No. Description
Warning Alarm/Trip
Alarm/Trip Lock
Parameter
Reference
61
Tracking Error
(X)
(X)
4-30
62
Output Frequency at Maximum Limit
X
63
Mechanical Brake Low
(X)
2-20
64
Voltage Limit
X
65
Control Board Overtemperature
X
X
X
66
Heatsink Temperature Low
X
67
Option Configuration Has Changed
X
68
Safe Stop
(X)
(X)
1)
5-19
70
Illegal FC configuration
X
71
PTC 1 Safe Stop
X
X
1)
5-19
72
Dangerous Failure
X
1)
5-19
80
Drive Initialized to Default Value
X
90
Encoder Loss
(X)
(X)
17-61
91
Analog input 54 wrong settings
X
S202
100-
199 See Instruction Manual for MCO 305
250 New spare part
X
14-23
251 New Type Code
X
X
6.2: Alarm/Warning code list
(X) Dependent on parameter
1) Cannot be auto-reset via Par 14-20
A trip is the action taken when an alarm has
occurred. The trip will coast the motor and can
be reset by pressing the reset button or make
a reset by a digital input (Par. 5-1* [1]). The
event that causes an alarm cannot damage
the drive or result in dangerous conditions. A
trip lock is the action taken when an alarm oc-
curs that may cause damage to the drive or
its connected parts. A trip lock situation can
only be reset by a power cycling.
LED indication
Warning
yellow
Alarm
flashing red
Trip-locked
yellow and red
VLT
®
AutomationDrive FC 300 Instruction
Manual
6. Troubleshooting
MG.33.A9.22 - VLT is a registered Danfoss trademark
89
6