Control card, 10 V DC output:
Terminal number
50
Output voltage
10.5 V ±0.5 V
Max. load
15 mA
The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage
terminals.
Control card, RS-485 serial communication:
Terminal number
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Terminal number 61
Common for terminals 68 and 69
The RS-485 serial communication circuit is functionally separated from other central circuits and
galvanically isolated from the supply voltage (PELV).
Control card, USB serial communication:
USB standard
1.1 (Full speed)
USB plug
USB type B “device” plug
Connection to PC is carried out via a standard host/device USB cable.
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-volt-
age terminals.
The USB ground connection is not galvanically isolated from protection ground. Use only an
isolated laptop as PC connection to the USB connector on the adjustable frequency drive.
Relay outputs:
Programmable relay outputs
FC 301
≤
10 hp [7.5 kW]: 1 / FC 302 all hp [kW]: 2
Relay 01 Terminal number
1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
240 V AC, 2 A
Max. terminal load (AC-15)
1)
(Inductive load @ cos
φ
0.4)
240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
60 V DC, 1A
Max. terminal load (DC-13)
1)
(Inductive load)
24 V DC, 0.1A
Relay 02 (FC 302 only) Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
400 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cos
φ
0.4)
240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load)
80 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load)
24 V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load)
240 V AC, 2 A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cos
φ
0.4)
240 V AC, 0.2 A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load)
50 V DC, 2 A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load)
24 V DC, 0.1 A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
24 V DC 10 mA, 24 V AC 20 mA
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
1) IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation
(PELV).
5. General Specifications
VLT
®
AutomationDrive FC 300 Instruction
Manual
84