ICM/ICAD Motorized Valve
Installation, Programming, and Troubleshooting
Danfoss (USCO / MKS), 11 - 006
DKRCI.EI.HT0.A1. / 50H1639
7
CUSTOMER SUPPLIED
Brown
Green
Pink
Yellow
Relay
White
Optional UPS/battery
back up
+
24 V d.c
Power
Supply
+
-
Wiring diagram showing ICAD wired with
a digital input for ON/OFF solenoid valve
operation
Note:
The ICAD motor can be programmed to
open or close when the relay is closed.
See parameter ¡09 in programming
section.
Wiring diagram showing ICAD digital
outputs wired with customer supplied
auxiliary relays
Note:
The same 24 Vd.c. power supply that
powers the ICAD can be used with the
ICAD digital outputs to power auxiliary
relays (or other small load devices), but
please note that the system will no
longer be galvanically isolated.
CUSTOMER SUPPLIED
5-24 V d.c
K
1
K
2
K
3
K
2
K
1
K
3
K
2
K
1
K
3
K1 : Common Alarm
K2 : ICM fully open
K3 : ICM fully closed
Auxillary relays
White
Brown
Green
Yellow
Brown
Green
Terminal Box
24 V d.c
Power
Supply
+
-
Power
Supply
+
-
White
Optional UPS/
battery back up
+
Terminal box is customer supplied.
Terminal box is customer supplied.