User Guide | Interface, EKC 366 

© Danfoss | DCS (ADAP-KOOL®) | 2015-11

DKRCI.PS.RP0.C1.02  | 6

Data

Ordering

Type

Function

Code No.

EKC 366

Interface module

084B7076

EKA 173

Data communication module (ac-

cessories), (FTT 10 module)

084B7092

EKA 174

Data communication module (ac-

cessories), (RS 485 module)

with galvanic separation

084B7124

Necessary connections

Terminals:

25-26  Supply voltage 24 V a.c. 80 VA

17-18  Signal from NTC sensor in valve

23-24  Supply to valve’s PTC resistance

Control signal, if applicable

 (see also o10)

Either terminals:

15-16 

Voltage signal

or

18-19 

Current signal

Data communication, if applicable

Terminals:

3-4  

Mount only, if a data communication module has been 
mounted.

It is important that the installation of the data communi-

cation cable be done correctly. Cf. separate literature No. 
RC8AC...

Connections

Supply voltage

24 V a.c. +/-15% 50/60 Hz, 80 VA

(the supply voltage is galvanically separated 

from the input and output signals)

Power consumption

Controller

Valve

5 VA

75 VA

Input signal 

4-20 mA, 0-20 mA, 0-10V d.c. or

2-10 V d.c. 

Actuator

Input

Temperature signal 

from sensor in actua-

tor

Output

Pulsating 24 V a.c. to 

actuator

Data communication

Possible to connect a data communication 

module

Ambient temperature

During operation

During transport

-10 - 55°C

-40 - 70°C

Enclosure

IP 20

Weight

300 g

Mounting

DIN rail

Display

LED, 3 digits

Terminals

max. 2.5 mm

2

 multicore

Approvals

EU Low Voltage Directive and EMC demands re 

CE-marking complied  with.

LVD-tested acc. to EN 60730-1 and  EN 60730-

2-9

EMC-tested acc. to EN 50081-1 and EN 50082-2

Data communication

Valves: 

Kindly refer to catalogue RK0YG

Содержание EKC 366

Страница 1: ...n of the pressure in the valve and the interface module will keep this temperature constant The media temperature is regulated by a PLC or similar device Here the interface module receives a variable...

Страница 2: ...suction pressure from the compressor this feedback will produce the result that the evaporating pressure is kept constant In conjunction with the controller an electronic constant pressure valve is t...

Страница 3: ...tuator Ref Sundry configurations Miscellaneous External signal Here you set the signal that is to be connected to the controller 0 no signal 1 4 20 mA 2 0 20 mA 3 0 10 V 4 2 10 V o10 AI Type Frequency...

Страница 4: ...conds the controller automatically returns to its setting and it again shows the valve s actual temperature Set one of the other menus 1 Push the upper button until a parameter is shown 2 Push one of...

Страница 5: ...he actuator temperature cor responding to the required evaporating temperature push Set the value in the controller as mentioned under Set the valve s basic temperature reference The two curves are sh...

Страница 6: ...he installation of the data communi cation cable be done correctly Cf separate literature No RC8AC Connections Supply voltage 24 V a c 15 50 60 Hz 80 VA the supply voltage is galvanically separated fr...

Страница 7: ...operated from the various menu displays The programme will for example upload all the col lected tempera ture values once a day With a simple change over the values can also be shown in a trend diagr...

Страница 8: ...Danfoss reserves the right to alter its products without notice This also applies to products already on order provided that such alternations can be made without subsequential changes being necessar...

Отзывы: