DKRCC.PI.CA0.C1.22 / 520H8304 

© Danfoss A/S (AC-MCI / jmn), 2013-11

 

Load Option A

CUT-OUT on temperature drop

Wire terminals 1 - 4:

CUT-IN = High Set Point (HSP)

see “Setting”

CUT-OUT = Low Set Point (LSP)

see “Setting”

Terms 1 - 4 close on temperature rise

Terms 1 - 4 open on temperature drop

Example: 

CUT-IN 

= 10 °C (50 °F) 

   

CUT-OUT  = 4.5 °C (40 °F)

This means 

CUT-IN 

= HSP  = 10 °C (50 °F) 

and 

CUT-OUT 

= LSP  = 4.5 °C (40 °F) 

Note:

      

= Bellows movement on pressure rise

      

= Bellows movement on pressure drop

             The free terminal can be used for 

              signal purpose. 

 

Load Option B

CUT-OUT on temperature rise

Wire terminals 1 - 2:

CUT-IN = Low Set Point (LSP)

see “Setting”

CUT-OUT = High Set Point (HSP)

see “Setting”

Terms 1 - 2 close on temperature drop

Terms 1 - 2 open on temperature rise

Example: 

CUT-IN 

=   0 °C (32 °F) 

   

CUT-OUT  = 10 °C (50 °F) 

This means 

CUT-IN 

= LSP  = 0 °C (32 °F) 

and 

CUT-OUT 

= HSP  = 10 °C (50 °F)

Manual reset

To resume control operation after safety 

cut-out, push reset knob as indicated.

Note:

Man. reset is possible only after a 

temperature rise of fixed differential (example 

5.4 °F)

 

  

 

Note:

 

use FINGERS ONLY!

(Do NOT use screwdriver)

KP w/ manual reset

Note:

Push manual reset knob during manual

tripping.

Manual tripping

 

(Electrical contacts/wiring test)

  

 

Note:

use FINGERS ONLY!

(Do NOT use screwdriver)

 

KP w/ auto reset

Main

lever

Contacts

position

Main

lever

Contacts

position

Contacts

position

Contacts

position

120V a.c.

16 FLA, 96 LRA

240V a.c.

8 FLA, 48 LRA

240V d.c.

12W pilot duty

Wiring 

CAUTION:

 Disconnect power supply before 

wiring connections are made to avoid possible 

electrical shock or damage to equipment.

All wiring should conform to the National

Electrical Code and local regulations.

     Terminal block

CAUTION: 

Use terminal screws furnished 

inthe contact block.

Use tightening torque 20 lb. in. (2.3 Nm).

Use copper wire only.

Contact load ratings