FCM 300 / FCD 300 / VLT
®
2800 / DP V1 PROFIBUS
■
Synchronize and freeze
The control commands SYNC/UNSYNC and
FREEZE/UNFREEZE are broadcast functions.
SYNC/UNSYNC is used to send syncronized
control commands and/or speed reference to all
the connected slaves (FCM 300/FCD 300/VLT 2800
Series). FREEZE/UNFREEZE is used to freeze the
status feedback in the slaves to get syncronized
feedback from all connected slaves.
The synchronize and freeze commands only affect
Process Data (the PCD part of the PPO).
SYNC/UNSYNC
SYNC/UNSYNC can be used to obtain simultaneous
reactions in several slaves, for example synchronised
start, stop or speed change. A SYNC command
will freeze the actual control word and speed
reference, incoming Process Data will be stored
but not used until a new SYNC command or a
UNSYNC command is received.
See the example below where the left column
holds the speed reference send out by the master
and the three right columns hold the actual speed
reference used in each of the three slaves.
Actual slave speed reference
VLT
VLT
VLT
From DP master to address:
Address 3
Address 4
Address 5
1. Speed reference = 50% to address 3
50%
0%
0%
2. Speed reference = 50% to address 4
50%
50%
0%
3. Speed reference = 50% to address 5
50%
50%
50%
4. SYNC command to all addresses
50%
50%
50%
5. Speed reference = 75% to address 3
50%
50%
50%
6. Speed reference = 75% to address 4
50%
50%
50%
7. Speed reference = 75% to address 5
50%
50%
50%
8. SYNC command to all addresses
75%
75%
75%
9. Speed reference = 100% to address 3
75%
75%
75%
10. Speed reference = 50% to address 4
75%
75%
75%
11. Speed reference = 25% to address 5
75%
75%
75%
12. UNSYNC command to all addresses
100%
50%
25%
13. Speed reference = 0% to address 3
0%
50%
25%
14. Speed reference = 0% to address 4
0%
0%
25%
15. Speed reference = 0% to address 5
0%
0%
0%
FREEZE/UNFREEZE
FREEZE/UNFREEZE can be used to get simultaneous
reading of Process Data for example output current
from several slaves. A FREEZE command will freeze
the current actual values and on request the slave
will send back the value that was present when
the FREEZE command was received. The actual
values will be updated when a new FREEZE or
UNFREEZE command is received.
See the example below where the left column
holds the current values read by the master and
the three right columns hold the actual output
current of the three slaves.
Actual slave output current
VLT
VLT
VLT
DP master reads address:
Address 3
Address 4
Address 5
1. Address 3 output current = 2 A
⇐
2 A
3 A
4 A
2. Address 4 output current = 5 A
2 A
⇐
5 A
2 A
3. Address 5 output current = 3 A
3 A
2 A
⇐
3 A
4. FREEZE command to all addresses
1 A
3 A
3 A
5. Address 3 output current = 1 A
⇐
4 A
2 A
5 A
6. Address 4 output current = 3 A
2 A
⇐
2 A
2 A
7. Address 5 output current = 3 A
3 A
1 A
⇐
2 A
8. UNFREEZE command to all addresses
2 A
3 A
4 A
Reading as by 1, 2 and 3
MG.90.A5.02 - VLT is a registered Danfoss trademark
24