The IO_Module function block enables communication with the IX012-010 expansion module so the
module's additional inputs and outputs can be used.
Configure CAN
Set up CAN so that CAN messages can be transmitted to and from the I/O module.
Input
Type
Range
Description
CAN
Bus
——
In the GUIDE template, identify the CAN bus that contains CAN messages to and
from the I/O module. Route this bus to the CAN input on this function block.
CAN messages sent from the I/O module to the function block contain
information about the I/O modules’ inputs, outputs and configuration. CAN
messages sent to the I/O module from the function block set outputs and
configurations.
Baudrate U32
50000–1000000
The Baudrate is the speed of the CAN Port.
Port Port
——
Assigns the hardware CAN port that transmits the data.
AddrMode
U8
0–2
I/O module addressing mode.
0: Variable ID addressing mode. The I/O module Tx and Rx message identifiers
are determined by the I/O module measuring the voltage on its CAN shield
input and matching that value with a predefined range and matching identifiers
in the
I/O Module CAN Message Identifiers
table. The CAN messages use 11 bit
identifiers in this mode.
1: Predefined ID addressing mode. The I/O module Tx and Rx message identifiers
are determined by Node/N1. These identifiers are selected by matching to the
N1 value in the
I/O Module CAN Message Identifiers
table. The CAN messages use
11 bit identifiers in this mode.
2: Fixed ID addressing mode. The I/O module Tx and Rx message identifiers are
determined directly by setting Tx ID and Rx ID. The CAN messages use either 11
bit or 29 bit identifiers in this mode, as determined by Frame.
Tx ID
U32
0x00–0x1FFFFFFF
Tx ID is the CAN message identifier used by the function block for sending
messages to the I/O module when using the Fixed ID addressing mode.
When using the service tool to configure the I/O module, this value corresponds
to the Rx parameter saved on the I/O module.
Rx ID
U32
0x00–0x1FFFFFFF
Rx ID is the CAN message identifier used by the function block for receiving
messages from the I/O module when using the Fixed ID addressing mode.
When using the service tool to configure the I/O module, this value corresponds
to the Tx parameter saved on the I/O module.
Frame
U8
0–1
Sets CAN message identifier length when using the Fixed ID addressing mode.
0: 11 bit ID
1: 29 bit ID
Node/N1
U8
0–15
The KWP2000 node address used for communications between the I/O module
and the PLUS+1
®
Service Tool is Node/N1 x 8. For Variable ID addressing mode
and Predefined addressing mode this value also determines the CAN.
Net
U8
0–255
KWP2000 network used for communications between the I/O module and the
PLUS+1
®
Service Tool.
Enable
BOOL
——
Enables the function block to send CAN messages to the I/O module. An F/T
transition or T at power up starts initialization.
User Manual
PLUS+1® Compliant IX012-010 Function Block
IX012-010 Function Block
4 |
©