background image

© Danfoss A/S (MWA), 2016.05 

DKRCI.PI.S00.A6.52 / 520H2528 7

ENGLISH

Installation

General procedure for all GD types (fig. 

2, 3, 4)

All GD products are for wall mounting.
Removal of GD top cover:-

•   For Standard and LCD display types:

    •   Unscrew two front screws 

•  For the models

  IP 65 with stainless steel sensor head /

  Exd / IP 65 low temperature

  (fig. 3, 4):

    •   Unscrew four front screws

Electrical installation (fig. 5 and 6)

The Earth/Ground connection must be 

made when using the standard, LCD 

display, or Exd enclosuretypes.  The safety 

of the equipment is dependent on the 

integrity of the power supply and the 

earthing of the enclosure.
Apply voltage at CON 1 and the green LED 

will light up (fig. 6).

Stabilisation Period

Once the GD is initally powered up it takes 

some time to stabilise and will give a 

higher analog output (4-20 mA/0-10 V/0-5 

1

) ) at the start before reverting to the 

actual concentration reading (in clean air 

and no leaks, on the analog output reverts 

back to: 

(~ 0 V/4 mA / ( ~ 0 ppm)) 

2

).

The stabilisation times specified below are 

only intended as a guide and may vary due 

to temperature, humidity, cleanliness of 

the air, storage time 

3

) e.t.c

Model

GDA with EC sensor ...........................20-30 Sec

GDA with SC sensor ............................... 15 min.

GDA with CT sensor ............................... 15 min.

GDA with CT sensor, Exd model ...........7 min.

GDHC/GDHF/GDHF-R3 

with SC sensor ............................................1 min.

GDC with IR sensor ..................................10 sec.

GDC with IR sensor, 

Exd model ...................................................20 sec.

GDH with SC senso  ..................................3 min.

When changing any jumper position, the 

power must be disconnected (CON1) to 

enable the new jumper setting.
Setting of normally open (NO) / normally 

closed (NC) for the digital output Low/

High Level alarm.

Both have an option to set at NO or NC. 

Factory setting is NO.

 

 

NO/NC can not be used as fail  

 

safe during power failure.

Digital output Low Level alarm

NO : JP3 ON, JP4 OFF (removed)

NC : JP4 ON, JP3 OFF (removed)

(fig. 6)

Digital output High Level alarm

NO : JP5 ON in upper position

NC : JP5 ON in lower position

(fig. 6)

Manual reset / auto reset of Low/High 

Level alarm (fig. 6)

This option available through JP8 (Low 

Level alarm) and JP7 (High Level alarm).

The pre-set factory setting is Auto Reset.

If manual reset is selected for either Low/

High Level alarm condition then manual 

reset push button is located next to CON 7.

Digital output Low Level alarm

Auto Reset : JP8 in left hand position

Manual: JP8 in right hand position 

Digital output High Level alarm

Auto Reset : JP7 in left hand position

Manual: JP7 in right hand position 

Adjusting delayed response time (fig. 6)

The digital output for Low/High Level 

alarms can be delayed.

The pre-set factory setting is 0 Minutes

Digital output Low Level alarm

JP1 in position

1 : 0 minutes

2 : 1 minutes

3 : 5 minutes

4 : 10 minutes

Digital output High Level alarm

JP2 in position

1 : 0 minutes

2 : 1 minutes

3 : 5 minutes

4 : 10 minutes

Adjusting Low/High alarm values (fig. 7)

All GD have been preset by the factory to 

realistic values related to the actual ppm 

range of the GD product. The actual Low 

and High alarm ppm limits are detailed on 

the external GD label. The factory preset 

value can be adjusted, with a voltmeter 

measuring the 0-5 V d.c output.

0 V corresponds to the min. ppm range 

(e.g. 0 ppm)

5 V corresponds to the max. ppm range 

(e.g. 1000)

E.g. if a setting of 350 ppm is required then 

the voltage shall be set to 1.75 V (35 % of 

5 V)

Adjusting the Low alarm limit value

Between TP0(-) and TP2(+) a voltage 

between 0-5 V can be measured and with 

that the ppm Low alarm limit setting.

The voltage/ppm setting can be adjusted 

at RV1.

Adjusting the High alarm limit value

Between TP0(-) and TP3(+) a voltage 

between 0-5 V can be measured and with 

that the ppm High alarm limit setting.

The voltage/ppm setting can be adjusted 

at RV2.

