"t1A"
Min. -20.0 K
Max. 20.0 K
Default 0.0 K
Air Temperature Adjustment
(applies to non-Danfoss temperature sensors only)
This parameter is a relative value and allows adjustment of the control
sensor temperature.
For instance, at a measured temperature of 7*C and "
tAd
" set to -2 K,
the input from the control sensor will be 5*C instead.
"t2A"
"t3A"
Inputs and outputs are configurable
There are two steps:
1.
Define the type of sensor attached to the input:
- temperature: light/digital.
2. Define the application for the sensor:
- temperature: control/condenser/evaporator.
- light: ECO/display/both.
- motion
- digital: door sensor.
Please contact your local Danfoss representative for information about
default settings.
NOTE: coded sensors will impact on the number of possible
configurations.
For instance: Danfoss supplies only 2-pole defrost sensors, so input "
S3
"
will most likely be used as a defrost/evaporator temperature sensor input.
"S1C"
Default Stn
S1 Config/S1C
S2 Config/S2C
S3 Config/S3C
Available options are:
"
Stn
": for a standard temperature sensor NTC 5 K @ 25°C and TPE precision.
"
Htn
": for a high temperature sensor NTC 100 K @ 25°C.
"
Ldr
": for a light sensor (values given in Luminens).
"
dig
": for a digital sensor with simple ON/OFF indication
(motion, magnet, switch, buttom).
"S2C"
Default Stn
"S3C"
Default Stn
"S1A"
Default SCo
S1 Application/S1A
S2 Application/S2A
S3 Application/S3A
Available options are:
"
nC
": not connected.
"
SCo
": temperature control.
"
EuA
": evaporator temperature.
"
Con
": condenser temperature (Condenser cleaning).
"
AuS
": only for showing temperature on display.
"
Ldr
": light sensor, Luminens.
"
ECo
": external input to control ECO mode.
"
doC
": door contact, contact closed when door closed.
"
doo
": door contact, contact open when door closed.
"
Pir
": motion sensor (only "
S3
").
"S2A"
Default nC
"S3A"
Default nC
"diC"
Default non
DI Config
This is the digital input used for a digital sensor or bus communications.
"
non
": not used.
"
doC
": door contact, contact closed when door closed.
"
doo
": door contact, contact open when door closed.
"
ECo
": external input to control ECO mode.
"
Pir
": motion sensor. Passive infrared.
"o1C"
Default Con
D01 Config
Condenser relay will follow the compressor ON/OFF, it will be turned On whenever compressor is ON and turned off when com-
pressor is OFF.
"Con "
: condenser fan control
"
PiC
": pilot Relay (no zero cross) – if using pilot relay to control a
condenser, this option must be used instead of "
Con
".
User Guide | ERC 112D VSC Refrigeration Controller
© Danfoss | DCS (vt) | 2019.07
BC286552322855en-000201 | 21