The Application Guide can be cancelled at any time by
pressing [Back]. The Application Guide can be re-entered
through the Quick Menu:
130BC957.10
Illustration 4.25
When re-entering the Application Guide, select between
previous changes to the factory set-up or restore default
values.
NOTE
If the system requirement is to have the internal pack
controller for 3 compressors plus by-pass valve connected,
there is the need to specify FC 103 with the extra relay
card (MCB 105) mounted inside the frequency converter.
The bypass valve must be programmed to operate from
one of the extra relay outputs on the MCB 105 board.
This is needed because the standard relay outputs in the
FC 103 are used to control the compressors in the pack.
4.3.2 Required Initial Frequency Converter
Programming
NOTE
If the wizard is run, ignore the following.
Frequency converters require basic operational
programming before running for best performance. Basic
operational programming requires entering motor-
nameplate data for the motor being operated and the
minimum and maximum motor speeds. Enter data in
accordance with the following procedure. Parameter
settings recommended are intended for start up and
checkout purposes. Application settings may vary. See for
detailed instructions on entering data through the LCP.
Enter data with power ON, but before operating the
frequency converter.
1.
Press [Main Menu] twice on the LCP.
2.
Use the navigation keys to scroll to parameter
group 0-**
Operation/Display
and press [OK].
130BP066.10
1107 RPM
0 - ** Operation/Display
1 - ** Load/Motor
2 - ** Brakes
3 - ** Reference / Ramps
3.84 A
1 (1)
Main menu
Illustration 4.26
3.
Use navigation keys to scroll to parameter group
0-0*
Basic Settings
and press [OK].
0-
**
Operation / Display
0.0%
0-0
*
Basic Settings
0-1
*
Set-up Opperations
0-2
*
LCP Display
0-3
*
LCP Custom Readout
0.00A
1(1)
130BP087.10
Illustration 4.27
4.
Use navigation keys to scroll to
0-03 Regional
Settings
and press [OK].
0-0
*
Basic Settings
0.0%
0-03 Regional Settings
[0] International
0.00A
1(1)
130BP088.10
Illustration 4.28
5.
Use navigation keys to select
[0] International
or
[1] North America
as appropriate and press [OK].
(This changes the default settings for a number
of basic parameters. See
American Default Parameter Settings
for a
complete list.)
6.
Press [Quick Menu] on the LCP.
7.
Use the navigation keys to scroll to parameter
group
Q2 Quick Setup
and press [OK].
Start Up and Functional Tes...
VLT® Refrigeration Drive 110-250 kW Operating Instructions
MG16F102 - VLT® is a registered Danfoss trademark
27