© Danfoss | DCS (jmn) | 2016.11

4 | 520H11543 | DKRCC.PI.CD0.F4.22

Adjustment:  

Low Pressure Switch 

Cut out on pressure fall  

with automatic reset.
Scale plate directly indicates  

the Cut In and the Differential  

set points.

1. Set Cut In by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2. Then set Differential by adjusting differential screw. Turn the 

screw clockwise to increase the Differential.

3. The Cut Out setting equals the Cut In  

less the Differential: CUT OUT = CUT IN - DIFFERENTIAL

Adjustment:  

Condenser Fan Cycling

Scale plate directly indicates  

the Cut In and the Differential  

set points.

1. Set Cut In by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2. Then set Differential by adjusting differential screw. Turn the 

screw clockwise to increase the Differential.

3.The Cut Out setting equals the Cut In less  

the Differential: CUT OUT = CUT IN - DIFFERENTIAL

Adjustment:  

Low Pressure Switch

Cut out on pressure fall  

with manual reset.
Scale plate directly indicates the Cut 

Out set point. There is no pointer for 

the Differential. 

The Differential pressure value is 

fixed and printed on the scale plate.

Adjustment:  

High Pressure Switch 

Cut Out on pressure  

rise with automatic reset.
Scale plate directly indicates  

the Cut Out and the Differential  

set points.

1. Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2. Then set Differential by adjusting differential screw. Turn the 

screw clockwise to decrease the Differential.

3. The Cut In setting equals the Cut Out  

less the Differential: CUT IN = CUT OUT - DIFFERENTIAL

Adjustment:  

High Pressure Switch

Cut Out on pressure  

rise with manual reset.
Scale plate directly indicates  

the Cut Out set point. 

There is no pointer for the 

Differential. 

The Differential pressure value is 

fixed and printed on the scale plate.

1. Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2. The Cut In setting equals the Cut Out  

less the Differential: CUT IN = CUT OUT - 60 psi

1. Set Cut Out by adjusting range screw.  

Turn the screw clockwise to lower the set point.

2. The Cut In setting equals the Cut Out plus  

the Differential: CUT IN = CUT OUT + 10 psi

NOTE: 

Cut Out set point must be above absolute vacuum!  

If the Differential is set too high then the switch  

will not stop the compressor. 

IMPORTANT:

The scale plate is only for reference and for more 

precise setting a pressure gauge should be used.

IMPORTANT:

After installing and adjusting pressure switch run the 

controlled equipment several times (at least three 

cycles) at normal operating conditions.

1

2

1

Содержание KPU Series

Страница 1: ...lose High open Low 6 in 108 10 60 250 290 KPU 2 060 5237 060 5235 Auto SPST NO close High open Low 6 in 73 6 30 250 290 KPU 2 060 5239 060 5240 Auto SPDT 6 in 73 6 30 250 290 KPU1B 060 5232 060 5234 Man Min SPDT 28 in 100 10 fixed 250 290 Fan switch KPU 5 060 5241 060 5242 Auto SPST NO close High open Low 100 465 25 85 510 530 High Pressure Switch Cut Out on pressure rise KPU 6W 060 5243 060 5245 ...

Страница 2: ...switch NOTE After installing the pressure switch evacuate the plant in accordance with applicable EPA and other regulations to remove air moisture and other contaminants Screws for bracket mounting Mounting holes for flat surfaces 120 V AC 24 FLA 144 LRA make only 240 V AC 24 FLA 144 LRA make only 240 V DC 12 W pilot duty Wiring Electrical ratings according to UL regulations European electrical ra...

Страница 3: ... its components when checking pressure switch operation or operating the controlled equipment Do not adjust pointers beyond the highest or lowest indicator marks on the scale plate as this may cause inaccurate switch operation A Manual trip Press the lever up USE FINGERS ONLY B Manual reset button available only for contols with manual reset function C Terminal block D Grounding screw A Differenti...

Страница 4: ...ressure rise with automatic reset Scale plate directly indicates the Cut Out and the Differential set points 1 Set Cut Out by adjusting range screw Turn the screw clockwise to lower the set point 2 Then set Differential by adjusting differential screw Turn the screw clockwise to decrease the Differential 3 The Cut In setting equals the Cut Out less the Differential CUT IN CUT OUT DIFFERENTIAL Adju...

Отзывы: