© Danfoss | DCS (im) | 2017.07

IC.PS.P40.B3.52 | 520B7739 | 9

INSTALLATION NOTES 

SAFETY INSTRUCTIONS

For safe installation of MBT 9110 084Z7443 the following must be observed. The module shall only be Installed by qualified 

personnel who are familiar with the national and international laws, directives and standards that apply to this area. 

Year of manufacture can be taken from the first two digits in the serial number.
The sensor circuit is not infallibly galvanic isolated from the input circuit. However, the galvanic isolation between the circuits is 

capable of withstanding a test voltage of 500 VAC during 1 minute.
In a potentially explosive gas atmosphere, the transmitter shall be mounted in an enclosure in order to provide a degree of 

protection of at least IP20 according to EN60529.
If the transmitter is installed in an explosive atmosphere requiring the use of equipment of category 1G and if the enclosure is 

made of aluminium, it must be installed such, that even in the event of rare incidents, ignition sources due to impact and friction, 

sparks are excluded; if the enclosure is made of non-metallic materials, electrostatic charging shall be avoided.

For installation in a potentially explosive dust atmosphere, the following instructions apply:

The transmitter shall be mounted in a metal enclosure form B according to DIN43729 that is providing a degree of protection of 

at least IP6X according to EN60529, that is suitable for the application and correctly installed.
Cable entries and blanking elements shall be used that are suitable for the application and correctly installed.
For an ambient temperature ≥ 60 °C, heat resistant cables shall be used with a rating of at least 20 K above the ambient 

temperature.
The surface temperature of the enclosure is equal to the ambient temperature plus 20 K, for a dust layer with a thickness up to 5 mm.

Danfoss A/S

Danfoss Industrial Automation

DK 6430 Nordborg Denmark

Phone +45 7488 2222

Содержание MBT 9110

Страница 1: ...old 12 12 Product type Myriad Pro light 12 12 xxxRxxxx bar code place holder xxxRxxxx bar code place holder Danfoss DCS xxx YYYY MM Myriad Pro Regular 7 pt XXXX XX XXX XX XX XXX XXXAXXXX 1 Temperature...

Страница 2: ...2017 07 2 520B7739 IC PS P40 B3 52 INDEX 2 Wire Programmable Transmitter Page 3 UK 2 Tr ds Programmerbar Transmitter Side 10 DK Transm 2 fils universel Pt100 TC Page 17 FR 2 Leiter Universalmessumfor...

Страница 3: ...dous areas the MBT 9110 084Z7443 can be mounted on a DIN rail with a special fitting 2 WIRE PROGRAMMABLE TRANSMITTER MBT 9110 084Z7443 ENGLISH APPLICATIONS V mA V mA V RTD to 4 20 mA 2 wire installati...

Страница 4: ...PECIFICATIONS INPUT RTD AND LINEAR RESISTANCE INPUT RTD type Min value Max value Min span Standard Pt 100 200 C 850 C 25 C IEC 60751 Ni 100 60 C 250 C 25 C DIN 43760 Lin R 0 5000 30 BASIC VALUES Input...

Страница 5: ...C584 K 180 C 1372 C 50 C IEC584 L 100 C 900 C 50 C DIN 43710 N 180 C 1300 C 100 C IEC584 R 50 C 1760 C 200 C IEC584 S 50 C 1760 C 200 C IEC584 T 200 C 400 C 50 C IEC584 U 200 C 600 C 75 C DIN 43710 W3...

Страница 6: ...Emission and immunity EN 61326 1 ATEX 94 9 EF EN 60079 0 EN 60079 11 EN 60079 15 EN 60079 26 EN 61241 0 EN 61241 11 KEMA 04ATEX1339 II 1 G Ex ia IIC T4 or T6 II 1 D Ex iaD Max amb temperature for T4...

Страница 7: ...elow and the help functions in PReset Loop Link is not approved for communication with modules installed in hazard ous Ex areas ORDER LOOP LINK 1 2 Loop Link 5909 USB 5905 RS232 MBT9110 Disconnect Con...

Страница 8: ...3 ATEX Certificate KEMA 04ATEX 1339 Marking II 1 G Ex ia IIC T6 T4 II 1 D Ex iaD Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 26 2007 EN 61241 0 2006 EN 61241 11 2006 1 2 6 5 4 3 Barrier Hazard...

Страница 9: ...uipment of category 1G and if the enclosure is made of aluminium it must be installed such that even in the event of rare incidents ignition sources due to impact and friction sparks are excluded if t...

Страница 10: ...rm B f lerhoved I ikke eksplosionsfarlige omr der kan MBT 9110 084Z7443 monteres p en DIN skinne med et specielt beslag 2 TR DS PROGRAMMERBAR TRANSMITTER MBT 9110 084Z7443 DANISH APPLIKATIONER V mA V...

Страница 11: ...dring 0 005 af span VDC Vibration IEC 60068 2 6 Test FC Lloyd s specifikation nr 1 4 g 2 100 Hz Max ledningskvadrat 1 x 1 5 mm2 stranded wire Luftfugtighed 95 RH non cond M l 44 x 20 2 mm T thedsgrad...

Страница 12: ...C584 K 180 C 1372 C 50 C IEC584 L 100 C 900 C 50 C DIN 43710 N 180 C 1300 C 100 C IEC584 R 50 C 1760 C 200 C IEC584 S 50 C 1760 C 200 C IEC584 T 200 C 400 C 50 C IEC584 U 200 C 600 C 75 C DIN 43710 W3...

Страница 13: ...ission og immunitet EN 61326 1 ATEX 94 9 EF EN 60079 0 EN 60079 11 EN 60079 15 EN 60079 26 EN 61241 0 EN 61241 11 KEMA 04ATEX1339 II 1 G Ex ia IIC T4 eller T6 II 1 D Ex iaD Max omgivelsestemp for T4 8...

Страница 14: ...Z7442 084Z7443EEx PGA D A Comu A D CPU E E PR OM Indganggnd Forsyning 4 20 mA Forsyning 7 2 35VDC TC Ext CJC mV RTD lin R tr d Ex kredsl b kun 084Z7443 Int CJC 1 2 Loop Link 5909 USB 5905 RS232 MBT911...

Страница 15: ...ATEX Certificate KEMA 04ATEX 1339 Marking II 1 G Ex ia IIC T6 T4 II 1 D Ex iaD Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 26 2007 EN 61241 0 2006 EN 61241 11 2006 1 2 6 5 4 3 Barrier Hazardo...

Страница 16: ...yr i kategori 1G og hvis kapslingen er lavet af aluminium skal den installeres s ledes at gnister fra ant ndelseskilder ved slag og friktion selv under us dvanlige omst ndigheder holdes ude Er kapslin...

Страница 17: ...zone non dangereuse le MBT 9110 084Z7443 peut tre mont sur rail DIN avec un raccord sp cial TRANSMETTEUR 2 FILS UNIVERSEL Pt100 TC MBT 9110 084Z7443 FRAN AIS APPLICATIONS V mA V mA V mA RTD en 4 20 m...

Страница 18: ...ATIONS LECTRIQUES ENTR E ENTR E RTD ET ENTR E R SISTANCE LIN AIRE RTD type Valeur min Valeur max Plage min Standard Pt 100 200 C 850 C 25 C IEC 60751 Ni 100 60 C 250 C 25 C DIN 43760 Lin 0 5000 30 VAL...

Страница 19: ...C584 K 180 C 1372 C 50 C IEC584 L 100 C 900 C 50 C DIN 43710 N 180 C 1300 C 100 C IEC584 R 50 C 1760 C 200 C IEC584 S 50 C 1760 C 200 C IEC584 T 200 C 400 C 50 C IEC584 U 200 C 600 C 75 C DIN 43710 W3...

Страница 20: ...108 CE Emission et immunit EN 61326 1 ATEX 94 9 CE EN 60079 0 EN 60079 11 EN 60079 15 EN 60079 26 EN 61241 0 EN 61241 11 KEMA 04ATEX1339 II 1 G Ex ia IIC T4 or T6 II 1 D Ex iaD Temp rature amb max T4...

Страница 21: ...05 RS232 MBT9110 D branch Valim Connexionfacultative Noir Rouge Jaune Verte Entr e APIouautres Connecteur File Product Input Output Communication Language Option 08 30 00 Pr etop 5331 Date 2004 8 10 S...

Страница 22: ...84Z7443 ATEX Certificate KEMA 04ATEX 1339 Marking II 1 G Ex ia IIC T6 T4 II 1 D Ex iaD Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 26 2007 EN 61241 0 2006 EN 61241 11 2006 1 2 6 5 4 3 Barrier...

Страница 23: ...le bo tier est en aluminium il doit tre mont d une telle mani re que m me dans le cas d incidents rares les sources d inflammation dues aux impacts et la friction et les tincelles ne puissent se prod...

Страница 24: ...N Form B Sensorkopf Montage Im sicheren Bereich kann der MBT 9110 084Z7443 auf einer DIN Schiene mittels eines speziellen Beschlages 2 DRAHT UNIVERSALMESSUMFORMER MBT 9110 084Z7443 DEUTSCH ANWENDUNGEN...

Страница 25: ...ANG WTH UND LINEARER WIDERSTANDSEINGANG WTH Typ Min Wert Max Wert Min Spanne Norm Pt 100 200 C 850 C 25 C IEC 60751 Ni 100 60 C 250 C 25 C DIN 43760 Lin R 0 5000 30 GRUNDWERTE Eingangsart Grund Genaui...

Страница 26: ...IEC584 K 180 C 1372 C 50 C IEC584 L 100 C 900 C 50 C DIN 43710 N 180 C 1300 C 100 C IEC584 R 50 C 1760 C 200 C IEC584 S 50 C 1760 C 200 C IEC584 T 200 C 400 C 50 C IEC584 U 200 C 600 C 75 C DIN 43710...

Страница 27: ...sion und Immunit t EN 61326 1 ATEX 94 9 EC EN 60079 0 EN 60079 11 EN 60079 15 EN 60079 26 EN 61241 0 EN 61241 11 KEMA 04ATEX1339 II 1 G Ex ia IIC T4 oder T6 II 1 D Ex iaD Max Umgebungstemp f r T4 85 C...

Страница 28: ...ilfe Funktion im PReset Programm Loop Link darf nicht zur kommunikation mit Modulen die in Ex gef hrdeten Bereichen installiert sind benutz werden BESTELLANGABE LOOP LINK 1 2 Loop Link 5909 USB 5905 R...

Страница 29: ...Z7443 ATEX Certificate KEMA 04ATEX 1339 Marking II 1 G Ex ia IIC T6 T4 II 1 D Ex iaD Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 26 2007 EN 61241 0 2006 EN 61241 11 2006 1 2 6 5 4 3 Barrier Ha...

Страница 30: ...das Geh use aus Aluminium hergestellt ist muss der Messumformer so installiert werden dass selbst bei seltenen Ereignissen Z ndquellen durch Schl gen oder Reibung keine Funken auftreten k nnen Bei ei...

Страница 31: ...Danfoss DCS im 2017 07 IC PS P40 B3 52 520B7739 31...

Страница 32: ...Danfoss DCS im 2017 07 IC PS P40 B3 52 520B7739 32...

Отзывы: