background image

1.

Command the MCD 500 to start. While the MCD 500 is starting, measure the voltage across each phase. The voltage should fall to less than
2 VAC just before the soft starter reaches Run mode.

If the voltage remains near nominal mains voltage, the SCR is not firing correctly. The Main Control PCB, Backplane PCB or connection between
these items may be faulty.

If the voltage starts near nominal mains voltage then falls to less than 2 VAC just before the MCD 500 reaches Run mode, the MCD 500 is operating
correctly and the cause of the starting problem is not the soft starter.

 

2.2.3 Run Performance Test

Models MCD5-0021B - MCD5-0215B incorporate internal bypass contactors. If the internal bypass contactor does not operate, the SCRs will eventually
fail due to thermal stress. This procedure tests the operation of the internal bypass contactors. Use this test if the starter trips with "Bypass Fail" or "Time
Overcurrent".

This test is performed using either an AC voltmeter.

1.

Connect the MCD 500 to mains voltage, control voltage and to a motor.

2.

Measure the voltage across each phase (L1-T1, L2-T2, L3-T3). This should be close to the nominal mains voltage (phase voltage for in-line
connection and line voltage for inside delta connection).

If the voltage is zero, the SCR on that phase may have failed.

If the voltage is not equivalent to the nominal mains voltage, the bypass contactor may be damaged and should be replaced.

1.

Command the soft starter to start. When the Run LED (green) stops flashing, you should hear the bypass contactor close.

If the bypass contactor does not close, the bypass contactor, Main Control PCB, Model PCB or Bypass Driver PCB (models MCD5-0131B -
MCD5-0215B only) may be faulty or there may be a faulty connection between these components.

1.

When the soft starter is running, measure the voltage across each phase. This should be less than 0.5 VAC.

2.

Command the soft starter to stop and listen for the bypass contactor to open. If the MCD 500 is configured for soft stop, this should occur when
the Run LED (green) starts flashing. If the MCD 500 is not configured for soft stop, this should occur when the Run LED turns off.

NB!

The bypass contactors used in the MCD 500 are latching. The MCD 500 control circuits are designed to open the bypass contactors
even in the event of removal or loss of control voltage. However it is still possible that the bypass contactor may be closed when there
is no control supply to the soft starter. The bypass contactors will open when control voltage is next applied.

Control Input Test

This procedure tests the condition of the soft starter control inputs. This test is performed using a wire link.

1.

Disconnect all external wiring from the soft starter's control inputs.

2.

Control voltage must still be connected to the soft starter.

3.

Connect a wire link between each input.

If the corresponding LED lights up then the input is operating correctly.

If the LED does not light up, the control input is damaged. Replace the Main Control PCB

2.3 Trip Messages

This table lists soft starter's protection mechanisms and the probable cause of the trip. Some of these can be adjusted using parameter group 2

Protection

 and parameter group 16 

Protection Action

, other settings are built-in system protections and cannot be set or adjusted.

2 Troubleshooting

MCD 500 Service Manual

6

MG.17.L1.02 - VLT

®

 is a registered Danfoss trademark

2  

Содержание MCD 500

Страница 1: ...MCD5 0927C G4C 18 MCD5 1200C MCD5 1600C G5C 19 4 Spare Parts 21 Spare Parts 21 Main Control PCB 21 Model PCB 22 Backplane PCB 23 Bypass Driver PCB 24 SCRs and Power Assemblies 25 Fans 26 Current Trans...

Страница 2: ...Using the Soft Starter to Switch a Contactor 36 Control Input 36 Contents MCD 500 Service Manual 2 MG 17 L1 02 VLT is a registered Danfoss trademark...

Страница 3: ...nual and local electrical safety codes Disconnect the soft starter from mains voltage before carrying out repair work It is the responsibility of the user or person installing the soft starter to prov...

Страница 4: ...2 Troubleshooting MCD 500 Service Manual 4 MG 17 L1 02 VLT is a registered Danfoss trademark 2...

Страница 5: ...ect operation If the resistance is above 500 k for any measurement the Main Control PCB or Interface PCB may be faulty or there may be a faulty connection between these two PCBs To isolate the fault p...

Страница 6: ...contactor Main Control PCB Model PCB or Bypass Driver PCB models MCD5 0131B MCD5 0215B only may be faulty or there may be a faulty connection between these components 1 When the soft starter is runnin...

Страница 7: ...using inside delta con figuration rather than in line connection If the soft starter is connected in line but the selected motor FLC is above the in line maximum the soft starter will trip at start R...

Страница 8: ...3 1 4 16 1 Motor Connection The motor is not connected correctly to the soft starter for inline or inside delta use Check individual motor connections to the soft starter for power circuit continuity...

Страница 9: ...ntact your local distributor Related Pars 16 10 Thermistor Cct The thermistor input has been enabled and The resistance at the input has fallen below 20 the cold resistance of most thermistors will be...

Страница 10: ...to complete the start successfully Wait for the motor to cool before attempting another start The emergency stop function may be active If Par 3 3 is set to Emergency Stop and there is an open circuit...

Страница 11: ...thermistor input is enabled once a link is fitted and short circuit protection has activated Remove the link then load the default parameter set This will disable the thermistor input and clear the tr...

Страница 12: ...3 Service Instructions MCD 500 Service Manual 12 MG 17 L1 02 VLT is a registered Danfoss trademark 3...

Страница 13: ...ows Class MCD 500 Models G1B MCD5 0021B MCD5 0037B MCD5 0043B MCD5 0053B MCD5 0068B MCD5 0084B MCD5 0089B MCD5 0105B G2B MCD5 0131B MCD5 0141B MCD5 0195B MCD5 0215B G3C MCD5 0245C G4C MCD5 0360C MCD5...

Страница 14: ...2 8 1 Cover 6 Model PCB 2 Cable guide 7 Current transformers 3 Main plastic 8 Mounting posts 4 Terminal blocks 9 SCRs 5 LCP and Main Control PCB 10 Side plastic 3 Service Instructions MCD 500 Service...

Страница 15: ...0 1 Cover 7 Current transformers 2 Cable guide 8 Mounting posts 3 Main plastic 9 SCRs 4 Terminal blocks 10 Side plastic 5 LCP and Main Control PCB 11 Fan 6 Model PCB MCD 500 Service Manual 3 Service I...

Страница 16: ...pport plastic 2 Main plastic 8 Model PCB 3 Cable guide 9 Current transformers 4 Terminal blocks 10 SCRs 5 LCP and Main Control PCB 11 Main body 6 Bypass Driver PCB 12 Fan and bracket 3 Service Instruc...

Страница 17: ...7 Support plastic 2 Cable guide 8 Model PCB 3 Main plastic 9 Current transformers 4 Terminal blocks 10 SCRs 5 LCP and Main Control PCB 11 Main body 6 Fan assembly MCD 500 Service Manual 3 Service Ins...

Страница 18: ...n plastic 8 Magnetic bypass plate models 0595 C 0927C 3 Cable guide 9 Fan assembly 4 Support plastic 10 Power assembly 5 Model PCB 11 Current transformer assembly 6 Module mount and spacer plastic 12...

Страница 19: ...etic bypass plate 2 Main plastic 8 Fan assembly 3 Cable guide 9 Power assembly 4 LCP and Main Control PCB 10 Current transformer assembly 5 Support plastic 11 Main body 6 Model PCB MCD 500 Service Man...

Страница 20: ...4 Spare Parts MCD 500 Service Manual 20 MG 17 L1 02 VLT is a registered Danfoss trademark 4...

Страница 21: ...21B 175G5603 175G5604 175G5601 175G5602 MCD5 0037B MCD5 0043B MCD5 0053B MCD5 0068B MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B 175G5607 175G5608 175G5605 175G5606 MCD5 0141B MCD5 0195B MCD5 0215B MCD...

Страница 22: ...5613 MCD5 0595C 175G5625 MCD5 0084B 175G5614 MCD5 0619C 175G5626 MCD5 0089B 175G5615 MCD5 0790C 175G5627 MCD5 0105B 175G5616 MCD5 0927C 175G5628 MCD5 0131B 175G5617 MCD5 1200C 175G5629 MCD5 0141B 175G...

