background image

4

VMIFB202

Hot gas temperature too high 

See in service under heat pump also check using own digital thermometer.

Action:

Check the refrigerant circuit see section below

The discharge pipe sensor displays correctly but still has high overheating

Action:

Using manometer apparatus and a digital thermometer check what the cooling and overheating reading of the unit is. 

Also check that bulb and capillary tube are undamaged and that the bulb is correctly positioned. (Bulb is positioned at two o’clock in 

the suction pipe). 

  

If the cooling is correct according to the instructions try adjusting the overheating using the expansion valve, if the overheating cannot 

be adjusted using the expansion valve or if the capillary tube or bulb are damaged replace it.

Lack of refrigerant, not enough refrigerant in the hp cooling circuit.

Action:

 Using manometer apparatus and a digital thermometer, check that the unit’s cooling and overheating is correct for the specific 

refrigerant.

If cooling is not at the correct level compared with the specific refrigerant and is too low, there is insufficient refrigerant in the unit. 

If there appears to be a leak in the refrigerant circuit, carry out leak tracing and any necessary corrective action. If leak tracer is not 

available, brush soap water on the suspected leak and look for bubbles.                                                                                   

Also check if oil has leaked. In event of leakage oil usually comes from the refrigerant circuit.    

Troubleshooting Guide 

Working pressostat and high pressure pipe

Discharge

pipe sensor

location

temperatur

ohm

-30

1884

-25

1443

-20

1115

-15

868

-10

681

-5

538

0

428

5

343

10

276

15

224

20

183

25

150

30

124

35

103

40

86

temperatur

kohm

0

66.3

5

52.4

10

41.8

15

33.5

20

27.1

25

22

30

18

35

14.8

40

12.2

45

10.1

50

8.5

55

7.1

60

6

65

5

70

4.2

75

3.7

80

3.1

85

2.7

150 ohm sensor

Outdoor / Defrost sensor

22 kohm sensor

Supply line, return line, hot water,

brine in, brine out, discharge pipe sensor

Содержание Heat Pump

Страница 1: ...h pressure 05 Alarm low pressure 08 Alarm motor protection 10 Alarm Circulation pump 12 Alarm Brinepump 13 Alarm Brine 14 Alarm Sensor 15 Alarm communication 16 Alarm Aux heater 17 Sound 18 Temperatur...

Страница 2: ...e compressor runs check the discharge pipe temperature by feeling it with your hand The discharge pipe must be hot not lukewarm even slightly away from the compressor if the phases are in the correct...

Страница 3: ...switch or discharge pipe sensor has broken the circuit In normal operation this is displayed after completed hot water production but can also be shown at high supply temperature in the heating system...

Страница 4: ...atus and a digital thermometer check that the unit s cooling and overheating is correct for the specific refrigerant If cooling is not at the correct level compared with the specific refrigerant and i...

Страница 5: ...re at the fuse and the relay card See wiring diagram If there is current there check the wiring between relay card and circulation pump If there is current the circulation pump has jammed If this is t...

Страница 6: ...g If it jams clean replace the insert or replace with a newer LK exchange valve Note When changing to LK one must replace both motor and valve because this is the twisting type Cable break or loose ca...

Страница 7: ...the heating system Ensure that there is a sufficiently large water volume for the heat pump to work against i e for the heat pump to give off its heat to approx 14 15 litres kw heat pump at smaller vo...

Страница 8: ...connect the cables from the low pressure switch and relay card to do this The low pressure switch opens too soon Action Check that the low pressure switch opens at the right pressure done with a manom...

Страница 9: ...oning documentation If the active collector is too short the heat pump cannot receive enough energy from the heat source which results in the heat pump requiring an addition to cover the energy requir...

Страница 10: ...on the soft starter the soft starter releases all three phases down to the compressor If the soft starter has signal but is unevenly loaded by amperes on the phases or if it breaks to MS alarm Try co...

Страница 11: ...tection Action Check the supply to the motor protection soft starter compressor Measure so that one can see where the supply disappears try pulling at the cables to see if there is any play If a cable...