Connecting GD to a Danfoss monitoring 

system (fig. 8 and 9)

Wiring (fig. 8)

All GD must be connected A-A, B-B,

COM – COM (screen)

When connecting to the Danfoss 

monitoring system panel the same 

terminals are connected to each other i.e. 

A-A, B-B, Com – Com.

On the last GD and Danfoss monitoring 

system, fit a 120 ohm resistor across 

terminal A and B to terminate the 

communications system.

A maximum of  31 GDs can be connected.

If more than 31 units are needed, please 

contact Danfoss for further information.

GD address (fig. 9)

The sensor address is set by S2 and S3, 

adjusting these dials between 0 and F will 

give the sensor its own address as shown in 

fig. 9.  A conversion chart between Danfoss 

monitoring system channel numbers and 

the hexadecimal address of the GD is 

attached.  Power must be removed when 

setting addresses on the GD.

Annual Test

To comply with the requirements 

of EN378 and the F GAS regulation 

sensors must be tested annually. 

However local regulations may 

specify the nature and frequency 

of this test. If not the Danfoss 

recommended bump test 

procedure should be followed. 

Contact Danfoss for details

After exposure to a substantial gas 

leak, sensor should be checked and

replaced if necessary.

Check local regulations on 

calibration or testing requirements.

1

)

Always use the voltage 0-10 V to check the 

output for stabilisation check.

2

)

GDC IR goes back to about 400 ppm as this is the 

normal level in air. (~4.6 mA/~0.4 V/ 0.2 V)

3

)

If the GD have been in long-term storage or have 

been swiched off for a long period, stabilisation 

will be much slower. However within 1-2 hours 

all the GD types should have dropped below the 

low alarm level and be operational. 

The progress can be monitored exactly on the 

0-10V output. When the output settles around 

zero (400 ppm in the case of IR CO

2

 sensors) the 

GD is stabilised. In exceptional circumstances 

particularly with CT sensors the process can take 

up to 30 hours.

Содержание GDA

Страница 1: ...dieses Ger ts Wird das Ger t nicht gem diesen Anweisungen und den in der Branche geltenden Normen installiert und bedient k nnen schwere Verletzungen und Tod die Folge sein Der Hersteller bernimmt die...

Страница 2: ...65 mit Edelstahl F hlerkopf IP 65 avec t te de capteur en acier inoxydable Exd Exd lav temperatur Exd low temperature Exd niedrigtemperatur Exd basse temp rature 1 2 2 3 4 Sk rm Stelforb Screen GRD Sc...

Страница 3: ...t responstid alarm for lavt niveau JP1 Delay response time for Low Level alarm JP1 Ansprechverz gerung f r Niedrigpegelalarm JP1 Temporisation pour l alarme de niveau bas 6 JP2 Forsinket responstid al...

Страница 4: ...when communicating with Danfoss Monitoring System Einstellen der Adresse zur Kommunikation mit Danfoss Monitoring System R glage d adresse pour communication avec Danfoss Monitoring System Justering...

Страница 5: ...oring system Kanal von Danfoss monitoring system Canal zur Danfoss monitoring system S3 S2 Kanal p Danfoss monitoring system Channel on Danfoss monitoring system Kanal von Danfoss monitoring system Ca...

Страница 6: ...ustering af lave h je alarmv rdier fig 7 Alle GD er fra fabrikken indstillet til realistiske v rdier der relaterer sig til GD detektorens faktiske ppm omr de Ppm gr nserne for den faktiske h je lave a...

Страница 7: ...n position 1 0 minutes 2 1 minutes 3 5 minutes 4 10 minutes Adjusting Low High alarm values fig 7 All GD have been preset by the factory to realistic values related to the actual ppm range of the GD p...

Страница 8: ...r den aktuellen ppm Bereich und f r das GD realistische Niedrig Hoch Werte eingestellt Die aktuellen Niedrig und Hochalarm ppm Werte sind am externen GD Typenschild angegeben Die Werkseinstellungen k...

Страница 9: ...eurs d alarme basse haute figure 7 Tous les d tecteurs GD sont pr r gl s en usine sur des valeurs r alistes et conformes la plage ppm r elle du produit GD Le d tail des valeurs ppm limites des alarmes...

Страница 10: ...10 DKRCI PI S00 A6 52 520H2528 Danfoss A S MWA 2016 05...

Страница 11: ...Danfoss A S MWA 2016 05 DKRCI PI S00 A6 52 520H2528 11...

Страница 12: ...12 DKRCI PI S00 A6 52 520H2528 Danfoss A S MWA 2016 05...

Отзывы: