background image

DKRCI.PI.RP0.C1.02 / 520H8794 

© Danfoss A/S (RC-MDP/MWA), 2014-08

ENGLISH

Liquid Level Regulating principle

 

Fig. 3a: 
LOW

System configuration 

ICAD

Regulating principle 

Low

Level Signal setup   

AKS 4100

Fig. 3b: 
LOW

System configuration 

AKV/A

Regulating principle 

Low

Level Signal setup   

AKS 4100

Fig. 3c: 
LOW

System configuration 

AKV/A

Regulating principle 

Low

Level Signal setup   

AKS 4100

Fig. 3d:

 

HIGH

System configuration 

AKV/A

Regulating principle 

High

Level Signal setup   

AKS 4100

Necessary connections (fig. 4, 5 and 6)

Terminals:
28-29  Supply voltage 24 V a.c. or d.c.
1-7 

Signal from  level transmitter type  

 

AKS 4100/4100U 

or

7-10 

Signal from level transmitter type  

 

AKS 41

36-37  Expansion valve type AKV or AKVA  
 

(see note to the right)  

or

 

23-24  Expansion valve type: ICM with    
 ICAD
13-14  Switch function for start/stop of   
 

controller. If a switch is  

   

 

not connected, terminals 13 and 14  

 

must be shortcircuited.

Application dependent connections
(fig. 4, 5 and 6)

Terminals:
33-35   Relay for common alarm. 
 

Installer can choose between 

 

Normally Open (33-34) or Normally  

 

Closed (34-35) circuits. 

 

The relay will switch according to  

 

the programmed setting.

25-27  Relay for low level limit. 
 

Installer can choose between 
Normally Open (26-27) or Normally 
Closed (25-26) circuits. 

 

The relay will switch when the set 
value is passed. 

30-32  Relay for upper level limit. 
 

Installer can choose between 
Normally Open (30-31) or Normally 
Closed (31-32) circuits. 

 

The relay will switch when the set 
value is passed.

6-10 

ICM valve feedback signal from 
ICAD 0/4-20 mA

Note!

If AKV(A) is used, the power supply 
must cover the AKV(A) coil wattage 
additionally (see fig. 5).
AKV(A) Coil voltage must be the 
same as controller supply voltage 
AC or DC.

MASTER/SLAVE and I/O configuration 
(fig. 7b and 7c)

When more controllers are connected via 
CAN bus each end of the bus must be ter-
minated with a jumper between 15 and 16.

Control Panel (fig. 8)

The user interface of the control panel con-
sists of a multiline display and 4 individual 
push buttons: Enter button, Page up 
button, Page down button and Back 
button.

Fig. 8 shows the Home display image, 
which give the actual overview. This is the 
starting point for entering into menus, and 
you will revert to this image by pushing     
1 – 3 times (depending on actual position).  

Display (fig. 9)

The display itself show the state of 

Liquid 

level, Controller Mode

 (controller On/

Off), 

Valve opening degree, Lower level 

alarm

 (on = no alarm present) and 

Upper 

level alarm

 (off = no alarm present). 

Additional to the external connected alarm 
audio/video sources, a Bell symbol will 
flash in the upper right corner in case of an 
alarm.

To see more details on system perfor-
mance and setting of parameters, 2 
different main menu levels can be reached 
by operation of the push buttons. 

Содержание EKE 347

Страница 1: ...0 1 080G5000 2 110 5 70 60 63 Danfoss 80G74_ 01 2014 Liquid Level Regulating principle ICM with ICAD motor EKE 347 Danfoss 80G75_06 2014 AKS 4100 AKS 4100U Danfoss 80G76_06 2014 EKE 347 AKS 4100 AKS 4...

Страница 2: ...e display ModBUS 4 20 mA 24 V DC yellow blue orange ICAD 1st gen ICAD ICM feedback ICAD 2nd gen blue 24 V AC L N 1 2 3 yellow gray orange ICAD 1st gen pre 2010 ICAD 2nd gen 2010 yellow green brown bro...

Страница 3: ...C 2 NO 2 NO 1 C 1 NC 1 POWER SUPPLY AKV AKVA 24 V AC 20 15 VA 24 V DC 20 10 W Common Normally Open or Normally Closed Low Level Alarm Normally Open or Normally Closed High Level Alarm Normally Open or...

Страница 4: ...ication Open Close solenoid valve with coil 24V 230V AKS 4100 AKS 4100U Danfoss M84H0084_1 MASTER I O AKVA ICAD R120 CAN H CAN L GND 15 16 17 18 R120 CAN H CAN L GND 15 16 17 18 Jumper 15 16 Jumper 15...

Страница 5: ...mode Lower level alarm off pump on Upper level alarm off Power on 1st time Power on Setup Wizard A guided configuration of EKE 347 Home Image Log in Press and hold Short press on Reference Alarm setup...

Страница 6: ...the set value is passed 30 32 Relay for upper level limit Installer can choose between Normally Open 30 31 or Normally Closed 31 32 circuits The relay will switch when the set value is passed 6 10 ICM...

Страница 7: ...no alarm is active Level signal out of range hours minutes Standby mode hours minutes Detailed status Controller state Stop Manual Auto Slave IO Actual level 0 0 100 Actual reference 0 0 100 Actual OD...

Страница 8: ...ndication level OD R RW RW D Level Login timeout 0 120 min R RW RW 10 min Backlight timeout 0 120 min RW RW RW 2 min Password daily 3 digit 0 999 N A N A RW 100 Password service 3 digit 0 999 N A N A...

Страница 9: ...R R D Actual OD C R R R D Manual Mode On Off R RW RW D Off Manual OD 0 100 R RW RW D 50 0 Manual low alarm Off On R RW RW D Off Manual high alarm Off On R RW RW D Off Manual common alarm Off On R RW...

Страница 10: ...a to e 1 Language You can select any of these 9 languages English Chinese Portuguese Russian Spanish French Italian German Arabic 2 System configuration Select any of these 5 predefined configura tion...

Страница 11: ...Danfoss A S RC MDP MWA 2014 08 DKRCI PI RP0 C1 02 520H8794 11...

Страница 12: ...12 DKRCI PI RP0 C1 02 520H8794 Danfoss A S RC MDP MWA 2014 08 www danfoss com ir...

Отзывы: