Installation guide

Thermostat

Type KPU

© Danfoss A/S (AC-MC / jmn), 2014-02 

DKRCC.PI.CD0.A3.22 / 520H8467 

1

06

0R

976

9

06

0R

976

9

Application

KPU thermostats are used for regulation and to ensure safety 

in refrigeration, freezing, air conditioning, ventilating and 

heating systems.

KPU thermostats are available with vapor charge or with 

adsorption charge.

All KPU thermostats are fitted with Single-Pole Double-Throw 

(SPDT) switches.

For large a.c. motors and for all d.c. motors, KPU is installed 

in the control circuit. For single phase ac motors, KPU 

is installed in the line voltage supply to the motor.

The standard KPU enclosure is rated NEMA 1. 

NEMA 1 is obtained when the thermostat is mounted on a flat 

surface. When mounting KPU on a bracket, cover all unused 

holes.

Product Specification

Thermostat bulb types

Charge

Type

Code no.

Bulb type

Capillary tube 

length

Reset 

function

Regulating 

range

Differential Δt

Max. bulb 

temperature

Ambient  

temperature

[in.]

[°F]

 [°F]

[°F]

[°F]

Vapor

KPU 61

060L5201

A

80

auto.

-20 – 60

4 – 18 

2)

250

-40 – 122

(170 for max. 

2 hours)

KPU 61

060L5203

B

80

auto.

-20 – 60

4 – 18 

2)

250

KPU 61B

060L5204

B

80

man. (min.) 

1)

-20 – 60

5 (fixed) 

2)

250

KPU 61B

060L5205

B

200

man. (min.) 

1)

-20 – 60

5 (fixed) 

2)

250

KPU 61

060L5210

B

80

auto.

-20 – 60

4 – 18 

2)

250

KPU 62

060L5206

C1

0

auto.

-20 – 60

4 – 18 

2)

250

KPU 63

060L5213

A

80

auto.

-60 – 15

10 – 25 

2)

250

KPU 63

060L5214

B

80

auto.

-60 – 15

10 – 25 

2)

250

KPU 68

060L5215

C1

0

auto.

25 – 95

5 – 22 

2)

250

KPU 69

060L5217

B

80

auto.

25 – 95

5 – 22 

2)

250

Adsorption

KPU 62

060L5207

C2

0

auto.

-20 – 60

4 – 15

175

KPU 73

060L5208

E3

80

auto.

-15 – 60

5 – 35 

175

KPU 73

060L5209

E1

80

auto.

-15 – 60

15 – 45

175

KPU 73B

060L5211

E3

80

man. (min.) 

1)

-15 – 60

6 (fixed)

175

KPU 73

060L5212

D

80

auto.

-15 – 60

5 – 35

175

KPU 71

060L5218

E2

80

auto.

25 – 70

5 – 18

175

KPU 71B

060L5216

E2

80

man. (min.) 

1)

25 – 70

5 (fixed)

175

KPU 74

060L5219

E1

80

auto.

0 – 80

9 – 35

175

KPU 74B

060L5220

E1

80

man. (min.) 

1)

0 – 80

10 (fixed)

175

KPU 75

060L5221

F

80

auto.

30 – 95

5 – 18

230

KPU 77

060L5223

E3

80

auto.

60 – 140

6 – 18

265

1)

 man. (min.): Manual reset after cut-out on falling temperature.

2)

 The switch differential is dependent on range settings. Low range settings increases the differential. 

   High range settings decreases the differential. Use the graphs on page 3 to determine the correct differential setting.

A

B

C

D

E

F

straight capillary tube

remote air coil

air coil/room sensor

double contact remote coil

remote bulb

remote duct coil

Содержание KPU 61

Страница 1: ...61B 060L5204 B 80 man min 1 20 60 5 fixed 2 250 KPU 61B 060L5205 B 200 man min 1 20 60 5 fixed 2 250 KPU 61 060L5210 B 80 auto 20 60 4 18 2 250 KPU 62 060L5206 C1 0 auto 20 60 4 18 2 250 KPU 63 060L5213 A 80 auto 60 15 10 25 2 250 KPU 63 060L5214 B 80 auto 60 15 10 25 2 250 KPU 68 060L5215 C1 0 auto 25 95 5 22 2 250 KPU 69 060L5217 B 80 auto 25 95 5 22 2 250 Adsorption KPU 62 060L5207 C2 0 auto 20...

Страница 2: ... times as these actions can weaken the material and increase the likelihood of the tube cracking 4 Form and locate the capillary tube away from sharp or abrasive objects that might damage it 5 Never allow the capillary tube of a vapor charged thermostat to run alongside of a suction line in a wall entry 6 Ensure minimal length of capillary tube exposed to temperature for KPU with straight capillar...

Страница 3: ...he lever Use fingers only B Manual reset button only on versions sold with manual reset function C Terminal block D Grounding screw Wiring Option A Cut Out on temperature fall Wiring Option B Cut Out on temperature rise C F KPU 61 KPU 62 C F LSP B C F D C KPU 63 LSP C F LSP KPU 68 KPU 69 C F C F 15 10 0 10 20 30 70 15 F Differential lines Differential lines 130 0 20 40 60 80 100 120 90 80 70 60 50...

Страница 4: ...used for service on non electrical parts Interrupt mains power before servicing electrical parts Adjustment thermostat with automatic reset Scale plate directly indicates High Switching Point and Differential Adjustment thermostat with manual reset Scale plate directly indicates Low Switching Point which is Cut Out There is no pointer for Differential Differential value is fixed and printed on the...

Отзывы: