background image

8510223 P01-A     © Danfoss Commercial Compressors March 2006

Instructions

main.  The  values  for  the  compressor  electrical 
motor can be directly displayed on the frequency 
converter control panel.
•  Monitor  the  oil  sight  glass  for  60  min.  after 
system  equilibrium  to  ensure  proper  oil  return 
to the compressor. This oil check has to be done 
over the speed range to garanty:
  - a good oil return at low speed when gas velo-
city is at it’s minimum,
  - a good oil management at high speed where 
oil carry over is at it’s maximum.
• Suction superheat setting: Optimal compressor 
suction superheat would be around 10K, with the 
maximum allowable superheat being 30K.
•  In  all  cases,  the  application  limits  of  the 
compressor  must  be  respected;  moreover, 
high  superheat  values  lead  to  high  discharge 
temperatures and decrease compressor capacity. 
The  maximum  discharge  temperature  is  130°C: 
operating at a higher temperature may result in 
refrigerant decomposition.
•  Under  steady-state  operating  conditions,  check 
refrigerant  piping  or  capillary  tubes  for  abnormal 
vibrations (refrigeration line movement in excess of 1.5 
mm necessitates corrective actions, pipe brackets, etc.).
•  After  2  to  4  hours  of  operations  under 
established  conditions,  check  the  oil  level  and 
add oil if necessary (refer to TI 2-025). If oil return 
continues to perform poorly, further investigation 
of the piping design is required.
• Ensure that refrigerant flow through the liquid 
line sight glass (when mounted) is adequate and 
that  operating  temperatures  correspond  with 
system specifications.
• When needed, refrigerant may be added in the 
liquid  phase,  carefully  throttling  the  refrigerant 
on  the  low-pressure  side  and  as  far  as  possible 
from  the  compressor.  The  compressor  must  be 
operating during this process at a medium speed 
if possible (this can be manually hand forced at 
50 Hz for exemple).

 Do not overcharge the system.

11 – Troubleshooting

•  Compressor  failure  to  start:  Verify  that  the 
compressor  is  hooked  up  to  the  frequency 
converter; check the power lead connections. If 
these verifications reveal no abnormality, control 
the motor windings with an ohmmeter.
•  Check  the  frequency  converter  control  panel: 
If  any  alarm  is  displayed  check  the  wiring  and 
specially  the  polarity  of  the  control  cables, 
when  an  alarm  is  shown  refer  to  the  converter 
application  manual  and  specially  revue  the 
electrical motor parameters set in.
• Compressor failure to build up pressure: Check 
to make sure that all bypass valves in the system 
have  not  been  opened.  Also  check  that  all 
solenoid valves are in their proper position. 
• Abnormal running noise: Ensure the absence of 
any liquid flood-back to the compressor by means 
of measuring the return gas superheat and com-
pressor sump temperature. The sump should be at 
least 10K above the saturated suction temperature 
under steady-state operating conditions.
•  The  high-pressure  switch  trips  out:  Check 
condenser  operations  (condenser  cleanliness, 
fan  operations,  water  flow  and  water  pressure 
valve,  water  filter,  etc.).  If  above  check  out  OK, 
the  problem  may  be  due  to  either  refrigerant 
overcharging  or  the  presence  of  a  non-
condensable (e.g. air, moisture) in the circuit.

• The low-pressure switch trips out: Check evapo-
rator operations (coil cleanliness, fan operations, 
water  flow,  water  filter,  etc.),  liquid  refrigerant 
flow  and  pressure  drops  (solenoid  valve,  filter 
dryer, expansion valve, etc.), refrigerant charge.
• Low refrigerant charge: The correct refrigerant 
charge  is  given  by  the  liquid  sight  glass  indica-
tion, the condenser delta T in relation to the re-
frigerant pressure tables (pressure-temperature), 
the superheat and the sub-cooling, etc. (if addi-
tional  charge  is  deemed  necessary,  refer  to  the 
“Filling the system” section).
• Compressor short cycling: The number of cycles 
shall never exceed 12 starts per hour.

12 - Maintenance

• Maneurop® compressors do not necessitate any 
special maintenance procedure. However, it must 
be  recalled  that  proper  operations  and  mainte-
nance of the system serve to prevent against sys-
tem-related  compressor  problems. The  following 
preventive maintenance checks, to be performed 
at regular intervals, are highly recommended:
  -  Control  operating  conditions  (evaporating 
temperature, condensing temperature, compres-
sor discharge temperature, temperature differen-
ce on heat exchangers, superheat, sub-cooling). 
These  conditions  must  always  remain  within 
compressor operation limits.
  - Verify that safety devices are operational and 
properly set.
  -  Check  the  compressor  oil  level  and  qua-
lity; this step may include an acid test, humidity 
check, spectrometer analysis, etc. whenever the 
oil becomes discolored.
  - Ensure that the circuit is leak tight.
  - Verify  the  proper  operation  of  heat  exchan-
gers and, if necessary, clean them.
  - Check the current draw on the compressor motor 
as well as proper voltage balance between phases.
  - Check that all electrical connections are still 
adequately fastened.
  - Make sure the compressor is clean and in good 
working  order;  verify  the  absence  of  rust  on  the 
compressor shell, piping and electrical connections.
  -  Make  sure  the  refrigerant  charge  is  suitable 
for both winter and summer operations.
•  Insure  that  periodic  in-service  inspections 
required by local regulations are performed.
• For the frequency converter check the internal 
temperature  on  the  display  and  control  the 
proper air flow for cooling.
• Fault are logged on the converter memory and 
can  be  displayed,  this  can  help  to  revue  some 
parameter  of  the  frequency  converter  or  of  the 
system itself.

13 – Replacement

  Precaution  must  be  taken  when  disconnec-

ting, cutting or drilling holes in the tubing to en-
sure that no refrigerant under pressure is present 
in the system.

 The refrigerant shall not be discharged directly 

into the atmosphere; rather, it must be removed 
using  approved  reclamation  techniques  and 
equipment and then safely stored, in accordance 
with applicable legislation.

 The presence of refrigerant vapor can displace 

air and lead to suffocation. Proper ventilation is man-
datory at all times when servicing the equipment.

 A refrigeration system component change must 

be carried out in compliance with local regulations.

• Make sure that the main power supply has been 
switched off.
• Before replacement, it is necessary to determi-
ne the cause of failure and implement remedial 
action. If such analysis and repair are not perfor-
med,  repetitive  failure  may  occur.  Note  that  an 
oil acidity test always proves helpful in diagnosis 
when undertaking compressor replacement.
•  Don’t  forget  to  use  the  fault  memory  of  the 
frequency  converter  and  to  recover  the  fault 
descriptions  before  initializing  the  system  and 
even shutting off the power
• Check that the new Maneurop® compressor and 
the on-site compressor to be replaced display the 
same  electrical  and  refrigeration  performance 
characteristics.
• Use the rubber grommets and gaskets supplied 
with the new compressor.
•  Whenever  piping  needs  to  be  modified, 
please  refer  to  the  “Safety  measures  prior  to 
assembly”
 section.
• For further details on replacement steps, refer to 
the previous sections of this manual.
• Danfoss recommends not to throw away a used 

compressor  but  to  dispose  of  the  com-
pressor and its oil at a specialised recycling 
company site. 

Note:

 In the event of motor failure, flush and clean 

the  entire  circuit  before  replacing  the  compressor 
in  order  to  remove  acids  and  contaminants. 
Systematically install a new filter dryer on the liquid 
line. Prior to this step (if necessary), run the system 
for  at  least  2  hours  with  anti-acid  cartridges  (in 
such  instances,  the  installation  of  a  suction  filter 
might also be required). After an operating period 
of  approximately  2  weeks,  check  the  level  of  oil 
acidity. If the oil acid test proves positive, drain and 
replace the oil, replace the anti-acid liquid line filter 
dryer  cartridges  and  the  suction  filter  previously 
installed.  Repeat  oil  and  filter  dryer  replacements 
until the system is clean and acid-free. When there 
is no longer any sign of acidity, replace the anti-acid 
cartridges by the standard model and remove the 
suction strainer cartridge as required.

14 - User advisory 

Insist  that  all  service  operations  only  be 
performed by qualified personnel.

  The  compressor  and  tubing  surface 

temperatures  may  exceed  100°C  (212°F)  and 
cause  severe  bodily  burns.  Special  precaution 
must  be  taken  when  working  around  the 
compressor  and  refrigerant  tubing.  Moreover, 
a  compressor  in  operation  can  generate  very 
cold  surface  temperatures  (as  low  as  -45°C  /  -
49°F), thereby exposing personnel to the risk of 
freezing burns.

 Pressure inside the compressor can reach dange-

rously high levels (e.g. abnormal operation, fire,…) 
leading to personnel injury if suddenly released; the-
refore, never drill, weld or cut the compressor shell 
and adjacent tubing (release of liquid refrigerant can 
cause flash freezing on exposed skin).
Be  aware  that  the  product  warranty  may  be 
deemed null and void in the following cases:
•  external  modifications  to  the  compressor  (ab-
sence  of  nameplate,  drilling,  welding,  broken 
feet, shock marks),
• compressor opened by the customer or returned 
unsealed (i.e. open discharge or suction ports),
• presence of rust or water inside the compressor,
• addition of leak-detection fluid in the lubricant,

Содержание Maneurop VTZ Series

Страница 1: ...INSTRUCTIONS 8510223 P01 A Danfoss Commercial Compressors March 2006 ...

Страница 2: ...C 3 4 7 8 1 1 8 1 3 8 1 5 8 1 5 8 1 5 8 d d d d 175ZA786 10 Installation Make always sure that there is no possibility of exhaust hot air by pass from the drive This will lead to overheating thermal trip of the inverter The wiring of a variable speed system is to be done in a very professional way The main precautions on assembly has to be done in relation with the present drawings Generally speak...

Страница 3: ...moured Use the clamp from the accessory bag to connect the screen to the decoupling plate for control cables Motor cable must be screened armoured Use the accessory decoupling plate Make sure the earth wire is connected to the earth terminal on this plate and install the screened part of the motor cable as shown on the above drawings Earth wire and screen cable part must be earth connected on both...

Страница 4: ...Drive frequency converters are delivered with a factory preset open loop control for compressor speed magement To switch from open loop to process loop cable signal connections have to be done has shown below The only parameters modifications are Load motor Parameter1 00 Configurationmode Process Reference Ramps Parameter 3 01 bar Parameter 3 02 1 bar Parameter 3 03 12 bar Parameter 3 10 suction p...

Страница 5: ...t systems have been specifically reserved for these refrigerants and never used with other CFC HCFC refrigerants Use only clean and dehydrated refrigeration grade copper tubes as well as silver alloy brazing material Verify that all system components are appropriate use of refrigerant etc clean and dehydrated before being connected to the completed assembly Perform a check on the suction lines Hor...

Страница 6: ...al for wiring fig 7 8 and 9 bases are that all control wires have to be of a screee ned design the cable for electrical motor supply has to be of a shielded design too Correct ear thing of the shield cover has to be done using the method shown on fig 8 and 9 every time this one has to be earthed on each end of the cables Distinct cable tray must be used for control and motor supply The frequency c...

Страница 7: ...d qua lity this step may include an acid test humidity check spectrometer analysis etc whenever the oil becomes discolored Ensure that the circuit is leak tight Verify the proper operation of heat exchan gers and if necessary clean them Checkthecurrentdrawonthecompressormotor as well as proper voltage balance between phases Check that all electrical connections are still adequately fastened Make s...

Страница 8: ...l are property of the respective companies Speerall Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved use of a refrigerant or lubricant not approved by Danfoss Commercial Compressors anydeviationfromrecommendedinstructionsper taining to installation application or maintenance use in mobile applications boats trains trucks etc or under explosive atmospheric conditio...

Отзывы: