Table 21: Parameter 5-24 Terminal X46/9 Digital Input
Option
Function
[0]*
No operation
This parameter is active when option module VLT® Extended Relay Card MCB 113 is installed in the drive.
Functions are described in
parameter group 5-1* Digital Inputs
.
Table 22: Parameter 5-25 Terminal X46/11 Digital Input
Option
Function
[0]*
No operation
This parameter is active when option module VLT® Extended Relay Card MCB 113 is installed in the drive.
Functions are described in
parameter group 5-1* Digital Inputs
.
Table 23: Parameter 5-26 Terminal X46/13 Digital Input
Option
Function
[0]*
No operation
This parameter is active when option module VLT® Extended Relay Card MCB 113 is installed in the drive.
Functions are described in
parameter group 5-1* Digital Inputs
.
4.2.3 Parameter Group 5-3* Digital Outputs
The 2 solid-state digital outputs are common for terminals 27 and 29. Set the I/O function for terminal 27 in
parameter 5-01 Terminal 27
Mode
, and set the I/O function for terminal 29 in
parameter 5-02 Terminal 29 Mode
.
NOTICE
These parameters cannot be adjusted while the motor is running.
Table 24: 5-30 Digital Outputs - 1
Option
Function
[0]
No operation
Default for all digital outputs and relay outputs.
[1]
Control ready
The control card is ready, for example: Feedback from a drive controlled by a 24 V external supply
(VLT® 24 V DC Supply MCB 107) and the main power to the unit is not detected.
[2]
Drive ready
The drive is ready for operation and applies a supply signal on the control card.
[3]
Drive rdy/rem ctrl
The drive is ready for operation and is in auto-on mode.
[4]
Enable/no warning
Ready for operation. No start or stop command has been given (start/disable). No warnings are ac-
tive.
[5]
Running
The motor runs, and shaft torque is present.
[6]
Running/no warn-
ing
The output speed is higher than the speed set in
parameter 1-81 Min Speed for Function at Stop [RPM]
.
The motor runs and there are no warnings.
[7]
Run inrange/no
warn
The motor runs within the programmed current and speed ranges set in
parameter 4-50 Warning
Current Low
to
parameter 4-53 Warning Speed High
. There are no warnings.
[8]
Run on ref/no warn
The motor runs at reference speed. There are no warnings.
[9]
Alarm
An alarm activates the output. There are no warnings.
[10]
Alarm or warning
An alarm or warning activates the output.
Parameter Setup
Operating Guide | VLT® Extended Relay Card MCB 113