Recommendations for capillary tube and flare connections:

1.   Ensure self-draining of the capillary tube to minimize  

 clogging.

2.   Coil excess capillary tube into smooth, circular coils (approx. 

  3 inch diameter). The coiled tube should be securely fastened  

  in order to prevent possible damage due to vibration.

3.   Leave a little slack in the capillary tube as it helps to damp  

  mechanical vibrations.

4.   Avoid sharp bends as well as re-bending of the capillary tube  

  on the same point as it weakens the material, increasing the  

  risk of crack.

5.   Never allow for contact between the capillary tube and sharp  

  or abrasive objects as during vibrations the tube could be  

  damaged due to friction.

6.   Purge the piping before connecting pressure switches.

  

7.  Always use two wrenches 

  tightening the flare nut on 

  the pressure switch. One 

  wrench should support the 

  connector while the second 

  wrench is used to tighten the 

 nut.

8.   Do not over tighten flare nuts as it may damage the threads 

  causing leaks.

9.   Protect the capillary tube from damage caused by vibrations 

  from compressor:

    –  when the switch unit is mounted directly on the compressor, 

    the capillary must be secured to the compressor so that 

    everything vibrates as a whole.

    –  when the switch is mounted remote from the compressor, 

make the pressure connections away from the compressor.

    –  when the switch is mounted remote from the compressor 

   and the pressure connections have to be on the compressor,  

    then damping coils must be used between the compressor 

    and the pressure switch.

NOTE: 

After installing the pressure switch, evacuate the plant in 

accordance with applicable EPA and other regulations, 

to remove air, moisture, and other contaminants.

Screws for 

bracket mounting

Mounting holes 

for flat surfaces

120 V AC

24 FLA, 144 LRA – make only

240 V AC

24 FLA, 144 LRA – make only

240 V DC

12 W pilot duty

Wiring

Electrical ratings according to UL regulations

European electrical ratings according to EN 60947

AC1

AC3

AC15

LR

DC13

16 A

16 A

10 A

112 A

12 W

400 V

220 V

CAUTION:

Disconnect power supply before wiring connections 

are made or service to avoid possible electrical shock or 

damage to equipment. 

Do never touch live parts with your fingers or with 

any tool.

NOTE: 

All wiring should conform to the National Electrical Code 

and local regulations. 

Use copper wire only. 

Use terminal screws furnished in the contact block. 

Do not exceed tightening torque 20 lb. in (2.3 Nm). 

Do not exceed electrical ratings for the switch.

The terminal block as well as grounding screw  

are accessible after dismounting of the front cover.

Mount the KPU pressure switch on a bracket  

or on a completely flat surface.  

Mounting to an uneven surface might cause improper switch 

operation.

For bracket mounting use only the 10-32x3/16 screws provided 

with the switch. If other screws are used function of the 

pressure switch might be disturbed (they may not protrude 

into the switch more than 

1

/

8

 in.).

Use only the mounting holes provided; no other holes are to 

be added to the switch.

IMPORTANT:

Pressure pulsations in the refrigeration system 

reduce life time of the bellows and might disturb 

switch function. Pressure pulsations should always be 

effectively damped e.g. by connection the pressure 

switches to the refrigeration system through a capillary 

tube.

Содержание KPU Series

Страница 1: ...lose High open Low 6 in 108 10 60 250 290 KPU 2 060 5237 060 5235 Auto SPST NO close High open Low 6 in 73 6 30 250 290 KPU 2 060 5239 060 5240 Auto SPDT 6 in 73 6 30 250 290 KPU1B 060 5232 060 5234 Man Min SPDT 28 in 100 10 fixed 250 290 Fan switch KPU 5 060 5241 060 5242 Auto SPST NO close High open Low 100 465 25 85 510 530 High Pressure Switch Cut Out on pressure rise KPU 6W 060 5243 060 5245 ...

Страница 2: ...switch NOTE After installing the pressure switch evacuate the plant in accordance with applicable EPA and other regulations to remove air moisture and other contaminants Screws for bracket mounting Mounting holes for flat surfaces 120 V AC 24 FLA 144 LRA make only 240 V AC 24 FLA 144 LRA make only 240 V DC 12 W pilot duty Wiring Electrical ratings according to UL regulations European electrical ra...

Страница 3: ... its components when checking pressure switch operation or operating the controlled equipment Do not adjust pointers beyond the highest or lowest indicator marks on the scale plate as this may cause inaccurate switch operation A Manual trip Press the lever up USE FINGERS ONLY B Manual reset button available only for contols with manual reset function C Terminal block D Grounding screw A Differenti...

Страница 4: ...ressure rise with automatic reset Scale plate directly indicates the Cut Out and the Differential set points 1 Set Cut Out by adjusting range screw Turn the screw clockwise to lower the set point 2 Then set Differential by adjusting differential screw Turn the screw clockwise to decrease the Differential 3 The Cut In setting equals the Cut Out less the Differential CUT IN CUT OUT DIFFERENTIAL Adju...

Отзывы: