DKRCC.PI.RR0.A3.02          

                                                                                   

    

© Danfoss A/S (AC-MCI / sw), 2016-12

Connecting external display EKA 164A

To setup the EKD 316C an EKA 164A display is needed. The display can be used not only for setting up the

necessary parameter but also to use as an external display during operating to show the important 

parameters i.e. opening degree of the valve, superheat etc.

Important Note:

•  Max. distance between controller and display is 30 m.

 

•  The supply voltage to the display must be maintained at 12 V ± 15%.

•  Terminal resistor of 120 Ohm is recomanded at both sides of the wire for  

        length longer than 1 m to prevent electrical noice.

L = max. 30 m

EKA 164A         

 

EKD 316 C 

EKD 316C

Dan

fo

ss

84B3192.11

9

10

12

11

13

12 V

A+

B-

R

R

Warning

Separate the sensor and digital input cables as much as possible (at least 3 cm) from the power cables to  

the loads to avoid possible electromagnetic disturbance. Never lay power cables and probe cables in the 

same conduits (including those in the electrical panels).

R = 120 Ohm,  min. 0.25 Watt

EKA 164A

Cable and wiring

•  The cable distance between the controller and the valve depends on many factors like shielded/unshielded cable,  

  the wire size used in the cable, the output power for the controller and EMC. In general, for the cable distance upto 

  10 m, it is recommended to use cable with wire size 22AWG or lower. For cable distance up to 30 m, wire diameter  

  of 20 AWG or lower is recommended.
•  In case of electrical noises in the system, use cable filter AK 211.

•  Keep controller and sensor wiring well separated from mains wiring. Minimum recommended distance 30mm. 

•  Connecting sensors by wires more than 6 m long may decrease the accuracy of measured values.

•  Sensors and secondary (output) of transformer may not be grounded simultaneously.

Connecting Modbus

•  For the modbus cable, it is best to use  24 AWG shielded twisted-pair cable with a shunt capacitance of 

  16 pF/ft and 100Ω impedance.

•  The controller provides an insulated RS485 communication interface which is connected to terminals 9 to 11 

  (see connection overview).

•  The max. permissible number of devices simultaneously connected to RS485 output is 32 of full load device.  

    The maximum length of RS485 cable is 1000 m.

•  Termination resistors 120 Ohm for terminal devices are recommended for length > 1 m.  

  In EKD 316C communication frequency (baudrate) can be one of the following: 

  9600 baud, 19200 baud and 38400 baud.

•  The only available fixed communication settings in EKD 316C are 8 data bit, EVEN parity and 1 stop bit.  

  The default unit address is 240 which, can be changed using  parameter “03 unit address”.

Detail explanation on Modbus installation and software parameter setting can be found on 

Installation guide RC8AC602 and manual DKRCC.PS.RI0.F1.02.

Modbus

A+
B-
Not in use
Gnd

Danfoss

84N404.10

Содержание EKD 316C Colibri

Страница 1: ...put and output signals Power consumption Controller ETS C KVS C ETS KVS CCM CCMT 5 VA 7 2 VA 1 3 VA Input signal Ri mA 400 Ohm V 50 kOhm Current signal 4 20 mA or 0 20 mA Voltage signal 0 10 V or 1 5...

Страница 2: ...ble and avoid spiral paths enclosing power devices Separate from inductive loads and power cables to avoid possible electromagnetic noises Avoid touching or nearly touching the electronic components f...

Страница 3: ...oltage will close the ETS valve if the controller looses its supply voltage The battery voltage must not be connected from terminals 1 and 2 Power of the battery lower than 16 5 V will trigger the low...

Страница 4: ...ication dependent optional Connections A Connection for standalone controller B Connection for Valve Driver using analog signal Power supply 24 V AC DC Battery back up Temperature sensor S2 Temperatur...

Страница 5: ...KD 316C Danfoss 84N401 10 Danfoss 60G496 10 Evaporator outlet Conductive paste Important Note Mount sensor on a clean surface without any paints Remember to put on heat conducting paste and insulate t...

Страница 6: ...o use cable with wire size 22AWG or lower For cable distance up to 30 m wire diameter of 20 AWG or lower is recommended In case of electrical noises in the system use cable filter AK 211 Keep controll...

Страница 7: ...in EKD 316C is 16 i e non It is neccesary to define correct valve in Valve type i e parameter n03 The overview of the valve types has been defined in section valve overview Valve overview n03 EKA 164...

Страница 8: ...gnal check the parameter list Select valve type n03 17 valve type ETS C 17 for other valve types refer to valve overview table To start the controller in Valve driver mode Set r12 ON For detail parame...

Страница 9: ...R W 0 100 0 0 1 o56 Reg type 1 Normal 2 With inner loop 2076 R W x 1 2 1 1 1 o61 Appl mode 1 Valve driver mode using analogue signal 2 Superheat regulation 2077 R W x 1 2 2 2 1 Valve n03 Valve type Re...

Страница 10: ...00 10 n10 Min SH 3021 R W 1 100 6 60 10 n11 MOP bar max off 3013 R W 0 200 20 200 10 n15 Start time sec 3017 R W 1 90 0 0 1 n17 MinOdAtStart 3012 R W 0 100 0 0 1 n18 Stability 3014 R W 0 10 5 5 1 n19...

Отзывы: