3 Introduction to MCF 106 A/ B in C Option Adaptor
The A/ B in C Option Adaptor makes it possible to combine a number of different options.
130BB093.10
Illustration 3.1: Drawing of MCF 106 A/B in C Option Adaptor.Two options can be installed in the MCF 106 at the same time. The upper slot is called E0
and the lower is called E1.
One A and one B option can be installed in the standard A and B slots of the Control Card – behind the LCP/ Blind cover. With the addition of the MCF
106 the possibilities are increased.
•
Up to three different B options – one in the standard B slot and two in the Adaptor
•
One Fieldbus (A option) at any time – in the standard A slot or in the E0 slot of the adaptor.
•
The MCB 121 Ethernet takes up both slot A and slot B when installed in the standard slot A of the Control Card. The only way to to install a B
option at the same time: Use the standard B slot of the Control Card and move the MCA 121 in the E1 slot of the Adapter.
•
MCA 121 EthernetIP has bottom entry when installed in the Adaptor
•
Two identical options can not be installed at the same time
•
MCB 105 Relay Card and MCB 112 PTC Thermistor Card are not supported by the Adaptor and must thus only be installed in the standard slot
B of the Control Card. That also means that these two options can not be combined.
130BB094.11
MCF 106
B*
B
A
A*
Illustration 3.2: Generally, A- and B options can be installed in the MCF 106. The exceptions are the special B options (B*) MCB 105 Relay Card and MCB
112 PTC Thermistor Card that both have an extra large plastic part and are not supported by the MCF 106. Also the special A option (A*) MCA 121
EthernetIP that takes up the size of almost two standard options is an exception as it can only be installed in the lower slot of MCF 106 and with bottom
entry.
MCF 106 A/B in C Option Adaptor Instruction
3 Introduction to MCF 106 A/ B in C Option
Adaptor
MI.38.F1.02 - VLT
®
is a registered Danfoss trademark
7
3