27-32 Stage On Speed (Hz)
Range:
Function:
par. 4-14* [par. 4-12 – par. 4-14]
To be used if Hz is chosen.
If the lead pump is operating above Stage On Speed for the time specified in Staging Delay (par.
27-23), and a variable speed pump is available, it will be turned on.
27-33 Stage Off Speed (RPM)
Range:
Function:
par. 4-11* [par. 4-11 – par. 4-13]
If the lead pump is operating below Stage Off Speed for the time specified in De-staging Delay (par.
27-24), and more than one variable speed pump is on, a variable speed pump will be turned off.
27-34 Stage Off Speed (Hz)
Range:
Function:
par. 4-12* [par. 4-12 – par. 4-14]
If the lead pump is operating below Stage Off Speed for the time specified in De-staging Delay (par.
27-24), and more than one variable speed pump is on, a variable speed pump will be turned off.
6.1.7 Staging Settings, 27-4*
Parameters for configuring staging transitions.
6.1.8 Auto-tune Staging Settings, 27-40
27-40 Auto-tune Staging Settings
Option:
Function:
When enabled, the staging threshold will be auto-tuned during operation. The settings are optimized
in order to prevent overpressure and underpressure when staging and de-staging. If disabled, the
thresholds can be set manually.
[0]
Disabled
Staging or de-staging threshold.
[1] *
Enabled
27-41 Ramp-down Delay
Range:
Function:
10 s*
[0 s –120 s]
Ramp-down Delay sets the delay between turning on a soft starter controlled pump and ramping
down the drive-controlled pump. This is only used for soft starter-controlled pumps.
Extended and Advanced Cascade Controller
Option
6 How to Program