Figure 4.1: Staging:
A: Incorrectly adjusted stage on speed
B: Correctly adjusted stage on speed
C: Stage on speed pump 2
When the system is set in operation, it will monitor the actual energy consumption and fine adjust every time a stage or de-stage takes place.
Over time, this feature will ensure the most energy-efficient operation, taking into account wear and tear on the pump system.
Danfoss has made available the Multiple Unit Staging Efficiency Calculator (MUSEC), a free software program available on the Danfoss web site. By
entering pump and system data, MUSEC provides the optimal settings for the Stage On and Stage Off speed parameters.
4.1.6 Staging/De-staging of Fixed-speed Pumps Based on Pressure Feedback
Fixed speed pumps are staged based on a drop in system pressure, and are de-staged based on an increase in system pressure.
Since it is undesirable to have pumps turning on and off rapidly, an acceptable range of system pressure needs to be defined along with a period of time
the pressure is allowed to be outside of this range before staging or de-staging occurs. These values are set through parameters 27-20 “Normal Operating
Range” 27-23 “Staging Delay” and 27-24 “De-staging Delay”.
These parameters are installation dependent and should be set to meet the requirements of the system.
Automatic stage / de-stage threshold
The speed of the variable speed pump at the point of staging or de-staging is defined by a stage threshold or a de-stage threshold. These settings are
used in order to reduce minimum overpressure/underpressure at staging or de-staging as much as possible.
Compared to the basic cascade built in the drive, these settings can be auto-tuned in extended and advanced cascade options MCO101 and MCO102.
If enabled, the auto-tune of the staging and de-staging threshold monitors the feedback at the point of staging or de-staging and fine-adjusts the settings
every time staging takes place in order to keep the system optimized over time while taking into account wear and tear on the pumps.
New parameter descriptions:
Number
Display name
Range
Default
27-30
Auto Tune Staging Speeds
{Disabled [0], Enabled [1]}
Enabled [1]
27-40
Auto-tune Staging Settings
{Disabled [0], Enabled [1]}
Enabled [1]
Extended and Advanced Cascade Controller
Option