Страница 12: ...e 0 10V signal between terminals 329 and 330 Go into the service menu and run the circulation pump in manual mode 30 3V 40 4V 50 5V etc If the correct control signal is obtained there is a relay card...

Страница 13: ...rculation pump s 0 10V signal Measure the 0 10V signal between terminal 333 and 334 Go into the service menu and run the circulation pump in manual mode 30 3V 40 4V 50 5V etc If the correct control si...

Страница 14: ...when the temperature on BRINE OUT is as low or lower than the set value on ALARM BRINE In the factory setting this function is inactive If the problem is caused by a faulty setting in the ALARM BRINE...

Страница 15: ...pump and outdoor sensor is not damaged in anyway by nails pins or another cable securing device This is a commonly occurring fault If the sensor does not give a correct value the sensor is defective T...

Страница 16: ...he relay card drops the heat pump will stop while older heat pumps produced before Autumn 2008 will run as usual with the most recent setting Alarm com Air DHP A Action Check if the cable between the...

Страница 17: ...has jammed If it has jammed open the bleed screw and try to release the paddle wheel using a screwdriver for example does not apply to optimum pumps Check that all the shut off valves are open if not...

Страница 18: ...rrectly connected but still correct Check if the discharge pipe temperature rises quickly if it does not switch L1 and L3 When the compressor is running check the discharge pipe temperature by feeling...

Страница 19: ...compressor noise the compressor itself may be defective and needs to be replaced Noise from the soft starter Action Measurement check the input and output phases for the soft starter as well as the c...

Страница 20: ...prevent transmitting vibration it is recommended that flexible hoses are used for all pipe connections To avoid noise caused by pipe mountings a rubber coated pipe clamp should be used to prevent the...

Страница 21: ...e for example Vibration noise from the electrical installation Action Check for electrical steps or similar devices screwed to the heat pump and wall These can cause vibrations and noise The heat pump...

Страница 22: ...ning times set the value down to factory setting If the system has a high 8 C brine temperature you may have to reduce the start value further for a longer running time Sensor error hot water sensor A...

Страница 23: ...ssure switch that screws directly onto the schrader socket service outlet to avoid having to open the refrigerant circuit Insufficient exchange surface to transfer the heat pump s output to the heater...

Страница 24: ...emperature is maintained regardless of the outdoor temperature MIN Lowest set point value on the supply line regardless of the outdoor temperature except with heat stop Sensor fault Outdoor room suppl...

Страница 25: ...otor but the arm does not shift mode Replace either the 3 way insert or the whole 3 way NOTE If the white lever on the motor goes up and down all the time there is a short circuit in the motor replace...

Страница 26: ...to the relay card Use multimeters with buzzer to fault trace the cable between the control card and the shunt If there is voltage to the motor and the motor shifts mode as it should replace the 3 way...

Страница 27: ...art The groove of the white six edged sleeve must be towards 3 o clock in unaffected mode Adjust the motor as illustrated Then screw the motor into place and press the knob to Auto mode Manual mode wh...

Страница 28: ...tructions for the relevant model Peak heat operation occurs in connection with hot water production with the set interval Room Action Reduce the Room set point value 1 degree increase in room set poin...

Страница 29: ...e sensor is defective replace it The compressor runs backwards Action Check that the phases for the heat pump are correctly connected only applies to 3 phase heat pumps If the compressor runs backward...

Страница 30: ...e outdoor section via walls in the house Defrosting problems Action For a defrosting to occur the control computer calculates the difference between the defrost sensor and brine in On older models the...

Страница 31: ...the motor switches position when testing but defrosting still does not function remove the motor and try closing and opening the valve by hand by pressing in the spring loaded spindle If it should be...

Страница 32: ...ALUE FOR SUPPLY 0 20 C 22 C 40 C 1 20 C 22 C 38 C 2 20 C 22 C 36 C 3 20 C 22 C 34 C 4 20 C 22 C 32 C Installation The cover for the screw is removed and rear front is installed The terminal block is r...

Страница 33: ...t but no hot water comes out of it Action Check if the mixing valve is defective remedy or replace Check if there is cold water supply if not check why and rectify the fault The safety valve leaks Act...

Страница 34: ...order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies...

Отзывы: