manualshive.com logo in svg
background image

A

B

Danf

oss

060L2110

DKRCC.PI.CA0.F1.22 / 520H10107  

Installation

Select an accessible location, where 

the thermostat will not be subject 

to damage. Mount the KPU 19 on a 

bracket or on a completely flat surface. 

Mounting on an uneven surface may 

cause incorrect thermostat operation. 

Use only the mounting holes provided 

at the back of the metal housing. 

Wiring

                        Voltage [V]

        Amps [A]

P.F. 

cos Ø

A C

120

240

Resistive load

1

0.5 ~ 16 0.5 ~ 8

Inductive 

load

Full load 

Amps

0.75 0.5 ~ 16 0.5 ~ 8

Locked rotor 

Amps

0.45

96

48

 

Do not remove cover while power 

is supplied as it may cause electrical 

shock.

To avoid the possibility of electric 

shock and damage to equipment, 

disconnect the power supply before 

any wiring connections are made. 

Never touch current conducting (LIVE) 

parts with your fingers or with tools.

Electrical wires should be connected 

through the conduit rubber or 

alternatively by conduit boss. 

Caution

Note:

All wiring should conform to the 

National Electrical Code and to 

applicable local regulations. 

Use only copper wire. 

Use only the terminal screws furnished 

in the terminal block. 

Do not exceed tightening torque of 10 

lb. in. (1.18 Nm). 

Do not exceed the thermostat’s 

specified electrical ratings.

Do not use impact driver(shock driver).

The terminal block as well as 

grounding screw are accessible after 

removing the front cover.

General recommendations for 

capillary tube and bulb installation:

1. Protect the capillary tube from 

damage due to vibration.

a) When the thermostat unit is 

mounted directly on the compressor, 

the capillary tube must be secured to 

the compressor so that both vibrate 

together.

b) For mounting otherwise, form 

surplus capillary tube into a loose loop 

and secure the loop to the base on 

which the thermostat is mounted.

2. Leave a little slack in the capillary 

tube to help dampen vibration.

3. Avoid sharp bends (with the radius 

of 

1

/

2

" or less) and bending the capillary 

tube at the same point several times, 

as these actions can weaken the 

material and increase the likelihood of 

the tube cracking.

4. Bending of the capillary tube within 

1.75" from soldering point with bulb is 

not allowed.

5. Form and locate the capillary tube 

away from sharp or abrasive objects 

that might damage it.

6. For thermostats with room sensor 

coils, make sure that placement allows 

free airflow around the coil and bulb. 

At the same time, ensure that the bulb 

is not exposed to drafts from doors, or 

to heat radiated from the evaporator 

surface. Make sure that the bulb does 

not come into contact with a wall 

surface. Never mount the thermostat 

directly on a cold wall. Instead, mount 

the unit on an insulating plate.

7. KPU 19 sensing bulb is made of 

copper, copper alloy, silver solder – do 

not use it for media which are harmful 

for these materials .

The KPU 19 thermostat and the 

sensing bulb can be mounted in any 

position.

The sensing element is filled in with 

liquid expansion type charging with 

no limitations in terms of temperature 

at switch body (TS), temperature at 

sensing bulb (TB) or temperature at 

capillary tube (TC). KPU 19 can operate 

in all following conditions: 

TS > TB; TS < TB, TS = TB. 

Taking into consideration time 

constant of the thermostat it is 

recommended to install KPU 19 

where temperature is not changing 

rapidly. Fast changes of the 

measured temperature will cause 

thermostat measurements lags 

behind actual temperature changes 

in the application. Make sure to keep 

temperature variable acceleration 

within 3 minutes per 1.8 °F at liquid, or 

within 18 minutes per 1.8 °F at air.

KPU should be installed in a place 

in which harmful environmental 

conditions like radiation from sun, 

lamps or radiator is minimalized. 

Cooling due to the extensive air flow 

might affect thermostat performance 

as well. 

Pilot duty: 125VA; 120/240V AC

Do not make additional holes. 

Locking mounting holes must be 

fastened at position A as shown in 

diagram to the right. Fastening at 

position “B” may result in housing 

deformation and KPU 19 malfunction.

It is recommended to install the 

thermostat at a place where vibration 

is 1G or less.

                  Important

Do not dent or deform the bulb of the 

thermostat, as doing so could damage 

the bulb and cause charge

leakage.

Do not turn any other screws except 

screws on the scale plate, on the micro 

switch knob and on the terminal 

block.

Отзывы: