"doF"
Min. -10.0 K
Max. 10.0 K
Default 0.0 K
Display Offset
This parameter is a relative value and allows the temperature displayed
to be different to the temperature measured.
For instance, at a measured temperature of 7°C and "
doF
" set to -2K, the
displayed temperature will be 5°C instead.
"dLt"
Min. 0 min
Max. 60 min
Default 15 min
Lock Time After Defrost
In order not to show a rising temperature during defrosting, the displayed
temperature is locked at the temperature shown at the start of the defrost
cycle for the number of minutes set in this parameter.
"
0
": no lock.
"SEC"
Min. no
Max. yes
Default no
Show Economy State
If set to "
yES
", this parameter causes the display to show ECO when the
system is in ECO mode.
If set to "
nO
", the temperature continues to be displayed.
"SSC"
Min. no
Max. yes
Default no
Show Pull down state
If set to "
yES
", this parameter causes the display to show SC when the
system is in pull down mode.
If set to "
nO
", the temperature continues to be displayed.
"SHo"
Min. no
Max. yes
Default no
Show Holiday
"
no
": display will show temperature or ECO mode during holiday mode.
"
yES
": display will show "
HoL
" during holiday mode.
"SdF"
Min. no
Max. yes
Default yes
Show Defrost
If set to "
yES
", this parameter causes the display to show DEF when the
system is in defrost mode. If set to "
nO
", the temperature continues to
be displayed.
"SCS"
Min. no
Max. yes
Default yes
Show compressor symbol
"
no
": compressor symbol will not show on display.
"
yES
": show compressor symbol on display.
"SFS"
Min. no
Max. yes
Default yes
Show Fan symbol
"
no
": san symbol will not show on display.
"
yES
": show fan symbol on display.
"SdS"
Min. no
Max. yes
Default yes
Show Defrost symbol
"
no
": defrost symbol will not show on display.
"
yES
": show defrost symbol on display.
"SES"
Min. no
Max. yes
Default yes
Show ECO symbol
"
no
": ECO symbol will not show on display.
"
yES
": show ECO symbol on display.
ALA
Alarm settings
"HAt"
Min. -100.0°C
Max. 200°C
Default 15.0°C
High Temp Alarm
Absolute value.
By setting "
HAt
" to the maximum alarms will be deactivated.
"LAt"
Min. -100.0°C
Max. 200°C
Default -50.0°C
Low Temp Alarm
Absolute value.
By setting "
LAt
" to the minimum value, alarms will be deactivated.
In most situations, the low alarm delay will be set to 0 to warn about
too low a temperature immediately.
"Htd"
Min. 0 min
Max. 240 min
Default 30 min
Alarm delay on high temperature alarm
The number of minutes to wait before sounding an alarm once the
high temperature alarm temperature is reached.
User Guide | ERC 112D VSC Refrigeration Controller
© Danfoss | DCS (vt) | 2019.07
BC286552322855en-000201 | 17