ICM/ICAD Motorized Valve 

 

 

Installation, Programming, and Troubleshooting

10 

DKRCI.EI.HT0.A1. / 50H1639 

 

 Danfoss (USCO / MKS), 11- 006

Troubleshooting

The Manual Tool

The manual tool should always be ordered with any ICM/ICAD assembly.  This tool gives the 
user the ability to remove the ICAD actuator and manually rotate the valve in the open or 
close direction depending on need and application. When using the manual tool, a clock-
wise rotation will open the valve and a counter-clockwise rotation will close the valve.

NOTE:
It is very important to remember that when rotating the valve manually you are changing 
the position from that in the actuator’s memory.  If power is removed from the actuator prior 
to using the manual tool, no problem will occur because, once the ICAD is powered up again, 
it will automatically recalibrate to the fully closed position before returning to the position in 
memory to which the control signal last set the valve.  This recalibration will not occur if 
power is not removed from the ICAD prior to using the manual tool, and erroneous operation 
will likely occur. Always remove power before using the manual tool, and restore power 
afterward to ensure recalibration and trouble-free operation. 

The user will be able to troubleshoot and determine many of the conditions and set points 
within the ICAD by accessing the Service Menu.  A list of those service parameters follows 
below:

It is also possible to restore the original factory settings to the ICAD by the following 
procedure:

To restore factory settings:

1.   Remove the power supply.

.   Activate down arrow and up arrow push buttons at the same time.

3.   While holding the up and down arrow reconnect the power supply.

4.   Release down arrow and up arrow push buttons.

5.   When the display on ICAD is alternating between showing: 

CA

 and 

A1

 the factory    

  resetting is complete.

Service Menu

Description

Display 

name Min. Max. Unit Comments

OD %

¡50

0

100

%

ICM valve Opening Degree

AI [mA]

¡51

0

0

mA Analog Input signal

AI [V]

¡52

0

10

V

Analog Input signal

AO [mA]

¡53

0

0

mA Analog Output signal

DI

¡54

0

1

-

Digital Input signal

DO Close

¡55

0

1

-

Digital Output Closed status. ON when OD < 3 %

DO Open

¡56

0

1

-

Digital Output Open status. ON when OD > 97 %

DO Alarm

¡57

0

1

-

Digital Output alarm status. ON when an alarm is detected

MAS mP SW 

ver. 

¡58

0

100

-

Software version for MASTER Microprocessor

SLA mP SW ver. 

¡59

0

100

-

Software version for SLAVE Microprocessor

Service Parameters

Содержание ICM

Страница 1: ...REFRIGERATION AIR CONDITIONING ICM ICAD Motorized Valve Installation Programming and Trouble shooting Quick Start Guide...

Страница 2: ...and Troubleshooting DKRCI EI HT0 A1 22 520H1639 Danfoss USCO MKS 11 2006 Contents Page Installation 3 Wiring the ICAD 5 ICAD Overview 8 ICAD Programming 9 Troubleshooting The Manual Tool 10 Service pa...

Страница 3: ...d must be separately removed from the valve body with a 12 mm hex key prior to welding see diagrams below Removing ICM 25 to 65 bonnets 1 Remove the 4 bolts 2 Rotate the bonnet as shown 3 Pry the bonn...

Страница 4: ...4 ICM 65 110 81 7 Install the ICAD motor actuator on the ICM valve a The ICM valve must not be in its fully opened position while the ICAD motor is calibrated with the valve at a later step Therefore...

Страница 5: ...on White common alarm digital NPN transistor output when combined with yellow wire Brown indicates ICM is fully open digital NPN transistor output when combined with yellow wire Green indicates ICM is...

Страница 6: ...White Optional UPS battery back up Wiring diagram showing ICAD wired with a PLC or other type of third party electronics Note The ICAD supplies the power for the 4 20 mA feedback signal Wiring diagra...

Страница 7: ...Wiring diagram showing ICAD digital outputs wired with customer supplied auxiliary relays Note The same 24 Vd c power supply that powers the ICAD can be used with the ICAD digital outputs to power au...

Страница 8: ...valve position output signal to modulate another ICAD or to a PC or PLC for monitoring see parameter 06 p 6 4 Because the ICAD is employs a digital stepper motor its speed can be adjusted to any perc...

Страница 9: ...safe is installed 1 Close valve 2 Open valve 3 Maintain valve position 4 Go to OD given by 12 Digital Input function 09 1 2 1 Define function when DI is ON short circuited DI terminals when 02 2 1 Ope...

Страница 10: ...before using the manual tool and restore power afterward to ensure recalibration and trouble free operation The user will be able to troubleshoot and determine many of the conditions and set points wi...

Страница 11: ...not appear to be opening or closing properly The ICAD was not mounted properly on the valve stem Solution Check to make sure that the ICAD was mounted evenly on the ICM valve The ICAD is not receiving...

Страница 12: ...inuous power supply It is used to change the valve position usually to close the valve in the event of a power failure Therefore the system is not to be run in the UPS mode Add a solenoid valve in fro...