11 Polarity of the digital input 1 0 Activates on closing contact 1 Activates on opening contact 0 1 I20 Configuration of digital input 2 0 Deactivated 1 Door contact 2 External alarm 3 Severe exter...

Страница 7: ...value programmed in A1 has been reached AL Minimum temperature alarm in control probe The temperature value programmed in A2 has been reached AE External alarm activated by digital input AES Severe e...

Страница 8: ...13 A 250 V Relay AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V NC EN60730 1 10 8 A 250 V No of relay operations EN60730 1 100 000 operations Probe temperature range 50 0 99 9 C Resolution setting and dif...

Страница 9: ...de la configuraci n La funci n de las entradas digitales depende de la configuraci n Las intensidades y potencias indicadas son las m ximas de trabajo admitidas Conexionado Desconectar siempre la ali...

Страница 10: ...es temporales por otros par metros C10 C12 Con una alarma en curso una pulsaci n corta silencia la alarma ac stica Pulsando durante 3 segundos accede al ajuste del Set Point Indicadores Fijo Modo Stan...

Страница 11: ...ntes teclas una detr s de otra no a la vez SET Advertencia Si la funci n recogida de gas est activa puede transcurrir un cierto tiempo desde que iniciamos la funci n Stand by hasta que el controlador...

Страница 12: ...etardo para protecci n del compresor 0 Tiempo m nimo del compresor en OFF 1 Tiempo m nimo del compresor en OFF y en ON en cada ciclo 0 0 1 C5 Tiempo de retardo de la protecci n Valor de la opci n eleg...

Страница 13: ...st n parados C F 0 1 2 0 20 0 F2 Parar ventiladores al parar compresor 0 No 1 Si 0 0 1 F3 Estado de los ventiladores durante el desescarche 0 Parados 1 En marcha 0 0 1 F4 Retardo de arranque despu s d...

Страница 14: ...baja 8 Stand by remoto 0 8 I11 Polaridad de la entrada digital 1 0 Activa al cerrar contacto 1 Activa al abrir contacto 0 1 I20 Configuraci n de la entrada 2 0 Desactivada 1 Contacto puerta 2 Alarma...

Страница 15: ...nda de control Se ha alcanzado el valor de temperatura programado en A1 AL Alarma de temperatura m nima en sonda de control Se ha alcanzado el valor de temperatura programado en A2 AE Alarma externa a...

Страница 16: ...50 V Rel AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V NC EN60730 1 10 8 A 250 V N de operaciones de los rel s EN60730 1 100 000 operaciones Rango de temperatura de la sonda 50 0 a 99 9 C Resoluci n ajust...

Страница 17: ...vis des r glementations locales en vigueur Les relais AUXILIAIRES sont programmables leur fonctionnement d pend de la configuration La fonction des entr es num riques d pend de la configuration Les in...

Страница 18: ...nt compte des modifications temporaires par d autres param tres C10 ou C12 Avec une alarme en cours un appui court coupe le son de l alarme sonore Appuyez pendant 3 secondes pour acc der au r glage du...

Страница 19: ...on toutes en m me temps et SET Avertissement Si la fonction Pump Down est active un certain temps peut s couler entre le moment du d marrage de la fonction Stand by jusqu ce que le contr leur s arr te...

Страница 20: ...pour la protection du compresseur 0 Temps minimum du compresseur sur OFF 1 Temps minimum du compresseur sur OFF et ON au cours de chaque cycle 0 0 1 C5 Temps de retard de la protection Valeur de l opt...

Страница 21: ...0 F2 Arr ter les ventilateurs lors de l arr t de compresseur 0 Non 1 Qui 0 0 1 F3 tat des ventilateurs lors du d givrage 0 Arr t s 1 En marche 0 0 1 F4 Retard de d marrage apr s le d givrage si F3 0 N...

Страница 22: ...I11 Polarit de l entr e num rique 1 0 Active la fermeture du contact 1 Active l ouverture du contact 0 1 I20 Configuration de l entr e num rique 2 0 D sactiv e 1 Contact porte 2 Alarma externe 3 Al ex...

Страница 23: ...sonde de contr le La valeur de temp rature programm e en A1 a t atteinte AL Alarme de temp rature minimum dans la sonde de contr le La valeur de temp rature programm e en A2 a t atteinte AE Alarme ex...

Страница 24: ...15 13 A 250 V Relais AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V NC EN60730 1 10 8 A 250 V Nbre d op rations des relais EN60730 1 100 000 op rations Plage de temp rature de la sonde 50 0 99 9 C R solut...

