FCM 300 / FCD 300 / VLT
®
2800 / DP V1 PROFIBUS
Profibus
DP
■
Status word
When the frequency converter returns the frame to the
master, the same two bytes operate as status from the
frequency converter with the following functions:
Status word
According to PROFIDRIVE control word (par. 512 = 0)
Bit
Bit = 0
Bit = 1
00 (LSB)
Control not ready
Ready
01
VLT not ready
Ready
02
Motor coasting
Enable
03
No fault
Trip
04
ON 2
OFF 2
05
ON 3
OFF 3
06
Stop enable
Start disable
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local operation
Bus control
10
Out of range
Frequency OK
11
Not running
Running
12
13
Voltage OK
Limit
14
Torque OK
Limit
15 (MSB)
No thermal warning
Thermal warning
Status word
According to FC Control Word (par. 512 = 1)
Bit
Bit = 0
Bit = 1
00 (LSB)
Control not ready
Ready
01
VLT not ready
Ready
02
Coasting
Enable
03
No fault
Trip
04
R e s e r v e d
05
R e s e r v e d
06
No trip lock
Trip lock
07
No warning
Warning
08
Speed
≠
ref.
Speed = ref.
09
Local operation
Bus control
10
Out of range
Frequency OK
11
Not running
Running
12
13
Voltage OK
Above limit
14
Current OK
Above limit
15 (MSB)
No thermal warning
Thermal warning
The FCM 300 Design Guide (MG.03.BX.02), the
FCD 300 Design Guide (MG.04.AX.02) and the VLT
2800 Series Design Guide (MG.28.EX.02) hold a
detailed description of the control word.
MG.90.A5.02 - VLT is a registered Danfoss trademark
27