Warnings
The MCD 201 & MCD 202 contain
dangerous voltages when connected to
line voltage. Only a competent electrician
should carry out the electrical installation.
Improper installation of the motor or the
MCD 201 & MCD 202 may cause
equipment failure, serious injury or death.
Follow this manual and National Electrical
Codes (NEC
®
) and local safety codes.
Safety regulations
1.
The soft starter must be disconnected from the
mains if repair work is to be carried out.
2.
Stopping the soft starter of the does not
disconnect the equipment from the mains and
leaves one phase connected to the motor. Thus
the soft starter is not to be used as a safety
switch.
It is the responsibility of the user or the
person installing the MCD 201 & MCD
202 to provide proper grounding and
branch circuit protection according to the
National Electric Code (NEC
®
) and local
codes.
Symbols used in this manual
The following symbols indicate items that require
special attention:
Indicates a general warning.
Indicates a high voltage warning.
Avoiding soft starter damage
Please read and follow all instructions in this manual.
Additionally, take special note of the following:
1.
Do not connect power factor correction
capacitors to the soft starter output. Static power
factor correction, if used, must be connected on
the mains side of the soft starter.
Electrostatic Precaution: Electrostatic
discharge (ESD). Many electronic
components are sensitive to static
electricity. Voltages so low that they
cannot be felt, seen or heard, can reduce
the life, affect performance, or
completely destroy sensitive electronic
components. When performing service,
proper ESD equipment should be used
to prevent possible damage from
occurring.