background image

© Danfoss | 2016.03 | 9

VI.AA.A4.57

OBC 80 series

Application

The oil burner controls in the OBC 80 series are used to 

control and monitor one or two-stage oil burners with 

or without a preheater. The OBC 84.10 is used for burn-

ers with oil firing rates of 30 kg/h or above, and for hot 

air devices. Other OBC controls are used for oil burners 

with oil firing rates below 30 kg/h.

Mounting

Push the control’s contact plugs into the base with 12 

connection terminals. The control and base are held to-

gether by a spring system and can be released by press-

ing a screwdriver into the slot; see fig. 1. A front plate 

with knockouts or a front plate designed for PG 11 

screwed connections can be used; see fig. 2.

See fig. 3 for electrical connections in the base for the 

various types.

•  If using an LD or LDS photo unit, the blue wire must 

be connected to terminal 11 and the black wire to ter-

minal 12. If using a UV sensor, the blue wire must be 

connected to terminal 11, the black wire to terminal 

12, and the brown wire to terminal 1.

•  If preheater is not used, short-circuit terminals 3 and 8.

•  If the control is equipped with a remote reset switch 

connected to terminal 9, this switch must only be acti-

vated manually.

•  On some OBC 80 models, the ignition unit may be 

freely connected to either terminal 6 (TT1) or terminal 

7 (TT2).

Note: On the OBC 85 the boiler thermostat (TR) must always 

be connected to terminal 7, and the high temperature cut-

out (TB) must always be connected to terminal 1.

Function

The OBC controls the cut-in and cut-out of the oil 

burner’s components and monitors that the combustion 

cycle is performed safely. See function diagrams, fig. 3.

When the boiler thermostat (TR) cuts in, heating of the 

oil in the oil preheater (OFV) will begin.

Once the release temperature is reached and the oil pre-

heater’s thermostat (OTR) cuts in, the burner motor will 

start the pre-purge and power will simultaneously be 

applied to the ignition (TT1/TT2). Following the pre-ig-

nition and pre-purge time, the oil will be released by 

valve V1 being opened. On two-stage burners V2 will 

subsequently be opened.

On OBC controls without post-purge, power will be cut 

off when the boiler thermostat opens after the heating 

period and all relays at the outputs will open and be 

ready for the next start-up cycle.

On the OBC 85 control the power is 

not

 cut off when 

the boiler thermostat opens, as power is still needed for 

the burner motor so that post-purge can occur. Instead, 

a timer function ensures that the burner motor continues 

to run until the end of the post-purge time. If the ther-

mostat cuts in before the end of the postpurge time, the 

control will interrupt the postpurge and start a new cy-

cle with pre-heating.

Operating information

OBC 80 controls are equipped with a twocoloured LED 

which displays both the operating status and can indi-

cate the causes of errors leading to lockout.

In the event of operating lockout, the cause of error can 

be read out as a flash code by holding down the reset 

button for at least 5 seconds and then releasing it. 

Undervoltage will, however, be displayed automatically. 

Reset can be performed directly in alarm mode (constant 

red light) or in flash code mode by pressing the reset 

button for at least 0.5 seconds but no more than 3 sec-

onds.

In flash code mode it is possible to return to alarm 

mode by holding down the reset button again for at 

least 5 seconds.

Normal operation

When the boiler thermostat (TR) cuts in, the reset button 

flashes green. As soon as the preheater thermostat 

(OTR) cuts in, the reset button lights up constant green; 

see fig. 4.

When the boiler thermostat cuts out, the green light 

turns off. On the OBC 85, the light does not turn off until 

the post-purge period ends.

Errors during operation (flash codes; see fig. 5):

•  If the mains voltage falls below 185 V before start-up, 

the control will be blocked from starting. If the mains 

voltage falls below 170 V during operation, the oil 

supply and burner will be stopped. In both cases, the 

reset button will automatically flash 8 times. When the 

mains voltages reaches 185 V, the control will re-

start as normal. Please note that the control cannot be 

reset if the mains voltage is below 170 V.

•  If the mains voltage exceeds 264 V, the control will 

automatically enter alarm mode. The purpose of the 

overvoltage cut out is not simply to protect the elec-

tronics in the control, but also the other components 

in the burner.

•  If light is registered in the final stage of the pre-purge 

time, the control will not release oil and will enter 

alarm mode.

•  If no flame is established at the start, i.e. by the end of 

the safety time, the control will enter alarm mode.

•  In the event of a flame failure during operation, the oil 

supply will be cut off after no more than 1 second and 

the control will restart the burner. If flame failure oc-

curs more than three times in the same operating pe-

riod (TR connected), the control will enter alarm mode. 

Only one restart is allowed in the same operating period 

for OBC 84.10.

•  If the release temperature in the preheater is not 

reached within 10 minutes, the control will enter 

alarm mode.

The OBC 80 series’ processors also monitor the outputs 

at TT1/TT2, V1 and V2. If errors like electrical noise (EMC) 

are registered at the outputs, the control will enter 

alarm mode.

Troubleshooting

The OBC 80 series is approved in accordance with the 

latest EN 298:2012 norm, which sets more stringent re-

quirements for the monitoring of safety functions than 

previous norms. It is therefore important to ensure 

proper connection in accordance with the diagrams 

shown in order to avoid alarms.

When replacing the control in connection with service, 

please ensure that:

•  LD/LDS photo unit is connected to terminals 11 and 

12. Common 0 on terminal 2 or connected auxiliary 

terminals must not be used. Replacing the photo unit 

is always recommended when replacing the control.

•  If a certain function is not used, e.g. remote reset on 

terminal 9, the connection cannot be used as an auxil-

iary terminal. Instead, the extra auxiliary terminals in 

the base must be used.

•  The ignition is connected to terminal 6, though this 

does not apply to controls with alternate outputs for 

ignition on terminal 7 (TT2).

•  If an inverter which converts 12/24 V DC to 230 V AC is 

used, ensure that the inverter is capable of producing 

sinusoidal AC voltage. If the voltage is not sinusoidal, 

the electronics will be overloaded (burn out). There is 

also a risk that the control will detect an undervoltage.

•  The photo unit/UV sensor is positioned correctly in 

the burner so that the correct flame signal is generated. 

UV sensors are particularly sensitive, as they are very 

directional to prevent the ignition spark from being 

regarded as false light.

•  The photo unit/UV sensor is not sooty.

•  The insulation of the associated wiring is not degraded, 

as this can cause leakage currents that the control will 

register as errors at the inputs or outputs.

•  The boiler thermostat switch contacts are not worn or 

coated, as this can cause periodic supply power cuts.

•  The cables to and from the control are positioned so 

that they cannot generate electrical noise. Please be 

particularly aware that high voltage cables from the 

electronic ignition must not be placed against or wound 

around the other electrical or electronic components, 

such as the control itself and the pump’s solenoid 

valve.

Note: Automatic controls in the OBC 80 series can only be 

reset while the supply voltage is connected.

Approvals

The controls in the OBC 80 series are approved in ac-

cordance with EN 298:2012:

Technical data

Rated voltage

230 V~

Voltage range

195 - 253 V~

Frequency

50 - 60 Hz

Supply fuse

max. 10 A

Enclosure

IP 40

Ambient temperature

-20 - +60°

C

Transportation & storage temperature

-30 - +70°

C

Undervoltage protection

< 170 V

Protection class

II

Pollution degree

2

Terminal loads

Terminal

Max. operating current

3

5 A

4

1 A

5

1 A

6 / 7

1 A

8

5 A

10

1 A

Note: Total operating current max. 5 A.

Conversion / Service

BHO 60 series

BHO 70 series

OBC 80 series

-

BHO 71.10

OBC 81.10

-

BHO 71A.10

OBC 81A.10

BHO 64

BHO 72.10

OBC 82.10

BHO 64.1

BHO 72.11

OBC 82.11

BHO 64 A

BHO 73.10

OBC 82A.12

LOA 44

BHO 74.10

OBC 84.10

GB

Содержание OBC 80 Series

Страница 1: ...gneettiventtiili Fotounit Photo unit Fotozelle Unit photo lectrique Fotoc lula Fotounit Fotocel Valoyksikk Ekstern alarm External alarm Externer Alarm Alarme externe Alarma externa Allarme esterno Ext...

Страница 2: ...OBC 81 OBC 82 OBC 84 OBC 85B OBC 82A OBC 81A Fig 3 2 Danfoss 2016 03 VI AA A4 57 OBC 80 series...

Страница 3: ...op Burner stop Brenner abschaltung Arr t du br leur Detenci n del quemador Arresto del bruciatore Stilstand brander Polttimen pys ytys E Stop efterventilering End post purge Ende der Nachbe l ftung Fi...

Страница 4: ...en in dezelfde cyclus bij OBC 84 slechts 1 poging Yli 3 uudelleenk yn nistyst samassa jaksossa OBC 84 vain 1 uudelleenk ynnistys Maks ventetid 10 min p forvarmer overskredet Max waiting time 10 min on...

Страница 5: ...le du signal de flamme Pas de flamme sombre 5 A Flamme lumi re 65 A ES Comprobaci n de la se al de llama Sin llama oscura 5 A Llama clara 65 A IT Controllo del segnale di fiamma Nessuna fiamma scuro 5...

Страница 6: ...Vorz ndung t3 Nachz n dung t3n Intervall V1 V2 t4 Sicherheits zeit t2 max Nachbel f tung t8 Fernalarm Fern entriegelung OBC 81 10 057H8701 13 13 15 10 OBC 81A 10 057H8708 13 13 15 10 OBC 81A 12 057H87...

Страница 7: ...rente alla centralina spento o se il ripristino viene effettuata su la centralina stessa NL Type Code Voorventila tie t1 Voorontste king t3 Naontsteking t3n Interval V1 V2 t4 Veiligheidstijd t2 max Na...

Страница 8: ...170V under drift afbrydes olietilf rslen og br nderen stoppes Reset knappen vil i begge tilf lde automatisk blinke 8 gange N r netsp ndingen n r op p 185 V genstarter automaten p normal vis Bem rk ve...

Страница 9: ...es the reset button will automatically flash 8 times When the mains voltages reaches 185 V the control will re start as normal Please note that the control cannot be reset if the mains voltage is belo...

Страница 10: ...erden die lzufuhr und der Brenner gestoppt In beiden F l len blinkt die Reset Taste automatisch 8 Mal Wenn die Netzspannung 185 V erreicht startet der Automat wieder normal Achtung Ein Reset des lfeue...

Страница 11: ...le bouton de r initialisation clignote automatiquement 8 fois Lorsque la tension de secteur atteint 185 V le contr leur red marre normalement Noter que le contr leur ne peut tre r initialis si la tens...

Страница 12: ...el ctrica cae por debajo de 185 V antes del arranque el control se bloquear y no podr arrancar Si la tensi n de la red el ctrica cae por deba jo de 170 V durante el funcionamiento el suministro de com...

Страница 13: ...i il pulsante di ripristino lampegger automatica mente per 8 volte Quando la tensione di rete raggiun ge 185 V l unit di controllo si riavvier normalmente Si deve tener conto che l unit di controllo n...

Страница 14: ...n de olietoevoer en de oliebrander stilgezet In beide gevallen zal de resetknop automatisch 8 keer knipperen Wanneer de netspanning 185 V bereikt wordt de relais opnieuw en op de normale manier gestar...

Страница 15: ...nollauspainike vilkahtaa automaattisesti 8 kertaa Kun verkkoj nnite saavuttaa 185 V s din k ynnistyy uu delleen normaalisti Huomaa ett s dint ei voi k ynnist uudelleen jos verkkoj nnite on alle 170 V...

Страница 16: ...ter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed All trademarks in th...

Отзывы: