DKRCE.PI.RL0.O2.02 / 520H11062 | 4
© Copyright Danfoss | Published by AZ | 2016.04
Installation guide | ERC 213
Installation guide - ERC 213
Danf
oss
80G138.01
Sair
DI1 DI2
Sair
DI1 DI2
Sair
DI1 DI2 S5
APP 1
APP 2/3
APP 4/5
DO1
DO2 DO3
DO1
DO3
DO2
DO1
DO3
DO2
Danf
oss
80G115.01
6 - Basic functions
Adjusting the setpoint temperature
Initiate a manual defrost
Initiate a pull down
View an active alarm
Unlock keyboard
(short press)
SET
: adjust the setpoint temperature.
UP/DOWN
: change the temperature setpoint (in setting mode the setpoint flashes).
DEFROST
: press for 3 seconds to initiate a defsost.
DEFROST
: press for 3 seconds to stop manual defrost.
The DEFROST icon is shown during defrost.
PULL DOWN
: press for 3 seconds to initiate pull down.
“
Pud
”: is shown for 3 seconds to indicate pull down.
The
PULL DOWN
icon flashes during pull down.
PULL DOWN
: press for 3 seconds to stop pull down.
Temperature and alarm codes alternate flashes until the alarm is resolved.
The alarm bell is shown.
- After 5 minutes of inactivity, the keypad will be locked (if P76 = YES).
- When the keypad is locked, if any key is selected, “
LoC
” appears on the display.
- Press
UP
and
DOWN
buttons simultaneously for 3 seconds to unlock the keyboard. “unl” is displayed for 3 seconds.
SET
: saves the temperature setpoint.
7 - Default application settings
App
Mode Description
Temp.
Def. type
Def. end
App 0
Cooling None (no preset application)
App 1
Cooling Medium temperature ventilated refrigeration units with timed natural defrost
(2 – 6 °C)
Natural
Time
App 2
Cooling Medium temperature ventilated refrigeration units with timed electrical defrost
(0 – 4 °C)
Electrical
Time
App 3
Cooling Low temperature ventilated refrigeration units with timed electrical defrost
(-26 – -20 °C) Electrical
Time
App 4
Cooling
Medium temperature ventilated refrigeration units with electrical defrost
(by temperature)
(0 – 4 °C)
Electrical Temperature
App 5
Cooling
Low temperature ventilated refrigeration units with electrical defrost
(by temperature)
(-26 – -20 °C) Electrical Temperature
App 6
Cooling None (no preset application) with simplified parameter list
230 V AC
230 V AC