Страница 23: ...B MCD5 0068B MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B Not required MCD5 0141B MCD5 0195B MCD5 0215B MCD5 0245C MCD5 0360C MCD5 0380C MCD5 0428C MCD5 0595C MCD5 0619C MCD5 0790C MCD5 0927C MCD5 1200...

Страница 24: ...3B MCD5 0068B MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B 175G5633 MCD5 0141B MCD5 0195B MCD5 0215B MCD5 0245C Not required MCD5 0360C MCD5 0380C MCD5 0428C MCD5 0595C MCD5 0619C MCD5 0790C MCD5 0927C...

Страница 25: ...MCD5 0245C 175G5127 Models MCD5 0360C MCD5 1600C use power assemblies Each soft starter requires two power assemblies MCD5 0360C 175G5636 MCD5 0380C 175G5637 MCD5 0428C 175G5638 MCD5 0595C 175G5639 M...

Страница 26: ...MCD5 0068B 175G5646 1 MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B MCD5 0141B Not required MCD5 0195B 175G5646 1 MCD5 0215B MCD5 0245C 175G564647 3 MCD5 0360C MCD5 0380C MCD5 0428C MCD5 0595C MCD5 0619...

Страница 27: ...5 0131B 175G5650 MCD5 0141B MCD5 0195B MCD5 0215B MCD5 0245C 175G5650 MCD5 0360C 175G5652 MCD5 0380C 175G5653 MCD5 0428C MCD5 0595C 175G5654 MCD5 0619C MCD5 0790C 175G5655 MCD5 0927C 175G5656 MCD5 120...

Страница 28: ...ter requires three bypass contactors MCD5 0021B Not required MCD5 0037B MCD5 0043B MCD5 0053B MCD5 0068B 175G5660 MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B 175G5661 MCD5 0141B MCD5 0195B MCD5 0215B...

Страница 29: ...0053B MCD5 0068B MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B 175G5668 175G5672 Not required MCD5 0141B MCD5 0195B MCD5 0215B MCD5 0245C Not required MCD5 0360C MCD5 0380C MCD5 0428C MCD5 0595C MCD5 0...

Страница 30: ...72 175G5669 support plastic Complete plastics MCD5 0021B 175G5673 MCD5 0037B MCD5 0043B MCD5 0053B MCD5 0068B MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B 175G5674 MCD5 0141B MCD5 0195B MCD5 0215B MCD5...

Страница 31: ...174G5682 MCD5 0089B MCD5 0105B MCD5 0131B 175G5696 175G5683 MCD5 0141B 175G5684 175G5685 MCD5 0195B MCD5 0215B MCD5 0245C 175G5686 set of 6 175G5687 MCD5 0360C 175G5688 175G5689 MCD5 0380C MCD5 0428C...

Страница 32: ...175G5686 175G5687 175G5688 175G5690 175G5692 175G5694 175G5689 175G5691 175G5693 175G5695 4 Spare Parts MCD 500 Service Manual 32 MG 17 L1 02 VLT is a registered Danfoss trademark 4...

Страница 33: ...MCD5 0043B MCD5 0053B MCD5 0068B MCD5 0084B MCD5 0089B MCD5 0105B MCD5 0131B Not required MCD5 0141B MCD5 0195B MCD5 0215B MCD5 0245C MCD5 0360C MCD5 0380C MCD5 0428C MCD5 0595C MCD5 0619C MCD5 0790C...

Страница 34: ...5 Avoiding Damage MCD 500 Service Manual 34 MG 17 L1 02 VLT is a registered Danfoss trademark 5...

Страница 35: ...Protecting SCRs Modern SCRs are generally rugged and reliable However the risk of SCR damage can be reduced by using semiconductor fuses and or a main contactor 5 1 3 Semiconductor Fuses Semiconductor...

Страница 36: ...ay 2 Slave relay coil 3 Contactor coil A2 A10 A1 A11 177HA338 11 1 2 1 Soft starter output relay 2 Contactor coil 5 3 Control Input MCD 500 soft starters can be operated by external two wire or three...

Отзывы: