background image

Correct position

Warning

Never swich on power 

to the coil when it is 

dismounted from the valve. 

There is a danger the coil 

may be damaged and a risk 

of injuries and burns.

Installation Guide

Solenoid Valve

Types EVUL 1 – EVUL 8, EVU 1 – EVU 8, EVUB and EVUF 

 

DKRCC.PI.BD0.C5.02 / 520H7456 

1

03

2R

95

51

03

2R

95

51

Refrigerants: 

R744, R22/R407C, R404A/R507, 

R410A, R134a, R407A, R23.

For other refrigerants, please 

contact Danfoss.

Max. opening differential

pressure MOPD: 

Coil dependent

Note!

Danfoss recommends that a suitable

filter or filter drier (max. size of 

40 – 50 µm) is installed ahead of each 

solenoid valve to keep scale, solder 

material and other foreign dirt and 

particles out of the valve.

Be sure that 

the O-ring is 

in place

Max. temperature of medium: 

     -40 – 105 °C (-40 – 220 °F)

Ambient temperature: 

     -40 – 60 °C (-40° – 140 °F)

Max. working pressure PS/MWP:

– EVUL 1-8:  

90 barg / 1305 psig  

– EVU 1-8:  

70 barg / 1015 psig 

– EVUB and EVUF:  45.2 barg / 655 psig 

Click!

To ensure correct sealing between coil 

and valve make sure that the coil is fully 

clicked on to the valve.

Valve connection:

2 - 5 sec.

Cobber tube:

10 - 15 sec.

Valve connection: 

max. 700 °C (1300 °F)