potential throughout the network. Particularly in instal-
lations with long cables.
To prevent impedance mismatch, always use the same
type of cable throughout the entire network. When
connecting a motor to the frequency converter, always use
screened motor cable.
Cable
Screened twisted pair (STP)
Impedance
120
Ω
Max. cable length
1200 m (including drop lines)
500 m station-to-station
Table 3.9
Installation
VLT® Refrigeration Drive 110-250 kW Operating Instructions