FC 300 Operating Instructions
How to Programme
"
0-** Operation/Display
Par.
No.
#
Parameter description
Default value
4-set-up
FC 302
only
Change
during
operation
Conver-
sion
index
Type
0-0* Basic Settings
0-01 Language
[0] English
1 set-up
TRUE
-
Uint8
0-02 Motor Speed Unit
[0] RPM
2 set-ups
FALSE
-
Uint8
0-03 Regional Settings
[0] International
2 set-ups
FALSE
-
Uint8
0-04
Operating State at Power-up
(Hand)
[1] Forced stop,
ref=old
All set-ups
TRUE
-
Uint8
0-1* Set-up Operations
0-10 Active Set-up
[1] Set-up 1
1 set-up
TRUE
-
Uint8
0-11 Edit Set-up
[1] Set-up 1
All set-ups
TRUE
-
Uint8
0-12 This Set-up Linked to
[0] Not linked
All set-ups
FALSE
-
Uint8
0-13 Readout: Linked Set-ups
0
All set-ups
FALSE
0
Uint16
0-14 Readout: Edit Set-ups / Channel
0
All set-ups
TRUE
0
Int32
0-2* LCP Display
0-20 Display Line 1.1 Small
Speed [RPM]
All set-ups
TRUE
-
Uint16
0-21 Display Line 1.2 Small
Motor current [A]
All set-ups
TRUE
-
Uint16
0-22 Display Line 1.3 Small
Power [kW]
All set-ups
TRUE
-
Uint16
0-23 Display Line 2 Large
Frequency [Hz]
All set-ups
TRUE
-
Uint16
0-24 Display Line 3 Large
Reference [%]
All set-ups
TRUE
-
Uint16
0-25 My Personal Menu
-
1 set-up
TRUE
0
Uint16
0-3* LCP Custom Readout
0-30 Unit for User-defined Readout
[0] None
All set-ups
TRUE
-
Uint8
0-31 Min Value of User-defined Readout 0.00
All set-ups
TRUE
-2
Int32
0-32 Max Value of User-defined Readout 100.00
All set-ups
TRUE
-2
Int32
0-4* LCP Keypad
0-40 [Hand on] Key on LCP
[1] Enabled
All set-ups
TRUE
-
Uint8
0-41 [Off] Key on LCP
[1] Enabled
All set-ups
TRUE
-
Uint8
0-42 [Auto on] Key on LCP
[1] Enabled
All set-ups
TRUE
-
Uint8
0-43 [Reset] Key on LCP
[1] Enabled
All set-ups
TRUE
-
Uint8
0-5* Copy/Save
0-50 LCP Copy
[0] No copy
All set-ups
FALSE
-
Uint8
0-51 Set-up Copy
[0] No copy
All set-ups
FALSE
-
Uint8
0-6* Password
0-60 Main Menu Password
100
1 set-up
TRUE
0
Uint16
0-61 Access to Main Menu w/o Password [0] Full access
1 set-up
TRUE
-
Uint8
0-65 Quick Menu Password
200
1 set-up
TRUE
0
Uint16
0-66 Access to Quick Menu w/o Password [0] Full access
1 set-up
TRUE
-
Uint8
*
default setting
( )
display text
[ ]
value for use in communication via serial communication port
41
MG.33.A7.02 - VLT is a registered Danfoss trademark
Содержание FC 300
Страница 2: ...FC 300 Operating Instructions Index 81 2 MG 33 A7 02 VLT is a registered Danfoss trademark...
Страница 32: ...FC 300 Operating Instructions How to Install 32 MG 33 A7 02 VLT is a registered Danfoss trademark...
Страница 72: ...FC 300 Operating Instructions General Specifications 72 MG 33 A7 02 VLT is a registered Danfoss trademark...