Страница 25: ...programmierbar ihre Funktion ist jeweils von der Konfiguration abh ngig Die Funktion der Digitaleing nge h ngt von der Konfiguration ab Bei den Stromst rke und Leistungsangaben handelt es sich um die...

Страница 26: ...gezeigt wobei die vor bergehenden nderungen durch andere Parameter C10 oder C12 ber cksichtigt werden Bei aktiviertem Alarm wird durch kurzes Dr cken das akustische Alarmsignal ausgeschaltet Durch 3 S...

Страница 27: ...nander dr cken Warnung Wenn die Funktion Pump Down aktiv ist kann es ab dem Start der Stand by Funktion bis zum Stopp des Reglers einige Zeit dauern Notiz Bei Wahl der Optionen 2 5 7 9 oder 12 sichers...

Страница 28: ...0 min Zeit des Kompressors im OFF Zustand 1 min Zeit des Kompressors im OFF und ON Zustand in jedem Zyklus 0 0 1 C5 Verz gerungszeit f r den Schutz Wert der in Parameter C4 gew hlten Option Min 0 0 1...

Страница 29: ...0 nein 1 ja 0 0 1 F3 Status der L fter w hrend der Abtauung 0 abgeschaltet 1 in Betrieb 0 0 1 F4 L fter Anlaufverz gerung nach Abtauung wenn F3 0 Nur wirksam wenn gr er als d9 Min 0 2 99 EP Zur ck zu...

Страница 30: ...zugriff 0 8 I11 Polarit t des Digitaleingangs 1 0 aktiviert bei Kontaktschlie ung 1 aktiviert bei Kontakt ffnung 0 1 I20 Konfiguration des Eingangs 2 0 deaktiviert 1 T rkontakt 2 externer Alarm 3 schw...

Страница 31: ...ierte Temperaturwert wurde erreicht AL Alarm f r min Temperatur an Raumf hler Der in A2 programmierte Temperaturwert wurde erreicht AE Externer Alarm aktiviert per Digitaleingang AES Schwerwiegender e...

Страница 32: ...250 V Relais AUX 2 SPDT 16 A NO EN60730 1 12 9 A 250 V NC EN60730 1 10 8 A 250 V Anzahl der Relaisoperationen EN60730 1 100 000 operationen Temperaturbereich des F hlers 50 0 bis 99 9 C Aufl sung Ein...

Страница 33: ...uir o conselho dos regulamentos locais em vigor Os rel s AUXILIARES s o program veis o seu funcionamento depende da configura o A fun o das entradas digitais depende da configura o As intensidades e p...

Страница 34: ...metros C10 C12 Com um alarme em curso um breve toque silencia o alarme ac stico Premindo durante 3 segundos acede ao ajuste do Set Point Indicadores Fixo Modo Stand By ativo a regula o est parada Int...

Страница 35: ...ma a seguir outra e n o uma de cada vez SET Aviso Se a fun o de pump down estiver ativada pode decorrer algum tempo desde que a fun o Stand by inicia at o controlador parar Observa o Caso sejam escolh...

Страница 36: ...2 C4 Tipo de atraso para a prote o do compressor 0 Tempo m nimo do compressor em OFF 1 Tempo m nimo do compressor em OFF e em ON em cada ciclo 0 0 1 C5 Tempo de atraso da prote o valor da op o escolhi...

Страница 37: ...0 F2 Parar ventiladores ao parar compressor 0 N o 1 Sim 0 0 1 F3 Estado dos ventiladores durante o degelo 0 Parados 1 Em funcionamento 0 0 1 F4 Atraso de arranque depois do degelo Se F3 0 S atua se f...

Страница 38: ...baixa 8 Stand by remoto 0 8 I11 Polaridade da entrada digital 1 0 Ativa ao fechar contacto 1 Ativa ao abrir contacto 0 1 I20 Configura o da entrada 2 0 Desativada 1 Contacto porta 2 Alarme externo 3...

Страница 39: ...sonda de controlo Foi alcan ado o valor de temperatura programado em A1 AL Alarme de temperatura m nima na sonda de controlo Foi alcan ado o valor de temperatura programado em A2 AE Alarme externo at...

Страница 40: ...25 C 0 4 C Temperatura ambiente de trabalho AK RC 204B 10 a 50 C AK RC 205C 10 a 45 C Temperatura ambiente de armazenamento 30 a 60 C Grau de prote o IP 65 Categoria de instala o II s EN 60730 1 Grau...

Отзывы: