6 | © Danfoss | FEC | 2020.03
AN29434614196101-000401 | 088N2112 00
Installation Guide
Danfoss Icon™ Master Controller 24V
Setting up the system
Common settings for entire system (set once)
• Use the
key to choose INSTALL mode.
• Choose actuator type, press
to choose NC (normally closed is default) or NO (normally open). The type
will be marked on the actuator.
• Choose regulation type, either PWM+ or ON/OFF, by pressing the Mode key
.
Choose INSTALL mode
Use the
key to toggle to Install and confirm with
OK
. The Master Controller is now ready to include ther-
mostats.
Include thermostats and assign outputs
1. Touch the screen of the thermostat to make it search for the master controller and include the thermostat
into the system.
2. When the available outputs are flashing choose the output(s) on the master controller, which the thermostat
must control (Quick Guide D5). The available outputs will have a flashing LED.Once output is assigned to a
thermostat, it will be permanently lit. Confirm with
OK
.
Note!
Do not turn off
Master Controller while assigning RT to outputs.
3. Repeat step 1–2 for all rooms until all thermostats and outputs are paired.
Final test and starting system in normal run mode
Choose “test” mode by pressing
key. In the test menu you can choose 3 different tests using
keys:
1.
Net Test.
Performs a full network test. The thermostats must be mounted in their final position when start-
ing the test. We recommend that you always perform this test in a wireless system, to make sure that all
thermostats can still communicate with the Master Controller, when in their final position. (Quick Guide E7).
This test can run for up to 90 minutes, but you can accelerate the test by touching each thermostat (to wake
it up).
During the network test the connection to Master controllers, Repeaters and Room thermostats will be tested.
During the test the display will inform which device it currently being tested.
rt = Room thermostat
MAS = Master controllers
rEP = Repeaters
While testing the connection to the room thermostats (Rt) the actuator outputs
will be flashing until the
connection to the thermostat connected to the output(s) have been tested.
When successful the outputs LED will light up permanently. When the network test is successfully com-
pleted the display will show Net Test Done.
2.
App Test.
Performs an application specific test if the expansion module is fitted. Tests all sub-components
and allows installer to verify correct functionality visually – step by step.
3.
Flo Test.
Force opens all outputs and activates circulation pump. Run for 30 minutes, but can be stopped at
any time. Use to bleed air from system before going into normal operation.
4. When you have conducted the needed tests, choose “run” mode by pressing
key and confirm with
OK
–
the system is now fully operational.
Connecting more Danfoss Icon™ Master Controllers in a system
If wired system
Connect up to three Danfoss Icon™ Master Controller 24V to each other with a 4-wire twisted pairs cable and
the supplied connector (pic. 10: A – 4 (2 × twisted pairs), B – Max. 3 x Master Controllers in one system). See data
table in the back of installation guide for wiring recommendations.
If wireless system
Wireless connection of up to three Danfoss Icon™ Master Controllers 24V requires a Radio Module with each
Master / Slave (pic. 11).
Pairing System Master and Slave in both wired and wireless systems
Note! Slave Controllers must be assigned as System Slaves before assigning outputs and thermostats to them.
1. On the selected system master, press
to select
INSTALL
mode and press
OK
.
2. On the system slave, press and hold
for 1,5 sec. The display now toggles between
SLA TYPA
and
SLA
TYPB
.
3. Press
to choose between the two slave types and confirm with
OK
. See “Slave type definition” section
for explanation.
4. Repeat step 1–3 to assign a second Slave Controller to the system (max. two slaves are permitted).
Test procedures for multiple Danfoss Icon™ Controllers in a system
NET TEST on System Slave (after connecting slave to master)
1. Install all thermostats and actuators as described in the Quick Guide D2 to D6.
2. Perform Network test. Press
to select
TEST
and press
to choose
NET TEST
. Confirm with
OK
(Quick
Guide E7 and E8).
3. After completing the TEST press
to select
RUN
mode and press
OK
(Quick Guide E9).
APP TEST on System Master
1. Perform application test. Press
to select
TEST
and press
to choose
APP TEST
. Confirm with
OK
(Quick
Guide E7 and E8).
2. After completing the TEST press
to select
RUN
mode and press
OK
(Quick Guide E9).
Changing Slave type
1. On Danfoss Icon™ Slave Controller press and hold
for 1,5 sec. The display now toggles between
SLA
TYPA
and
SLA TYPB
.
2. Press
to choose between the two slave types and confirm with
OK
. See “Slave type definition” for more
information.
LINK test on Slave (between Master and Slave)
Press
for 1,5 sec. The display shows inclusion pattern while making the LINK test. When done, the display
shows the strength of the connection in percentage.
Note! If an Expansion Module is added to the system, it must be installed on the Master Controller.
Slave type definition
The potential free relay is activated on all Master Controllers when heat is demanded on either Master Controller.
SLA TYPA:
Pump is activated on Danfoss Icon™ Master Controller 24V when heat is demanded on either Master
or Slave(s).
SLA TYPB:
Pump relay is only activated on the Danfoss Icon™ Master Controller 24V to which the thermostat
with heat demand is assigned.
Содержание Icon Series
Страница 1: ...Installation Guide Danfoss Icon Master Controller 24V...
Страница 2: ......
Страница 76: ...76 Danfoss FEC 2020 03 AN29434614196101 000401 088N2112 00 76 76 76 77 77 78 78 78 78 79 79 79 79 80 80 80 81...
Страница 77: ...Danfoss FEC 2020 03 AN29434614196101 000401 088N2112 00 77 CN 7 8 9 10 11 12 13 14...
Страница 78: ...78 Danfoss FEC 2020 03 AN29434614196101 000401 088N2112 00...
Страница 79: ...Danfoss FEC 2020 03 AN29434614196101 000401 088N2112 00 79 CN...
Страница 81: ...Danfoss FEC 2020 03 AN29434614196101 000401 088N2112 00 81 CN...
Страница 100: ......
Страница 101: ......
Страница 102: ...102 Danfoss FEC 2020 03 AN29434614196101 000401 088N2112 00...