FC 300 Operating Instructions
How to Programme
"
5-** Digital In/Out
Par.
No.
#
Parameter description
Default value
(SR = Size Related)
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
5-0* Digital I/O mode
5-00 Digital I/O Mode
[0] PNP
All set-ups
FALSE
-
Uint8
5-01 Terminal 27 Mode
[0] Input
All set-ups
TRUE
-
Uint8
5-02 Terminal 29 Mode
[0] Input
All set-ups
x
TRUE
-
Uint8
5-1* Digital Inputs
5-10 Terminal 18 Digital Input
-
All set-ups
TRUE
-
Uint8
5-11 Terminal 19 Digital Input
-
All set-ups
TRUE
-
Uint8
5-12 Terminal 27 Digital Input
-
All set-ups
TRUE
-
Uint8
5-13 Terminal 29 Digital Input
-
All set-ups
x
TRUE
-
Uint8
5-14 Terminal 32 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-15 Terminal 33 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-16 Terminal X30/2 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-17 Terminal X30/3 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-18 Terminal X30/4 Digital Input
[0] No operation
All set-ups
TRUE
-
Uint8
5-3* Digital Outputs
5-30 Terminal 27 Digital Output
-
All set-ups
TRUE
-
Uint8
5-31 Terminal 29 Digital Output
-
All set-ups
x
TRUE
-
Uint8
5-32 Term X30/6 Digi Out (MCB 101)
-
All set-ups
TRUE
-
Uint8
5-33 Term X30/7 Digi Out (MCB 101)
-
All set-ups
TRUE
-
Uint8
5-4* Relays
5-40 Function Relay
-
All set-ups
TRUE
-
Uint8
5-41 On Delay, Relay
0.01 s
All set-ups
TRUE
-2
Uint16
5-42 Off Delay, Relay
0.01 s
All set-ups
TRUE
-2
Uint16
5-5* Pulse Input
5-50 Term. 29 Low Frequency
100 Hz
All set-ups
x
TRUE
0
Uint32
5-51 Term. 29 High Frequency
100 Hz
All set-ups
x
TRUE
0
Uint32
5-52 Term. 29 Low Ref./Feedb. Value
0.000
All set-ups
x
TRUE
-3
Int32
5-53 Term. 29 High Ref./Feedb. Value
SR
All set-ups
x
TRUE
-3
Int32
5-54 Pulse Filter Time Constant #29
100 ms
All set-ups
x
FALSE
-3
Uint16
5-55 Term. 33 Low Frequency
100 Hz
All set-ups
TRUE
0
Uint32
5-56 Term. 33 High Frequency
100 Hz
All set-ups
TRUE
0
Uint32
5-57 Term. 33 Low Ref./Feedb. Value
0.000
All set-ups
TRUE
-3
Int32
5-58 Term. 33 High Ref./Feedb. Value
SR
All set-ups
TRUE
-3
Int32
5-59 Pulse Filter Time Constant #33
100 ms
All set-ups
FALSE
-3
Uint16
5-6* Pulse Output
5-60 Terminal 27 Pulse Output Variable
-
All set-ups
TRUE
-
Uint8
5-62 Pulse Output Max Freq #27
SR
All set-ups
TRUE
0
Uint32
5-63 Terminal 29 Pulse Output Variable
-
All set-ups
x
TRUE
-
Uint8
5-65 Pulse Output Max Freq #29
SR
All set-ups
x
TRUE
0
Uint32
5-66
Terminal X30/6 Pulse Output
Variable
-
All set-ups
TRUE
-
Uint8
5-68 Pulse Output Max Freq #X30/6
SR
All set-ups
TRUE
0
Uint32
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
48
MG.33.A7.02 - VLT is a registered Danfoss trademark